Bryant 569C Installation, Start-Up And Service Instructions Manual Download Page 2

NOTE:

If vibration isolators are required for a particular in-

stallation, use corner weight information in Fig. 2 to make
proper selection.

I. LOCATE THE UNIT

A. Clearance

Maintain clearance around and above unit to provide mini-
mum distance from combustible materials, proper airflow, and
service access. Refer to Fig. 2 and 3.

Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces 0 inches.
b. Condenser coil, for proper airflow, 36 in. (914 mm) one side,

12 in. (305 mm) the other. The left or rear side receiving
the greater clearance is optional.

c. Overhead, 60 in. (1524 mm) to ensure proper condenser

fan operation.

d. Between units, control box side, 42 in. (1067 mm) per NEC

(National Electrical Code, U.S.A. Standard).

e. Between unit and ungrounded surfaces, control box side,

36 in. (914 mm) per NEC.

f. Between unit and block or concrete walls and other grounded

surfaces, control box side, 42 in. (1067 mm) per NEC.

Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Slab-mounted units should be at least 4 in. (102 mm) above
the highest expected water level (flood and runoff). Do not
use the unit if it has been under water.

II. RIG AND PLACE UNIT

Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by us-
ing unit frame as a reference. See Tables 1A and 1B and Fig. 4
for additional information. Operating weight is shown in
Tables 1A and 1B.

These units are designed for overhead rigging only. Rig with
packaging assembly and wood bumper strips in place to pre-
vent unit damage by rigging cable. As further protection for
coil faces, plywood sheets may be placed against sides of unit,
behind cables. Run cables to a central suspension point so
that angle from the horizontal is not less than 45 degrees.
Raise and set unit down carefully.

If it is necessary to roll unit into position, mount unit on lon-
gitudinal rails, using a minimum of 3 rollers. Apply force to
rails, not unit. 
If unit is to be skidded into position, place it
on a large pad and drag it by the pad. Do not apply any force
to unit.

Raise from above to lift unit from rails or pad when unit is in
final position.

Lifting holes are provided in base rails as shown in Fig. 4.
Refer to rigging instructions on unit.

IMPORTANT:

If unit has forklift protection skids, be sure to

remove forklift protection skids from under unit before set-
ting unit in place.

After unit is in position, remove shipping materials and rig-
ging skids.

III. COMPRESSOR MOUNTING

Compressors are shipped from the factory held down by 4 bolts.
After unit is installed, loosen each bolt until the snubber washer
can be moved with finger pressure (376B units only). See Fig. 5.

IV. UNIT REFRIGERANT PIPING CONNECTIONS

Suction connection is sweat with plastic cap; liquid connec-
tion is sweat with plastic cap. Refer to Table 2 for refrigerant
piping sizes. Follow standard piping practices.

A. Size Refrigerant Lines

Consider length of piping required between condensing unit
and evaporator, amount of liquid lift, and compressor oil
return. See Table 3 for design details and line sizing. Refer
to

evaporator

installation

instructions

for

additional

information.

NOTES:
1. Dimensions in [

] are in millimeters.

2. See Fig. 3 for additional information.

UNIT

WEIGHT CHART*

Std Unit

Corner

W

Corner

X

Corner

Y

Corner

Z

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

569C072

340

154

86

39

53

24

77

35

124

56

569C090

370

168

86

39

78

35

99

45

107

49

569C120

395

179

89

40

92

42

109

49

105

48

576B090

510

231

115

52

89

40

133

60

173

87

576B102

564

256

133

50

97

44

141

64

193

88

576B120

564

256

133

60

97

44

141

64

193

88

*Weights are for aluminum coils.

Fig. 2 — Weight Distribution

—2—

Summary of Contents for 569C

Page 1: ...otential for per sonal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert sym bol Danger identifies the most serious hazards which will result in severe personal injury or death Warning indicates a condition that could result in personal injury Caution is used to identify unsafe practices which would result in minor personal injury or product a...

Page 2: ...ides of unit behind cables Run cables to a central suspension point so that angle from the horizontal is not less than 45 degrees Raise and set unit down carefully If it is necessary to roll unit into position mount unit on lon gitudinal rails using a minimum of 3 rollers Apply force to rails not unit If unit is to be skidded into position place it on a large pad and drag it by the pad Do not appl...

Page 3: ... Drive Quantity Rpm 1 850 1 1100 Diameter in 26 26 Motor Hp NEMA 1 3 3 4 Nominal Airflow cfm 3800 6500 7000 6500 6500 6500 CONDENSER COIL Enhanced Copper Tubes Aluminum Lanced Fins Face Area sq ft 12 24 15 75 20 5 18 0 18 0 18 0 Storage Capacity lb 11 26 14 88 18 87 16 56 16 56 16 56 CONNECTIONS sweat Suction in 11 8 11 8 11 8 11 8 11 8 11 8 Liquid in 1 2 1 2 5 8 1 2 5 8 5 8 CONTROLS Pressurestat ...

Page 4: ... 660 660 Motor Hp NEMA 1 3 3 4 Nominal Airflow L s 1800 3050 3300 3050 3050 3050 CONDENSER COIL Enhanced Copper Tubes Aluminum Lanced Fins Face Area sq m 1 14 1 46 1 90 1 67 1 67 1 67 Storage Capacity kg 5 1 6 75 8 6 7 5 7 5 7 5 CONNECTIONS sweat Suction in 11 8 11 8 11 8 11 8 11 8 11 8 Liquid in 1 2 1 2 5 8 1 2 5 8 5 8 CONTROLS Pressurestat Settings kPa High Cutout 2937 6 48 Cut in 2206 6 138 Low...

Page 5: ...r The left or rear side getting the greater clearance is optional b Overhead 60 in 1524 to assure proper condenser fan operation c Between units control box side 42 in 1067 per NEC National Electrical Code U S A Standard d Between unit and ungrounded surfaces con trol box side 36 in 914 per NEC e Between unit and block or concrete walls and other grounded surfaces control box side 42 in 1067 per N...

Page 6: ... 3 7 48 3 2 1 576B090 60 18 3 7 48 3 2 1 576B102 65 19 8 7 48 3 2 1 576B120 65 19 8 7 48 3 2 1 NOTE Values shown are for units operating at 45 F 7 2 C saturated suction and 95 F 35 C entering air V ELECTRICAL CONNECTIONS WARNING The unit cabinet must have an uninter rupted unbroken electrical ground to minimize the pos sibility of personal injury if an electrical fault should occur This ground may...

Page 7: ...minimum For 50 to 75 ft 15 2 to 22 9 m use no 16 AWG 1 30 mm insulated wire 35 C minimum For over 75 ft 22 9 m use no 14 AWG 2 08 mm insulated wire 35 C minimum All wire larger than no 18 AWG 0 82 mm cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat 1 Connect thermostat wires to screw terminals of low volt age connection board 2 Pass the co...

Page 8: ...0 93 2 2 32 2 40 460 3 60 414 508 19 9 99 1 4 26 3 35 575 3 60 518 632 15 9 79 1 4 21 3 25 220 3 50 198 253 39 7 198 1 4 52 7 70 400 3 50 342 460 19 9 99 1 4 26 3 35 LEGEND CSA Canadian Standards Association FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection NEC National Electrical Code U S A Standar...

Page 9: ...ything inside terminal box 5 Never attempt to repair soldered connection while refrigerant system is under pressure 6 Do not use torch to remove any component Sys tem contains oil and refrigerant under pressure To remove a component wear protective goggles and proceed as follows a Shut off electrical power to unit b Recover refrigerant Relieve all pressure from system c Cut component connecting tu...

Page 10: ...4v indoor evaporator fan contactor to function A field supplied and installed liquid line valve connected between Terminals G and C will also open allowing the system to function in cooling As cooling demand is satisfied the ther mostat contacts break deenergizing the contactor causing the system to shut off The liquid line solenoid LLS valve closes minimizing the potential for refrigerant migrati...

Page 11: ...is Clean the outer surfaces with a stiff brush in the normal manner 6 Reposition the outer coil section attach the bracket re moved in Step 4 and remove the coil corner post from between the top panel and side panel Secure the sec tions together Install the coil corner post and replace all screws removed in Step 2 II LUBRICATION A Compressors Each compressor is charged with the correct amount of o...

Page 12: ...en compressor is not operating Close both compressor service valves if applicable when crank case heater is deenergized for more than 6 hours VII REFRIGERANT CHARGE Unit panels must be in place when unit is operating during charging procedure Unit is shipped with a holding charge only Weigh in 7 lbs 3 kg of R 22 to start unit Refer to GTAC II Module 5 Charging Recovery Recycling and Reclamation fo...

Page 13: ...Fig 14 Cooling Charging Chart 569C072 Fig 15 Cooling Charging Chart 569C090 120 and 576B090 102 120 13 ...

Page 14: ...shaft Tighten fan hub screws Motor not running Check power and capacitor 1 3 and 3 4 hp motor Motor bearings seized Replace motor Motor overload open Check overload rating Check for fan blade obstruction Motor burned out windings open Replace motor Compressor cycles on low pressure switch Evaporator fan running Filter drier plugged Replace filter drier Expansion valve power head defective Replace ...

Page 15: ...itch LPS Low Pressure Switch NEC National Electrical Code OFC Outdoor Condenser Fan Contactor OFM Outdoor Condenser Fan Motor OL Overload Relay QT Quadruple Terminal TB Terminal Block TDR Time Delay Relay TRAN Transformer Terminal Marked Terminal Unmarked Terminal Block Factory Wiring Field Power Wiring Fig 16 Typical 569C Wiring Schematic and Component Arrangement Fig 17 Typical 576B Wiring Schem...

Page 16: ......

Page 17: ......

Page 18: ...Copyright 1999 Bryant Heating Cooling Systems CATALOG NO 5356 902 ...

Page 19: ...N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN CONFIRMED Y N PIPING IS LIQUID LINE SOLENOID VALVE LOCATED AT THE EVAPORATOR COIL AS REQUIRED Y N HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR CONDENSER EVAPORATOR TXVs Thermostatic Expansion Valves SOLENOID VALVES FILTER DRIERS A...

Page 20: ...URE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEAVING CONDENSER AIR TEMP EVAP ENTERING AIR DB dry bulb TEMP EVAP ENTERING AIR WB wet bulb TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS L1 L2 L3 HAS REFRIGERANT CHARGE BEEN ADJUSTED PER UNIT CHARGING CHART NOTES Copyright 1999 Bryant Heating Cooling Systems CATALOG NO 5356 902 CL 2 ...

Reviews: