background image

3

2. Drop three ice cubes into a glass of water and stir. If, within

three minutes, moisture does not form on the glass, the air is

too dry and a humidifier would be beneficial. (Do not per-
form this test in the kitchen, cooking vapors may produce
inaccurate results.)

A good relative humidity is one just high enough to barely start
condensation along the lower edges or lower corners of the

windows, when it is cold outside. More than that can be damaging.
If the humidity is too high, try these suggestions to lower the
humidity:

1. Reduce setting or discontinue use of humidifier.
2. Use range and bathroom exhaust fans while cooking and

bathing. Open a door or window for a few minutes to bring
in cool drier air.

3. Cook with pans covered.
4. Take shorter baths or showers with cooler water.
5. Install a fresh air intake duct. Cold, dry air brought in from

outside to the furnace area lowers the indoor humidity level.

6. Have appliances checked. A malfunctioning appliance can

contribute water vapor to the structure.

7. If the problem continues, consult a heating contractor about

adding a heat recovery ventilator or air--to--air heat ex-

changer.

About Your Furnace

Fig. 2 shows the location of the components in the furnace.

Circulating Air Blower

The blower circulates room air through the furnace, air ducts, and
into the rooms of the structure. The blower can be set at the

thermostat for automatic or manual operation. In manual mode the

blower operates continuously. In automatic, the blower does not
come on until a preset time after the gas valve is energized. When

the structure reaches the temperature set on the thermostat, the

furnace will shut off. The blower will continue to run until the
furnace cools down.

Thermostat

There are many types and styles of thermostats. Most thermostats

control both heating and cooling functions and have a Fan Switch
with AUTO and ON settings. On AUTO, the Circulating Air

Blower will cycle on/off with the furnace on the heating speed
unless a call for cooling is initiated. Blower speed will correspond

to the mode of operation of the furnace. If the Fan Switch is
positioned to ON the blower will run continuously.
In addition some thermostats are programmable with multiple set

backs. The set backs can be pre--programmed to lower or raise the
temperature automatically.
Be sure to become familiar with your thermostat.

Rating Plate

The rating plate contains important information for the service

technician and lists the complete model, manufacturing and serial

numbers. You should always provide all these numbers when
requesting parts or if you need service. See Fig. 2 for rating plate

location.

Door Interlock Switch

All the electrical power for the furnace goes through the door

interlock switch. The interlock switch interrupts electrical power to

the furnace when the blower door is removed. The furnace will not
operate until the blower door is reinstalled.

Furnace Control

The furnace control provides power to the circulating air blower to
keep it on until the furnace cools down.
The fan off--delay setting can be adjusted if the fan remains on long

enough that cool drafts are felt in the room after the furnace shuts
off.

Manual Equipment Shutoff Valve

Primary Heat Exchanger

Circulating Air Blower

Furnace Control

Pressure Switches
(some models have one)

Representative drawing only, some models may vary in appearance.

Air Intake Pipe
(Required only for Direct--Vent Furnaces)

Rating Plate

Secondary Heat Exchanger

Furnace Main Gas Control Valve

Plastic Transition Box

Door Interlock Switch

Condensate Trap

5

/

8

I.D. Transition Box Drain Hose

1

/

2

I.D. Vent Pipe Drain Hose

Combustion Blower

Vent Drain Fitting

Vent Pipe Grommet

Furnace Vent Pipe (Vent Pipe Connec-

tions through Side Panel on Some Models-

Diagnostic Light

Ignitor & Flame Sensor
(not shown)

A07689

Fig. 2 -- Component Locations for Condensing 90+ Furnaces

359B

A

V

Summary of Contents for 359BAV

Page 1: ...ice agency should be contacted to inspect the furnace and to replace all gas controls control system parts electrical parts that have been wet or the furnace if deemed necessary CERTIFIED As an ENERGY...

Page 2: ...ze 5 On appliances with a draft hood check for spillage by hold ing a lighted match 2 50 8mm from the draft hood open ing Reference Fig 1 which shows a water heater draft hood Typical Gas Water Heater...

Page 3: ...have a Fan Switch with AUTO and ON settings On AUTO the Circulating Air Blower will cycle on off with the furnace on the heating speed unless a call for cooling is initiated Blower speed will correspo...

Page 4: ...ors 8 Turn ON all electrical power to the furnace 9 Set the thermostat to the desired temperature and the System Select Switch to HEAT The furnace will activate an igniter which lights the main burner...

Page 5: ...cleaned or replaced as required There are many types of filters that are commonly used Washable filters constructed of aluminum mesh foam or reinforced fibers may be cleaned by soaking in mild deterge...

Page 6: ...ace External Filter Rack A plastic end cap is inserted in the filter rack after the filter is installed The end cap keeps air from escaping around the open end of the filter rack See Fig 4 for removal...

Page 7: ...rs 800 900 20 x 25 508 x 635 1 Req 14 x 25 356 x 635 1 Req 1100 1300 14 x 25 356 x 635 2 Req 14 x 25 356 x 635 1 Req 1300 1500 16 x 18 406 x 457 2 Req 16 x 18 406 x 457 1 Req 1500 1700 20 x 25 508 x 6...

Page 8: ...Systems TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or classified section of your local telephone directory under the Heating Equipment or Air Conditioning Contractors Systems headin...

Reviews: