MODEL NUMBER NOMENCLATURE — 559F
ARI* CAPACITY RATINGS
LEGEND
*Air Conditioning and Refrigeration Institute.
NOTES:
1. Rated in accordance with ARI Standards 360-89 and 270-89.
2. The 559F300 is beyond the scope of the ARI Certification
Program.
3. ARI ratings are net values, reflecting the effects of circulating fan
heat.
4. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.
IPLV Standard:
80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
5. These units do not comply with ASHRAE 90.1-1999 efficiency
requirements.
AIR QUANTITY LIMITS
LOW OUTDOOR TEMPERATURE
OPERATING LIMITS (F)
UNIT
559F
NOMINAL
TONS
STANDARD
CFM
NET COOLING
CAPACITY
(Btuh)
TOTAL
WATTS
EER
SOUND
RATING
(dB)
IPLV
180
15
5250
176,000
19,813
8.9
88
9.6
216
18
6200
188,000
21,298
8.8
88
9.8
240
20
6600
220,000
25,146
8.7
95
8.9
300
25
7200
268,000
30,858
8.7
95
9.3
dB
—
Sound Levels (decibels)
db
—
Dry Bulb
EER —
Energy Efficiency Ratio
IPLV —
Integrated Part-Load Values
wb
—
Wet Bulb
UNIT 559F
MINIMUM CFM
MAXIMUM CFM
180
4500
7,500
216
5400
9,000
240
6000
10,000
300
7000
11,250
UNITS
TEMPERATURE
All
40
180 and 216 with Low Ambient Kit
10
240 and 300 with Low Ambient Kit
25
All with Head Pressure Control
–20
Nominal Tons
180
– 15
216
– 18
240
– 20
300
– 25
559F
– Standard Efficiency
Electric Cooling Unit
Fan Drive Position
(Standard Motor)
B
– Standard Low-Medium
Fan Drive Static Capability
D
– Alternate High Fan Drive
Static Capability
Voltage Designation
E
– 460-3-60
P
– 208/230-3-60
Electric Heaters
000
– No factory-installed electric heaters
Heat Type
X
– No Heat Installed
(Field-installed electric heaters available)
Factory-Installed
Outdoor Air and Other
Upgrade Options
C
– EconoMi$er
H
– Manual Outdoor-Air Damper
Design Series Code
AH
– Original Design Series
5 5 9 F E X 1 8 0 0 0 0 A H C B
NOTE:
The example model number 559FEX180000AHCB designates a 15-ton 460-3-60 volt electric cooling rooftop unit with scroll compressors,
TXVs, EconoMi$er and the standard low-medium fan drive static capability.
0
T
F
Q
0
04
-0
12
55
9F1
80-
30
0
Summary of Contents for 551A
Page 14: ...14 TYPICAL WIRING SCHEMATIC Single Fan Units Sizes 036 073 ...
Page 16: ...16 TYPICAL WIRING SCHEMATIC Sizes 155 300 ...
Page 29: ...29 BASE UNIT DIMENSIONS 558F036 072 0TFQ004 012 558F036 150 ...
Page 30: ...30 BASE UNIT DIMENSIONS 558F073 0TFQ004 012 558F036 150 ...
Page 31: ...31 BASE UNIT DIMENSIONS 558F090 102 120 150 0TFQ004 012 558F036 150 ...
Page 32: ...32 BASE UNIT DIMENSIONS 558F091 121 0TFQ004 012 558F036 150 ...
Page 74: ...74 BASE UNIT DIMENSIONS 551B036 072 0TFQ004 012 551B036 150 ...
Page 75: ...75 BASE UNIT DIMENSIONS 551B090 150 0TFQ004 012 551B036 150 ...
Page 133: ...133 BASE UNIT DIMENSIONS 558F180 210 0TFQ004 012 558F180 300 ...
Page 134: ...134 BASE UNIT DIMENSIONS 558F240 0TFQ004 012 558F180 300 ...
Page 135: ...135 BASE UNIT DIMENSIONS 558F300 0TFQ004 012 558F180 300 ...
Page 153: ...153 BASE UNIT DIMENSIONS 551A155 180 0TFQ004 012 551A155 180 ...