Table 18 – Dry Bulb Operation No DCV (CO
2
Sensor) -- 2 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
‐
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
None
No
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
24-v/On
0-v/Off
MIN POS L
Closed
On
On
High
24-v/On
24-v/On
MIN POS H
Closed
None
Yes
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
0-v/Off
0-v/Off
MIN POS L to Full-Open
Closed to Full-Open
On
On
High
DELAY
[
24-v/On
0-v/Off *
MIN POS H to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
[
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Table 19 – Dry Bulb Operation With DCV (CO
2
Sensor) -- 2 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
‐
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
Below set
No
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H
Closed
Yes
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN H to Full-Open
Closed to Full-Open
Above set
No
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L to VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to VENTMAX
Closed
Yes
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full-Open
Closed to Full-Open
On
On
High
DELAY
[
24-v/On
0-v/Off *
VENTMIN H to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
[
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Summary of Contents for 549J Series
Page 4: ...4 C160144 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Page 5: ...5 C160145 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Page 6: ...6 C10757A Fig 3 Unit Dimensional Drawing 09 Size Units ...
Page 7: ...7 C10758A Fig 3 Unit Dimensional Drawing 09 Size Unit cont ...
Page 40: ...40 a549J 001 Fig 44 Typical RTU Open Controller Wiring Diagram ...