44
PERFORMANCE DATA (cont)
ALTITUDE COMPENSATION*
581B036-072
*
As the height above sea level increases, there is less oxygen per cubic foot of air.
Therefore, heat input rate should be reduced at higher altitudes.
†Orifices available through your Bryant distributor.
ALTITUDE COMPENSATION*
581B090-150
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher
altitudes.
†Orifices available through your local Bryant distributor.
ALTITUDE DERATING FACTOR*
581B036-150
*Derating of the unit is not required unless the heating value of the
gas exceeds the values listed in the table above, or if the elevation
exceeds 6000 ft. Derating conditions must be 4% per thousand ft
above sea level. For example, at 4000 ft, if the heating value of the
gas exceeds 1000 Btu/ft
3
, the unit will require a 16% derating. For
elevations above 6000 ft, the same formula applies. For example, at
7000 ft, the unit will require a 28% derating of the maximum heating
value per the National Fuel Gas Code.
ELEVATIO
N
(ft)
72,000 AND 115,000/
60,000 and 90,000
BTUH NOMINAL
INPUT*
150,000/120,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
0-2,000
33/38
43/45
30/32
38/42
2,000
34/39
43/46
30/33
39/42
3,000
35/40
44/47
31/34
40/43
4,000
36/41
44/47
32/35
41/43
5,000
36/41
44/48
33/35
42/43
6,000
37/42
45/48
34/36
43/44
7,000
37/42
45/49
35/37
43/44
8,000
38/43
46/49
36/37
44/45
9,000
39/43
47/50
37/38
44/46
10,000
41/44
48/50
38/40
45/47
11,000
43/45
48/51
39/41
45/48
12,000
44/45
49/51
40/42
46/49
13,000
44/46
49/52
41/43
47/49
14,000
45/47
50/52
42/43
47/50
ELEVATION
(ft)
125,000-224,000 BTUH
NOMINAL INPUT
250,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
0-2,000
31
41
30
38
2,000
32
42
30
39
3,000
32
42
31
40
4,000
32
42
32
41
5,000
33
43
33
42
6,000
34
43
34
43
7,000
35
44
35
43
8,000
36
44
36
44
9,000
37
45
37
44
10,000
38
46
38
45
11,000
39
47
39
45
12,000
40
47
40
46
13,000
41
48
41
47
14,000
42
48
42
47
ELEVATION
MAXIMUM HEATING VALUE
(Btu/ft
3
)
0-2000
1100
2001-3000
1050
3001-4000
1000
4001-5000
950
5001-6000
900