GAS HEATING SYSTEM
General
The heat exchanger system consists of a gas valve feeding
multiple inshot burners off a manifold. The burners fire
into matching primary tubes. The tubes exit into the
collector box, then into the induced draft fan wheel inlet.
The induced fan wheel discharges into a flue passage and
flue gases exit out a flue hood on the side of the unit. The
induced draft fan motor includes a Hall Effect sensor
circuit that confirms adequate wheel speed via the
Integrated Gas Control (IGC) board. Safety switches
include a Rollout Switch mounted at the top of the burner
compartment. A limit switch is mounted through the side
of the fan deck, over the tubes. The vestibule plate faces
the tubes. See Figs. 45 and Fig. 47.
ROLLOUT
SWITCH
GAS
VALVE
SPARK
IGNITER
FLAME SENSOR
MANIFOLD PRESSURE
TAP
C10334
Fig. 45
−
Burner Section Details
CAPACITOR
INDUCER
HOUSING
INDUCER
WHEEL
INDUCER
COOLING FAN
INDUCER
MOTOR
C10335
Fig. 46
−
Inducer Assembly
SIDE SHOT
LIMIT SWITCH
DOWN SHOT
LIMIT SWITCH
C12592
Fig. 47
−
Limit Switch Locations
Fuel Types and Pressures
Natural Gas
The 580J unit is factory
−
equipped for use with Natural
Gas fuel at elevation under 2000 ft (610 m). See section
Orifice Replacement for information in modifying this
unit for installation at elevations above 2000 ft (610 m).
Gas line pressure entering the unit’s main gas valve must
be within specified ranges. Adjust unit gas regulator valve
as required or consult local gas utility. See Table 8.
Table 8 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL
UNIT SIZE
MIN
MAX
580J
All
4.0 in. wg
(996 Pa)
13.0 in. wg
(3240 Pa)
Manifold pressure is factory
−
adjusted for NG fuel use.
Adjust as required to obtain best flame characteristic. See
Table 9.
Table 9 – Natural Gas Manifold Pressure Ranges
UNIT
MODEL
UNIT
SIZE
HIGH
FIRE
LOW
FIRE
RANGE
580J
All
3.0 in. wg
(747 Pa)
2.0 in. wg
(498 Pa)
Reference MRT unit
nameplate for range
ratings
Liquid Propane
Accessory packages are available for field
−
installation
that will convert the 580J unit to operate with Liquid
Propane (LP) fuels. These kits include new orifice spuds,
new springs for gas valves and a supply line low pressure
switch. See section on Orifice Replacement for details on
orifice size selections.
Fuel line pressure entering unit gas valve must remain
within specified range. See Table 10.
Table 10 – Liquid Propane Supply Line Pressure
Ranges
UNIT MODEL
UNIT SIZE
MIN
MAX
580J
All
11.0 in. wg
(2740 Pa)
13.0 in. wg
(3240 Pa)
Manifold pressure for LP fuel use must be adjusted to
specified range. Follow instructions in the accessory kit to
make initial readjustment. See Table 11.
Table 11 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL
UNIT SIZE
HIGH FIRE
LOW FIRE
580J
All
11.0 in. wg
(2740 Pa)
7.3 in. wg
(1817 Pa)
Summary of Contents for 580J D17
Page 81: ...81 APPENDIX IV WIRING DIAGRAMS cont C160042 Fig 73 580J D17 D28 Power Diagram 208 230 3 60 ...
Page 82: ...82 APPENDIX IV WIRING DIAGRAMS cont C160043 Fig 74 580J D17 D28 Power Diagram 460 3 60 ...
Page 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C160044 Fig 75 580J D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 APPENDIX IV WIRING DIAGRAMS cont C160049 Fig 80 RTU OPEN Wiring Diagram ...