background image

5

Two Stage

On\Off
Knob

INLET

OF

N

O

O

N

O

OFF

A07684

Fig. 3 -- Gas Control Valve

2. Have someone check the structure frequently during cold

weather to make sure it is warm enough to prevent pipes
from freezing. Instruct them to call a qualified service

agency to call to provide service, if required.

--or--

3. Install a reliable remote sensing device that will notify

somebody of freezing conditions within the home.

Winter Shutdown (90+ Furnaces)

If you go away during the winter months and do not leave the heat
on in your home, the plastic transition box and the condensate trap

on the furnace must be protected from freeze damage. (See Fig. 2)

1. Disconnect the 1/2” I.D. rubber hose from the vent drain fit-

ting (or tee) that is located downstream of the combustion
blower. Insert a funnel into the hose and pour four (4)

ounces of sanitary type (RV) antifreeze into the condensate
trap. Reconnect the 1/2” I.D. rubber hose to the stub on the
vent drain fitting. Secure with the hose clamp.

2. Disconnect the 5/8” I.D. rubber hose from the condensate

trap. Insert a funnel into the hose and pour four (4) ounces

of sanitary type (RV) antifreeze into the plastic transition
box. Squeeze the hose together near the end and quickly re-
connect the 5/8” I.D. rubber hose to the stub on the con-

densate trap. Secure with the hose clamp.

3. When you return home, your furnace will be ready to start,

as it is not necessary to drain the antifreeze from the furnace.

Furnace Maintenance

Have your furnace inspected and serviced on an annual basis

(before the heating season) by a qualified service agency.

Labeling

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Label all wires prior to disconnection when servicing controls.

Verify proper operation after servicing. Only qualified service

agencies should attempt electrical service.

!

WARNING

Pressure Switches

During regular yearly maintenance, check for cracks in any tubes
on the pressure switches.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Turn off electrical power to furnace before performing any

maintenance or removing panels or doors.

!

WARNING

Air Filters/Monthly

The air filter(s) should be inspected at least monthly and cleaned or
replaced as required. There are many types of filters that are

commonly used. Washable filters (constructed of aluminum mesh,
foam, or reinforced fibers) may be cleaned by soaking in mild

detergent and rinsing with water. The fiberglass disposable type

should be REPLACED before it becomes clogged. Other filter
types should be serviced in accordance with the manufacturer’s

recommendations.
Remember that dirty filters are the most common cause of

inadequate heating or cooling performance.

Replacement Filters

If the filter is not located at or within the furnace, it should be
located somewhere in the return--air duct system.
The recommended sizes and types of filters that may be used with
your furnace are based on the furnace’s heating gas input rate (and

cooling system capacity, if so equipped).
Replacement filters should be of the same type and size as the
original filters, to ensure adequate air flow and filtering. A

disposable low velocity filter can be replaced with a washable high
velocity type. Do not replace a high velocity filter with a

disposable low velocity filter, except as permitted below.
If a cleanable (high--velocity) filter(s) is to be replaced with a

disposable (low--velocity) filter(s), the airflow area of the filter(s)

must be doubled (i.e., a second filter of the same size must be
installed so that only half of the air goes through each filter). A

second return--air duct to the furnace may be required in which to
install the second filter. Modification of a furnace installation shall

comply with the local installation code and the furnace installation

instructions, and shall be made only by a Qualified Service
Agency.

NOTE

: Some filters are marked with an arrow to indicate the

proper direction of air flow through the filter. The air flow
direction will be towards the blower motor. Make sure filter is
installed correctly.

Filter Replacement

The filter may be installed inside the bottom of the furnace blower

compartment, or the filter(s) rack may be installed under the
furnace or on either or both sides of the furnace. A plastic end

cap(s) is inserted in the filter rack(s) after the filter(s) is installed.
The end cap keeps air from escaping around the open end of the

filter rack. See Fig. 4 and Fig. 5 for side and bottom locations.

Rack end cap is similar for bottom mounted filter rack.
Filter rack(s) attached to the outside of the furnace is made so the

filter simply slides out one end for removal.

359B

A

V

Summary of Contents for 359BAV

Page 1: ...ice agency should be contacted to inspect the furnace and to replace all gas controls control system parts electrical parts that have been wet or the furnace if deemed necessary CERTIFIED As an ENERGY...

Page 2: ...ze 5 On appliances with a draft hood check for spillage by hold ing a lighted match 2 50 8mm from the draft hood open ing Reference Fig 1 which shows a water heater draft hood Typical Gas Water Heater...

Page 3: ...have a Fan Switch with AUTO and ON settings On AUTO the Circulating Air Blower will cycle on off with the furnace on the heating speed unless a call for cooling is initiated Blower speed will correspo...

Page 4: ...ors 8 Turn ON all electrical power to the furnace 9 Set the thermostat to the desired temperature and the System Select Switch to HEAT The furnace will activate an igniter which lights the main burner...

Page 5: ...cleaned or replaced as required There are many types of filters that are commonly used Washable filters constructed of aluminum mesh foam or reinforced fibers may be cleaned by soaking in mild deterge...

Page 6: ...ace External Filter Rack A plastic end cap is inserted in the filter rack after the filter is installed The end cap keeps air from escaping around the open end of the filter rack See Fig 4 for removal...

Page 7: ...rs 800 900 20 x 25 508 x 635 1 Req 14 x 25 356 x 635 1 Req 1100 1300 14 x 25 356 x 635 2 Req 14 x 25 356 x 635 1 Req 1300 1500 16 x 18 406 x 457 2 Req 16 x 18 406 x 457 1 Req 1500 1700 20 x 25 508 x 6...

Page 8: ...Systems TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or classified section of your local telephone directory under the Heating Equipment or Air Conditioning Contractors Systems headin...

Reviews: