background image

21

Table 13 -- 374RAN120 (cont)

OIL HEATING MODE

24 VAC INPUT (R) ON W ONLY

SW1---HEAT

DIP SWITCH POSITION

HEAT INPUT

(USGPH)

AIRFLOW (CFM)

EXTERNAL STATIC PRESSURE (IN WC)

0.2

0.5

0.7

0.9

A (1=OFF, 2=OFF)*

0.85

1417

1417

1417

1407

A (1=OFF, 2=OFF)**

1601

1601

1601

1590

A (1=OFF, 2=OFF)***

1204

1204

1204

1196

B (1=ON, 2=OFF)*

1.00

1674

1666

1658

1658

B (1=ON, 2=OFF)**

1892

1883

1874

1874

B (1=ON, 2=OFF)***

1423

1416

1409

1409

C (1=OFF, 2=ON)*

1.10

1826

1826

1826

1813

C (1=OFF, 2=ON)**

2063

2063

2063

2049

C (1=OFF, 2=ON)**

1552

1552

1552

1541

D (1=ON, 2=ON)

SAME VALUE AS A DIP SWITCH POSITION

CONTINUOUS FAN

24 VAC INPUT (R) ON G ONLY

SW2---COOL

DIP SWITCH POSITION

A/C SIZE

(TON)

AIRFLOW (CFM)

EXTERNAL STATIC PRESSURE (IN WC)

0.2

0.5

0.7

0.9

A (1=OFF, 2=OFF)*

5.0

1243

1259

1259

1251

A (1=OFF, 2=OFF)**

1367

1385

1385

1376

A (1=OFF, 2=OFF)***

1119

1133

1133

1126

B (1=ON, 2=OFF)*

4.0

989

995

977

959

B (1=ON, 2=OFF)**

1088

1095

1075

1055

B (1=ON, 2=OFF)***

890

896

879

863

C (1=OFF, 2=ON)*

3.5

871

871

843

831

C (1=OFF, 2=ON)**

958

958

927

914

C (1=OFF, 2=ON)**

784

784

759

748

D (1=ON, 2=ON)*

3.0

773

741

741

705

D (1=ON, 2=ON)**

850

815

815

776

D (1=ON, 2=ON)***

696

667

667

635

COOLING OR HEAT PUMP HEATING MODE --- SINGLE SPEED OR 2---SPEED HIGH

24 VAC INPUT (R) ON Y/Y2 AND O (FOR COOLING)

SW2---COOL

DIP SWITCH POSITION

A/C SIZE

(TON)

AIRFLOW (CFM)

EXTERNAL STATIC PRESSURE (IN WC)

0.2

0.5

0.7

0.9

A (1=OFF, 2=OFF)*

5.0

1738

1738

1738

1725

A (1=OFF, 2=OFF)**

1912

1912

1912

1898

A (1=OFF, 2=OFF)***

1564

1564

1564

1553

B (1=ON, 2=OFF)*

4.0

1333

1352

1352

1342

B (1=ON, 2=OFF)**

1466

1487

1487

1476

B (1=ON, 2=OFF)***

1200

1217

1217

1208

C (1=OFF, 2=ON)*

3.5

1154

1154

1145

1118

C (1=OFF, 2=ON)**

1269

1269

1260

1230

C (1=OFF, 2=ON)**

1039

1039

1031

1006

D (1=ON, 2=ON)*

3.0

992

997

974

974

D (1=ON, 2=ON)**

1091

1097

1071

1071

D (1=ON, 2=ON)***

893

897

877

877

NOTE: In cooling---dehumidification mode, with no 24VAC input to DH, the CFM is reduced 15%

COOLING OR HEAT PUMP HEATING MODE --- 2---SPEED LOW

24 VAC INPUT (R) ON Y1 AND O (FOR COOLING)

SW2---COOL

DIP SWITCH POSITION

A/C SIZE

(TON)

AIRFLOW (CFM)

EXTERNAL STATIC PRESSURE (IN WC)

0.2

0.5

0.7

0.9

A (1=OFF, 2=OFF)*

5.0

900

900

881

860

A (1=OFF, 2=OFF)**

990

990

969

946

A (1=OFF, 2=OFF)***

810

810

793

774

B (1=ON, 2=OFF)*

4.0

749

723

717

695

B (1=ON, 2=OFF)**

824

795

789

765

B (1=ON, 2=OFF)***

674

651

645

626

C (1=OFF, 2=ON)*

3.5

680

643

617

599

C (1=OFF, 2=ON)**

748

707

679

659

C (1=OFF, 2=ON)**

612

579

555

539

D (1=ON, 2=ON)*

3.0

595

576

539

511

D (1=ON, 2=ON)**

655

634

593

562

D (1=ON, 2=ON)***

536

518

485

460

NOTE: In cooling---dehumidification mode, with no 24VAC input to DH, the CFM is reduced 15%

*CFM with SW3---ADJ Dip Switch A Position

**CFM with SW3---ADJ Dip Switch B Position

***CFM with SW3---ADJ Dip Switch C Position

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: