POWER EXHAUST/
BAROMETRIC RELIEF
(ACCESSORY ONLY)
UNIT
STD UNIT
WEIGHT
ECONOMIZER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
DIM A
DIM B
DIM C
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
ft-in.
mm
ft-in.
mm
ft-in. mm
559F180
1550
703
110
50
391
177
365
166
384
174
410
186
3-5
1041
3-6
1067
1-10
559
559F216
1650
748
110
50
399
181
384
174
402
182
439
199
3-4
1016
3-6
1067
1- 8
508
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in (
) are in millimeters.
3.
Center of Gravity.
4.
Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 7
8
-0
9
(2134) for coil removal. This dimension can be reduced to 4
8
-0
9
(1219)
if conditions permit coil removal from the top.
• Left side: 4
8
-0
9
(1219) for proper condenser coil airflow.
• Front: 4
8
-0
9
(1219) for control box access.
• Right side: 4
8
-0
9
(1219) for proper operation of damper and power exhaust if so
equipped.
• Top: 6
8
-0
9
(1829) to assure proper condenser fan operation.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/power ex-
haust as stated in Note #6, a removable fence or barricade requires no
clearance.
8. Dimensions are from outside of corner post. Allow 0
8
-
5
⁄
16
9
(8) on each side for top
cover drip edge.
Fig. 4 — Base Unit Dimensions, 559F180 and 216
—4—