EconoMi$er
R
2 —
The RTU Open controller is used with EconoMi$er 2 (option
or accessory) for outdoor air management. The damper
position is controlled directly by the RTU Open controller;
the EconoMi$er 2 unit has no internal logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
2
sensor
Outdoor air CO
2
sensor
Field Connections
Field connections for accessory sensors and input devices
are made to the RTU Open controller at plugs J1, J2, J4,
J5, J11 and J20. All field control wiring that connects to
the RTU Open controller must be routed through the
raceway built into the corner post as shown in Fig. 38.
The raceway provides the UL required clearance between
high and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU Open controller.
Connect to the wires to the removable PCB connectors
and then reconnect the connectors to the board.
Space Temperature (SPT) Sensors —
There are two types of SPT sensors available from Bryant,
resistive input non-communicating (T55, T56, and T59)
and Rnet communicating (SPS, SPPL, SPP, and SPPF)
sensors. Each type has a variety of options consisting of:
timed override button, set point adjustment, a LCD
screen, and communication tie in. Space temperature can
be also be written to from a building network or zoning
system. However, it is still recommended that return air
duct sensor be installed to allow stand-alone operation for
back-up. Refer to the configuration section for details on
controller configurations associated with space sensors.
S
33ZCT55SPT, space temperature sensor with override
button (T--55)
S
33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment (T--56)
S
33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment (T--59)
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conductor, twisted pair cable may be used.
Connect T--55:
See Fig. 51 for typical T--55 internal
connections. Connect the T--55 SEN terminals to the RTU
Open controller at J20--1 and J20--2. See Fig. 52.
2
3
4
5
6
1
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
C08201
Fig. 51 -- T--55 Space Temperature Sensor Wiring
SEN
SEN
J20-1
J20-2
C08460
Fig. 52 -- RTU Open T--55 Sensor Connections
Connect T--56:
See Fig. 53 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to the RTU Open
controller at J20--1, J20--2 and J20--3 per Fig. 54.
2
3
4
5
6
1
SW1
SEN
SET
Cool
Warm
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
BLK
(T56)
C08202
Fig. 53 -- T--56 Internal Connections
SEN
J20-1
J20-2
SEN
SET
Jumper
J20-3
SET
C08461
Fig. 54 -- RTU Open T--56 Sensor Connections
Summary of Contents for 548J*14D Series
Page 5: ...5 a548J 011 Fig 2 Unit Dimensional Drawing Size 14 Unit...
Page 6: ...6 a548J 012 Fig 2 Unit Dimensional Drawing Size 14 Unit cont...
Page 10: ...10 a548J 013 Fig 6 Roof Curb Details...
Page 17: ...17 a50 9707 Fig 26 Typical 548J Size 14 Control Wiring Diagram...
Page 43: ...43 a50 9711 Fig 49 RTU Open Controller System Wiring Diagram...