119
PERFORMANCE DATA
COOLING CAPACITIES
LEGEND
NOTES:
1.
Direct interpolation is permissible. Do not extrapolate.
2.
The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator coil
3.
The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC
.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
LEGEND
NOTES:
1.
Direct interpolation is permissible. Do not extrapolate.
2.
The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator coil
3.
The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC
.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
559F180 (15 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air Quantity — Cfm/BF
4500/0.10
5250/0.12
6000/0.14
6750/0.15
7500/0.16
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
57
62
67
72
57
62
67
72
75
TC
164
177
193
212
171
181
197
216
178
184
202
220
183
188
204
224
188
190.2
206
226
SHC
164
146
124
100
171
157
132
105
178
169
140
111
183
176
147
116
188
185
157
120
kW
13.6
14.0
14.4
15.0
13.9
14.2
14.6
15.1
14.1
14.3
14.7
15.2
14.3
14.4
14.9
15.4
14.4
14.5
14.9
15.4
85
TC
159
170
186
204
166
174
190
208
172
178
194
212
178
181
197
216
182
183
199
218
SHC
159
142
120
98
166
152
129
102
172
163
137
107
178
172
144
112
182
180
151
117
kW
14.8
15.2
15.6
16.1
15.1
15.3
15.8
16.3
15.3
15.5
15.9
16.5
15.5
15.6
16.1
16.6
15.6
15.7
16.1
16.7
95
TC
154
163
178
195
160
167
182
200
166
170
186
204
171
173
189
206
175
175
190
208
SHC
153
139
117
94
160
148
126
100
166
158
133
104
171
168
141
109
175
175
147
113
kW
16.1
16.4
16.9
17.4
16.3
16.6
17.0
17.6
16.6
16.7
17.2
17.7
16.7
16.8
17.3
17.8
16.9
16.9
17.4
17.9
105
TC
148
155
170
186
154
159
174
190
160
162
177
193
164
165
179
196
168
168
181
197
SHC
147
135
114
91
154
144
122
96
160
155
130
101
164
163
137
105
168
168
143
109
kW
17.5
17.6
18.2
18.7
17.7
17.8
18.3
18.8
17.9
17.9
18.5
18.9
18.1
18.1
18.5
19.1
18.3
18.2
18.6
19.1
115
TC
142
148
162
176
148
151
165
180
153
153
167
183
157
157
169
185
161
160
171
187
SHC
142
131
111
88
148
140
118
93
153
150
126
97
157
156
133
102
161
160
140
106
kW
18.9
19.0
19.5
20.0
19.1
19.1
19.7
20.2
19.3
19.2
19.8
20.2
19.5
19.4
19.9
20.4
19.6
19.5
19.9
20.4
118
TC
140
145
159
173
146
148
162
177
151
151
164
179
155
154
166
182
158
158
168
183
SHC
140
130
110
87
146
139
117
92
151
148
125
96
155
154
131
100
158
158
138
105
kW
19.3
19.4
19.9
20.4
19.5
19.5
20.0
20.6
19.7
19.6
20.2
20.6
19.9
19.8
20.2
20.8
20.1
19.9
20.4
20.8
120
TC
139
144
157
171
144
147
160
—
149
149
162
—
153
153
164
—
157
156
166
—
SHC
139
129
109
86
144
139
116
—
149
147
124
—
153
153
130
—
157
156
137
—
kW
19.6
19.6
20.2
20.6
19.8
19.8
20.2
—
20.0
19.9
20.4
—
20.2
20.0
20.4
—
20.4
20.2
20.6
—
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW —
Compressor Motor Power Input
ldb —
Leaving Dry-Bulb
lwb —
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
=
Wet-bulb temperature corresponding to
enthalpy of air leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
BYPASS FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
559F216 (18 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air Quantity — Cfm/BF
5400/0.095
6000/0.105
7000/0.120
8000/0.140
9000/0.150
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
57
62
67
72
57
62
67
72
75
TC
180
191
211
231
186
194
213
235
193
198
218
239
200
202
221
243
206
206.6
223
245
SHC
180
165
138
111
186
173
145
115
193
187
155
121
200
199
166
128
206
206
175
133
kW
14.3
14.6
15.2
15.7
14.5
14.7
15.3
15.9
14.8
14.9
15.4
16.0
15.0
15.1
15.6
16.2
15.2
15.2
15.7
16.3
85
TC
175
184
202
224
180
187
206
226
188
191
209
231
194
194
213
234
199
199
215
237
SHC
175
161
135
108
180
170
142
112
188
183
152
119
194
194
162
125
199
199
172
131
kW
15.5
15.8
16.3
16.9
15.7
15.9
16.5
17.1
16.0
16.1
16.6
17.2
16.2
16.3
16.8
17.4
16.4
16.4
16.9
17.5
95
TC
169
176
194
214
174
179
196
217
181
183
200
222
187
187
203
224
192
192
205
226
SHC
169
158
132
105
174
166
138
109
181
178
149
115
187
187
159
121
192
192
168
128
kW
16.8
17.0
17.5
18.2
17.0
17.1
17.7
18.3
17.3
17.3
17.8
18.5
17.5
17.5
18.0
18.6
17.7
17.7
18.1
18.7
105
TC
163
168
185
204
168
171
187
207
175
174
191
209
180
180
193
213
185
184
194
215
SHC
163
154
128
102
168
162
135
106
175
174
145
112
180
179
154
118
185
184
164
124
kW
18.2
18.3
18.8
19.4
18.4
18.4
18.9
19.6
18.6
18.6
19.1
19.7
18.8
18.8
19.2
19.9
19.0
19.0
19.3
19.9
115
TC
157
160
176
194
161
162
177
196
167
167
180
198
172
172
182
200
177
176
183
203
SHC
157
150
125
99
161
157
131
102
167
167
141
108
172
172
151
114
177
176
160
120
kW
19.6
19.6
20.1
20.7
19.8
19.8
20.3
20.9
20.1
20.0
20.4
21.0
20.3
20.2
20.5
21.1
20.5
20.3
20.5
21.2
118
TC
155
158
174
192
159
160
175
194
165
165
178
196
170
170
180
198
174
174
181
200
SHC
155
149
124
98
159
156
130
101
165
165
140
107
170
170
150
113
174
174
159
119
kW
20.1
19.9
20.4
21.1
20.2
20.0
20.5
21.1
20.5
20.3
20.7
21.3
20.7
20.5
20.7
21.4
20.9
20.7
20.9
21.5
120
TC
153
155
171
—
158
158
172
—
164
163
175
—
169
168
177
—
173
172
178
—
SHC
153
147
123
—
158
155
129
—
164
162
139
—
169
167
149
—
173
171
157
—
kW
20.4
20.3
20.9
—
20.5
20.5
20.9
—
20.8
20.7
21.1
—
21.0
20.9
21.1
—
21.2
21.1
21.2
—
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW —
Compressor Motor Power Input
ldb —
Leaving Dry-Bulb
lwb —
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
=
Wet-bulb temperature corresponding to
enthalpy of air leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
BYPASS FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
0
T
F
Q
0
04
-0
12
55
9F1
80-
30
0
Summary of Contents for 551A
Page 14: ...14 TYPICAL WIRING SCHEMATIC Single Fan Units Sizes 036 073 ...
Page 16: ...16 TYPICAL WIRING SCHEMATIC Sizes 155 300 ...
Page 29: ...29 BASE UNIT DIMENSIONS 558F036 072 0TFQ004 012 558F036 150 ...
Page 30: ...30 BASE UNIT DIMENSIONS 558F073 0TFQ004 012 558F036 150 ...
Page 31: ...31 BASE UNIT DIMENSIONS 558F090 102 120 150 0TFQ004 012 558F036 150 ...
Page 32: ...32 BASE UNIT DIMENSIONS 558F091 121 0TFQ004 012 558F036 150 ...
Page 74: ...74 BASE UNIT DIMENSIONS 551B036 072 0TFQ004 012 551B036 150 ...
Page 75: ...75 BASE UNIT DIMENSIONS 551B090 150 0TFQ004 012 551B036 150 ...
Page 133: ...133 BASE UNIT DIMENSIONS 558F180 210 0TFQ004 012 558F180 300 ...
Page 134: ...134 BASE UNIT DIMENSIONS 558F240 0TFQ004 012 558F180 300 ...
Page 135: ...135 BASE UNIT DIMENSIONS 558F300 0TFQ004 012 558F180 300 ...
Page 153: ...153 BASE UNIT DIMENSIONS 551A155 180 0TFQ004 012 551A155 180 ...