42
SETPOINTS
(CONT)
ERV OAT SP
††
32°F
0 to 50°F
increment by 1
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
EXH1 SET
50%
0 to 100%
Exhaust fan set point for single speed units. Based on OA Damper
position to activate power exhaust.
EXH1 L SET
65%
0 to 100%
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXH1 M SET
60%
0 to 100%
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only displays
if unit is set for 3 speed with 1 heat and 2 cool. Based on economizer
OA damper position to activate power exhaust.
EXH1 H SET
50%
0 to 100%
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXH2 L SET
80%
0 to 100%
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXH2 M SET
77%
0 to 100%
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays if
unit is set for 3 speed with 1 heat and 2 cool. Based on economizer
OA damper position to activate power exhaust.
EXH2 H SET
75%
0 to 100%
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
SYSTEM
SETUP
INSTALL
01/01/17
N/A
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
F
F or C
Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT
CONV
Conventional or
HP
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input
from thermostat or controller.
See Menu Note 4.
AUX2 IN
W
SD/W or
HP(O)/HP(B)
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for
W. Shutdown is not available in 2-speed fan mode. See Menu Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
FAN SPEED
2 speed
1 speed
2 speed
2SP H/C
3 speed
Sets the economizer controller operation based on 1 speed, 2 speed,
2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed in
AUX 2 In. See Menu Note 4.
FAN CFM
5000cfm
100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator
††
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an alarm signal
OCC
INPUT
INPUT or
ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24
vac is input “INPUT” to the OCC terminal. If no occupancy output from
the thermostat then change program to “ALWAYS” OR add a jumper
from terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD will
briefly flash YES and change to NO but all parameters will change to
the factory default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed
values.
ADVANCED
SETUP
MA LO SET
45°F
35 to 55°F;
Incremented by 10
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value).
FREEZE POS
CLO
CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ZERO
0ppm
0 to 500 ppm;
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN
2000ppm
1000 to 3000 ppm;
Increment by 10
CO
2
ppm span to match CO
2
sensor.
Table 12 — W7220 Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES
Summary of Contents for 551K 04N Series
Page 15: ...15 Fig 27 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab ...
Page 82: ...82 APPENDIX D WIRING DIAGRAMS Fig E 551K 04 06 208 230 1 60 Unit with RTU Open Controller ...
Page 83: ...83 APPENDIX D WIRING DIAGRAMS Fig F 551K 04 06 208 230 3 60 Unit with RTU Open Controller ...
Page 84: ...84 APPENDIX D WIRING DIAGRAMS Fig G 551K 04 06 460 575 3 60 Unit with RTU Open Controller ...
Page 85: ...85 APPENDIX D WIRING DIAGRAMS Fig H 551K 04 06 Power Wiring Diagram 208 230 1 60 ...
Page 86: ...86 APPENDIX D WIRING DIAGRAMS Fig I 551K 04 06 Power Wiring Diagram 208 230 3 60 ...
Page 87: ...87 APPENDIX D WIRING DIAGRAMS Fig J 551K 04 06 Power Wiring Diagram 460 575 3 60 ...
Page 89: ......