Table 8 — Accessory/FIOP Static Pressure (in. wg) — 559F180
COMPONENT
CFM
4500
5000
6000
7200
7500
Economizer
0.04
0.05
0.07
0.09
0.10
Glycol Coil
0.22
0.26
0.35
0.44
0.46
Electric Heat (kW)
26/34
0.06
0.07
0.09
0.11
0.12
32
0.06
0.07
0.09
0.11
0.12
42/56
0.07
0.08
0.12
0.16
0.17
55
0.07
0.08
0.12
0.15
0.17
56/75
0.09
0.10
0.15
0.20
0.21
80
0.09
0.10
0.15
0.20
0.21
LEGEND
FIOP — Factory-Installed Option
NOTES:
1. The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm
and watts.
2. Heaters are rated at 208/240 v and 480 v.
Table 9 — Accessory/FIOP Static Pressure (in. wg) — 559F216-300
COMPONENT
CFM
5400
6000
7200
9000
10,000
11,250
Economizer
0.06
0.07
0.09
0.11
0.12
0.14
Glycol Coil
0.30
0.35
0.44
0.58
0.66
0.77
Electric Heat (kW)
26/34
0.08
0.09
0.11
0.15
0.17
0.20
32
0.08
0.09
0.11
0.15
0.17
0.20
42/56
0.11
0.12
0.15
0.19
0.21
0.24
55
0.11
0.12
0.15
0.19
0.21
0.24
56/75
0.14
0.15
0.20
0.24
0.26
0.29
80
0.14
0.15
0.20
0.24
0.26
0.29
LEGEND
FIOP — Factory-Installed Option
NOTES:
1. The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm
and watts.
2, Heaters are rated at 208/240 v and 480 v.
Table 10 — Fan Rpm at Motor Pulley Settings*
UNIT
559F
MOTOR PULLEY TURNS OPEN
0
1
⁄
2
1
1
1
⁄
2
2
2
1
⁄
2
3
3
1
⁄
2
4
4
1
⁄
2
5
5
1
⁄
2
6
180†
††
††
1179
1150
1121
1093
1064
1035
1006
978
949
920
891
180**
††
††
1559
1522
1488
1455
1422
1389
1356
1323
1289
1256
1227
216†
††
††
1095
1077
1058
1040
1021
1002
984
965
947
928
910
216**
††
††
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
240†
††
††
1225
1209
1187
1165
1143
1120
1098
1076
1053
1031
1002
240**
††
††
1458
1434
1407
1381
1354
1328
1301
1275
1248
1222
1193
300†
††
††
1283
1269
1247
1225
1203
1182
1160
1138
1116
1095
1066
300**
††
††
—
—
1551
1524
1497
1470
1443
1415
1388
1361
1332
*Approximate fan rpm shown.
†Indicates standard drive package.
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
NOTE: For speeds not listed above, field-supplied drives are required.