46
Standard or Single Speed Fan Operation
FAN TYPE = 1SPEED is not used on 551K units.
2 Speed Fan Operation
The W7220 controller has the capability to work with a system
using a 2 speed supply fan. The W7220 does not control the
supply directly but uses the following input status to determine
the speed of the supply fan and controls the OA damper to the
required position, see Table 14.
Table 14 — Fan Speed
The W (heating mode) is not controlled by the W7220 but it re-
quires the status to know where to position the OA damper for
minimum position for the fan speed.
The 2 speed fan delay is available when the system is pro-
grammed for 2 speed fan (in the System Setup menu item). The
2 speed fan delay is defaulted to 5 minutes and can be changed
in the Advanced Setup menu item. When the unit has a call for
Y1 In and in the free cooling mode and there is a call for Y2 In,
the 2-speed fan delay starts and the OA damper will modulate
100% open, the supply fan should be set to high speed by the
unit controller. See Table 15.
After the delay one of two actions will happen:
• The Y2 In call will be satisfied with the damper 100%
open and fan on high speed and the call will turn off
OR
• If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will be
enabled through Y1 Out or Y2 Out.
Table 15 — Economizer Operation - FAN TYPE = 2SPEED
*With stage 3 delay (STG3 DLY) in Advanced setup, COOL Y2-OUT will be turned ON after the delay time specified.
N/A = Not applicable
STATE
FAN SPEED
OCC
Low
Y1
Low
Y2
High
W
High
INPUTS
OUTPUTS
DEMAND
CONTROLLED
VENTILATION
(DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
W
(HEAT ON)
COOL
Y1-IN
COOL
Y2-IN
COOL
Y1-OUT
COOL
Y2-OUT
FAN SPEED
(reference
only)
DAMPER POSITION
OCCUPIED
UNOCCUPIED
NONE
NO
ON
N/A
N/A
OFF
OFF
HIGH
MIN POS H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
MIN POS L
Closed
OFF
ON
OFF
ON
OFF
LOW
MIN POS L
Closed
OFF
ON
ON
ON
ON
HIGH
MIN POS H
Closed
YES
ON
N/A
N/A
OFF
OFF
HIGH
MIN POS H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
MIN POS L
Closed
OFF
ON
OFF
OFF
OFF
LOW
MIN POS L to
Full Open
Closed to
Full Open
OFF
ON
ON
ON
OFF*
HIGH
MIN POS H to
Full Open
Closed to
Full Open
Below CO
2
Set
NO
ON
N/A
N/A
OFF
OFF
HIGH
VENTMIN H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
VENTMIN L
Closed
OFF
ON
OFF
ON
OFF
LOW
VENTMIN L
Closed
OFF
ON
ON
ON
ON
HIGH
VENTMIN H
Closed
YES
ON
N/A
N/A
OFF
OFF
HIGH
VENTMIN H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
VENTMIN L
Closed
OFF
ON
OFF
OFF
OFF
LOW
VENTMIN L to
Full Open
Closed to
Full Open
OFF
ON
ON
ON
OFF*
HIGH
VENTMIN H to
Full Open
Closed to
Full Open
Above CO
2
Set
NO
ON
N/A
N/A
OFF
OFF
HIGH
VENTMIN H to
VENTMAX H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
VENTMIN L to
VENTMAX L
Closed
OFF
ON
OFF
ON
OFF
LOW
VENTMIN L to
VENTMAX L
Closed
OFF
ON
ON
ON
ON
HIGH
VENTMAX H to
VENTMAX H
Closed
YES
ON
N/A
N/A
OFF
OFF
HIGH
VENTMIN H to
VENTMAX H
Closed
OFF
OFF
OFF
OFF
OFF
LOW
VENTMIN L to
VENTMAX L
Closed
OFF
ON
OFF
OFF
OFF*
LOW
VENTMIN L to
Full Open
Closed to
Full Open
OFF
ON
ON
ON
OFF*
HIGH
VENTMIN H to
Full Open
Closed to
Full Open
Summary of Contents for 551K 04N Series
Page 15: ...15 Fig 27 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab ...
Page 82: ...82 APPENDIX D WIRING DIAGRAMS Fig E 551K 04 06 208 230 1 60 Unit with RTU Open Controller ...
Page 83: ...83 APPENDIX D WIRING DIAGRAMS Fig F 551K 04 06 208 230 3 60 Unit with RTU Open Controller ...
Page 84: ...84 APPENDIX D WIRING DIAGRAMS Fig G 551K 04 06 460 575 3 60 Unit with RTU Open Controller ...
Page 85: ...85 APPENDIX D WIRING DIAGRAMS Fig H 551K 04 06 Power Wiring Diagram 208 230 1 60 ...
Page 86: ...86 APPENDIX D WIRING DIAGRAMS Fig I 551K 04 06 Power Wiring Diagram 208 230 3 60 ...
Page 87: ...87 APPENDIX D WIRING DIAGRAMS Fig J 551K 04 06 Power Wiring Diagram 460 575 3 60 ...
Page 89: ......