background image

4

Table 1 – Minimum Clearances to Combustible Materials -- In. (mm)

UNIT APPLICATION

UPFLOW

DOWNFLOW

HORIZONTAL

Sides

Furnace

0 (0)

2 (51)

2 (51)

Supply Plenum and Warm---Air Duct Within 6 ft. (1.8 M) of

Furnace

1 (25)

2 (51)

1 (25)

Back

Service Clearance

0 (0)

1 (25)

4 (102)

Top

Furnace Casing or Plenum

2 (51)

2 (51)

2 (51)

Horizontal Warm---Air Duct Within 6 ft. (1.8 M) of Furnace

2 (51)

2 (51)

3 (76)

Flue

Pipe

Horizontally or Below Pipe

4 (102)

4 (102)

4 (102)

Vertically Above Pipe

9 (229)

9 (229)

9 (229)

Front

8 (203)

8 (203)

8 (203)

Bottom*

0 (0)

0 (0)

0 (0)

* For combustible floor, use approved subbase.
Note: Adequate service clearances should be provided over and above these dimensions as required.

The furnace should be located as close as possible to chimney or
vent in order to keep vent connections short and direct. The

furnace should also be located as near as possible to center of air
distribution system.

Step 2 — Location Relative to Cooling Equipment

When installing furnace with cooling equipment for year--round

operation, the following recommendations must be followed for
series or parallel airflow:

1. In series--airflow applications, coil is mounted after furnace

in an enclosure in supply--air stream. The furnace blower is

used for both heating and cooling airflow.

2. In parallel--airflow applications, dampers must be provided

to direct air over furnace heat exchanger when heat is
desired and over cooling coil when cooling is desired.

UNIT DAMAGE HAZARD

Failure to follow this caution may reduce the life of this unit.
The coil MUST be installed on air--discharge side of furnace.

Under no circumstances should airflow be such that cooled,

conditioned air can pass over furnace heat exchanger. This

will cause condensation in heat exchanger and possible

failure of heat exchanger. Heat exchanger failure due to

improper installation may not be covered by warranty.

CAUTION

!

IMPORTANT

: The dampers should be adequate to prevent cooled

air from entering furnace. If manually operated, dampers must be
equipped with a means to prevent operation of either cooling unit
or furnace unless damper is in full cool or heat position.

INSTALLATION

Step 1 — Air for Combustion and Ventilation

CARBON MONOXIDE, UNIT RELIABILITY HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
Installation of this furnace in an area where it will receive

contaminated combustion air must be avoided. Such

contamination would include the following: ammonia,

chlorine, hydrogen sulfide, halogenated hydrocarbons, carbon

tetrachloride, cleaning solvents, hydrochloric acid, water

softening chemicals, and similar chemicals.

!

WARNING

CARBON MONOXIDE, FIRE HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
Do not block combustion--air openings in the furnace. Any

blockage could result in improper combustion.

!

WARNING

Step 2 — General

This furnace should be installed in a location in which facilities for

ventilation permit satisfactory combustion of oil, proper venting,
and maintenance of ambient temperature at safe limits under

normal conditions of use. The location should not interfere with
proper circulation of air within the confined space. (See NFPA--31

or B139.)
In addition to air needed for combustion, process air shall be
provided as required for: cooling of equipment or material,

controlling dew point, heating, drying, oxidation or dilution, safety
exhaust, and odor control.
In addition to air needed for combustion, air shall be supplied for

ventilation, including all air required for comfort and proper
working conditions for personnel.
The barometric draft regulator (included with furnace) shall be
installed in same room or enclosure as furnace in such a manner as

to prevent any difference in pressure between regulator and

combustion--air supply.
Air requirements for operation of exhaust fans, kitchen ventilation

systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion--air

requirements.
The lack of a proper amount of combustion air can lead to serious

furnace operational problems. Some of these problems are:

1. Excessive oil burner after--drip and oil fumes.
2. Sooting.
3. Melted oil burner igniter/relay control.
4. Air band or air turbulator settings more open than normal.
5. Lockouts on start--up.

The requirements for combustion and ventilation air depend
upon whether furnace is located in a CONFINED or

UNCONFINED space.

Unconfined Space

An unconfined space must have at least 50 cu ft for each 1,000

BTUH of total input for all the appliances (such as furnaces,
clothes dryers, water heaters, etc.) in the space.
In unconfined spaces in buildings of conventional frame, brick, or

stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases. This

determination must be made on an individual installation basis and
must take into consideration the overall volume of unconfined

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: