background image

INSTALLING TXV IN PLACE OF PISTON

1. Pump system down to 2 psig and recover refrigerant.

2. Remove hex nut from piston body. Use backup wrench on

fan coils.

3. Remove and discard factory-installed piston. Be sure Teflon

seal is in place.

4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.

NOTE:

If the piston is not removed from the body, TXV will not

function properly.

CAUTION:

To prevent damage to the unit, use a brazing

shield and wrap TXV with wet cloth or use heat sink
material.

5. Install TXV on indoor coil liquid line. Sweat swivel adapter

to inlet of indoor coil and attach to TXV outlet. Use backup
wrench to avoid damage to tubing or valve. Sweat inlet of
TXV, marked “IN” to liquid line. Avoid excessive heat
which could damage valve.

6. Install vapor elbow with equalizer adapter to suction tube of

line set and suction connection to indoor coil. Adapter has
a 1/4-in. male connector for attaching equalizer tube.

7. Connect equalizer tube of TXV to 1/4-in. equalizer fitting

on vapor line adapter.

8. Attach TXV bulb to horizontal section of suction line using

clamps provided. Insulate bulb with field-supplied insula-
tion tape. See Fig. 5 for correct positioning of sensing bulb.

9. Proceed with remainder of unit installation.

REPLACING TXV ON R-22 INDOOR COIL

1. Pump system down to 2 psig and recover refrigerant.

2. Remove coil access panel and fitting panel from front of

cabinet.

3. Remove TXV support clamp using a 5/16-in. nut driver.

Save the clamp.

4. Remove R-22 TXV using a backup wrench on flare

connections to prevent damage to tubing.

5. Using wire cutters, cut equalizer tube off flush with vapor

tube inside cabinet.

6. Remove bulb from vapor tube inside cabinet.

IMPORTANT:

Route the equalizer tube of Puron® TXV through

suction line connection opening in fitting panel prior to replacing
fitting panel around tubing.

7. Braze equalizer stub-tube closed. Use protective barrier as

necessary to prevent damage to drain pan.

8. Install TXV with 3/8-in. copper tubing through small hole

in service panel. Use wrench and backup wrench, to avoid
damage to tubing or valve, to attach TXV to distributor.

9. Reinstall TXV support clamp (removed in item 3).

10. Attach TXV bulb to vapor tube inside cabinet, in same

location as original was when removed, using supplied bulb
clamps (nylon or copper). See Fig. 5 for correct positioning
of sensing bulb.

11. Route equalizer tube through suction connection opening

(large hole) in fitting panel and install fitting panel in place.

12. Sweat inlet of TXV, marked

IN

to liquid line. Avoid

excessive heat which could damage valve.

13. Install vapor elbow with equalizer adapter to vapor line of

line set and vapor connection to indoor coil. Adapter has a
1/4-in. male connector for attaching equalizer tube.

14. Connect equalizer tube of TXV to 1/4-in. equalizer fitting

on vapor line adapter. Use backup wrench to prevent
damage to equalizer fitting.

15. Proceed with remainder of unit installation.

CAUTION:

Remove indoor coil piston if unit is to be

installed on system with a TXV metering device.

VII.

MAKING PIPING CONNECTIONS

WARNING:

Relieve pressure and recover all refrigerant

before system repair or final unit disposal to avoid
personal injury or death. Use all service ports and open all
flow-control devices, including solenoid valves.

CAUTION:

Do not leave system open to atmosphere

any longer than minimum required for installation. POE
oil in compressor is extremely susceptible to moisture
absorption. Always keep ends of tubing sealed during
installation.

CAUTION:

If ANY refrigerant tubing is buried, provide

a 6 in. vertical rise at service valve. Refrigerant tubing
lengths up to 36 in. may be buried without further special
consideration. Do not bury lines over 36 in.

CAUTION:

To prevent damage to unit or service valves

observe the following:
• Use a brazing shield
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the

Fig. 4—Check-Flo-Rater® Components (533G Use)

A01164

PISTON

TEFLON SEAL

PISTON RETAINER

13

16

–IN.

BRASS HEX
NUT

3

4

–IN. BRASS

HEX BODY

STRAINER

DISTRIBUTOR

COPPER TUBE

PISTON
RING

—3—

Summary of Contents for 533G

Page 1: ...e living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit...

Page 2: ... AND INSTALL PISTON RING 533G STANDARD If unit is to be installed with a piston metering device proceed as follows 1 Check indoor coil piston to see if it matches the required piston shown on outdoor unit rating plate If it does not match replace indoor coil piston with piston shipped with outdoor unit The piston shipped with outdoor unit is correct for any approved indoor coil combination 2 After...

Page 3: ...e to tubing or valve to attach TXV to distributor 9 Reinstall TXV support clamp removed in item 3 10 Attach TXV bulb to vapor tube inside cabinet in same location as original was when removed using supplied bulb clamps nylon or copper See Fig 5 for correct positioning of sensing bulb 11 Route equalizer tube through suction connection opening large hole in fitting panel and install fitting panel in...

Page 4: ...HOD The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the most positive way of assuring a system is free of air and liquid water See Fig 7 TRIPLE EVACUATION METHOD The triple evacuation method should be used when vacuum pump is only capable of pumping down to 28 in o...

Page 5: ...se of available 24v accessories may exceed the mini mum 40va power requirement Determine total transformer load ing and increase the transformer capacity or split the load with an accessory transformer as required IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc IX...

Page 6: ...IQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3 8 3 8 5 8 5 8 5 8 5 8 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 3 4 7 8 042 048 3 8 3 8 7 8 7 8 7 8 1 1 8 060 3 8 3 8 7 8 1 1 8 7 8 1 1 8 NOTES 1 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 50 ft horizontal or greater than ...

Page 7: ...nutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid near outdoor coil 4 Refer to unit rating plate for required subcooling tempera ture 5 Refer to Table 4 Find the point where required subcooling temperature intersects measure...

Page 8: ... IMPORTANT Before leaving job be sure to do the following 1 Ensure that all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 2 Tighten service valve stem caps to 1 12 turn past finger tight 3 Leave User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checkli...

Page 9: ... 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 40 75 77 79 81 83 85 87 89 91 24 VAC HOT R C W2 Y G R C RVS COOLING C W2 HP THERMOSTAT TYP...

Page 10: ...INE SOLENOID VALVE IS REQUIRED ON SOME UNITS SEE SPECIFIC UNIT INSTRUCTIONS 5 THERMOSTATS ARE FACTORY CONFIGURED WITH 5 MINUTE COMPRESSOR CYCLE PROTECTION AND 4 CYCLES PER HOUR LIMIT SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR DETAILS 6 TO STAGE ELECTRIC RESISTANCE HEAT CONSULT OUTDOOR THERMOSTAT INSTALLATION IN STRUCTIONS A97368 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTIO...

Page 11: ...sture from oil Do not leave Puron suction line filter driers in line longer than 72 hrs Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere Poe oils may cause damage to certain plastics and roofing materials Wrap all filter driers and service v...

Page 12: ... 2002 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 12 Printed in U S A ii533g181 Catalog No 5353 309 ...

Reviews: