Table 12 – Damper Minimum Position Settings and Readings on Checkout Menu
Fan Speed
Demand Controlled Ventilation
(CO
2
Sensor)
Setpoints
Checkout
1
NO
MIN POS
VMAX---HS
1
NO
N/A
N/A
2
NO
MIN POS H
VMAX---HS
2
NO
MIN POS L
VMAX---LS
1
YES
VENT MIN
VMIN---HS
1
YES
VENT MAX
VMAX---HS
2
YES
VENT MIN H
VMIN---HS
2
YES
VENT MAX H
VMAX---LS
2
YES
VENT MIN L
N/A
2
YES
VENT MAX L
N/A
Sequence of Operation
Table 13 – Dry Bulb Operation No DCV (CO
2
Sensor) -- 1 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
‐
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
None
No
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
None
Yes
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off *
MIN POS to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
Table 14 – Dry Bulb Operation With DCV (CO
2
Sensor) -- 1 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
‐
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
Below CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN to Full-Open
Closed to Full-Open
Above CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN to VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN to VENTMAX
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
Summary of Contents for 548J*14D Series
Page 5: ...5 a548J 011 Fig 2 Unit Dimensional Drawing Size 14 Unit...
Page 6: ...6 a548J 012 Fig 2 Unit Dimensional Drawing Size 14 Unit cont...
Page 10: ...10 a548J 013 Fig 6 Roof Curb Details...
Page 17: ...17 a50 9707 Fig 26 Typical 548J Size 14 Control Wiring Diagram...
Page 43: ...43 a50 9711 Fig 49 RTU Open Controller System Wiring Diagram...