background image

40

High--cooling airflow is based on the A/C selection shown
in Fig. 39.

NOTE

: When transitioning from low--cooling to high--cooling the

outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high--cooling
airflow.

The electronic air cleaner terminal EAC--1 is energized

with 115 vac whenever the blower motor BLWM is
operating.

When the thermostat is satisfied, the R to G--and--Y circuit

are opened. The outdoor unit stops, and the furnace blower
BLWM and electronic air cleaner terminal EAC--1 will

remain energized for an additional 90 seconds. Jumper Y1
to DHUM to reduce the cooling off--delay to 5 seconds.

(See Fig. 33.)

3.

Two--Stage Thermostat and Two--Speed Cooling

(See Fig. 49 for thermostat connections)

NOTE

: The air conditioning relay disable jumper ACRDJ must

be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 33.)

The thermostat closes the R to G and--Y1 circuits for low

cooling or closes the R to G and--Y1--and--Y2 circuits for

high--cooling. The R to Y1 circuit starts the outdoor unit
on low--cooling speed, and the R to G--and--Y1 circuit

starts the furnace blower motor BLWM on low--cooling
airflow which is the true on--board CF selection as shown

in Fig. 41. The R to Y1--and--Y2 circuits start the outdoor
unit on high--cooling speed, and the R to G--and--Y/Y2

circuits start the furnace blower motor BLWM at

high--cooling airflow. High--cooling airflow is based on the
A/C selection shown in Fig. 39.

The electronic air cleaner terminal EAC--1 is energized
with 115 vac whenever the blower motor BLWM is

operating.

When the thermostat is satisfied, the R to G--and--Y1 or R
to G--and--Y1--and--Y2 circuits are opened. The outdoor

unit stops, and the furnace blower BLWM and electronic
air cleaner terminal EAC--1 will remain energized for an

additional 90 seconds. Jumper Y1 to DHUM to reduce the

cooling off--delay to 5 seconds. (See Fig. 33.)

Thermidistat Mode

See Fig. 43--46 for Thermidistat connections.

The dehumidification output, DHUM on the Thermidistat should

be connected to the furnace control thermostat terminal DHUM.
When there is a dehumidify demand, the DHUM input is activated,

which means 24 vac signal is removed from the DHUM input
terminal. In other words, the DHUM input logic is reversed. The

DHUM input is turned ON when no dehumidify demand exists.
Once 24 vac is detected by the furnace control on the DHUM

input, the furnace control operates in Thermidistat mode. If the

DHUM input is low for more than 48 hours, the furnace control
reverts back to non--Thermidistat mode.

The cooling operation described in item 3. above applies to
operation with a Thermidistat. The exceptions are listed below:

1.

Low cooling

--When the R to G--and--Y1 circuit is closed

and there is a demand for dehumidification, the furnace

blower motor BLWM will drop the blower airflow to 86%
of low--cooling airflow which is the true on--board CF se-

lection as shown in Fig. 39.

2.

High coolin

g--When the R to G--and Y/Y2 circuit is closed

and there is a demand for dehumidification, the furnace

blower motor BLWM will drop the blower airflow to 86%
of high--cooling airflow. High--cooling airflow is based on

the A/C selection shown in Fig. 39.

3.

Cooling off--delay

--When the “call for cooling” is satisfied

and there is a demand for dehumidification, the cooling

blower--off delay is decreased from 90 seconds to 5
seconds.

Super--Dehumidify Mode

Super--Dehumidify mode can only be entered if the furnace control
is in Thermidistat mode and there is a demand for

dehumidification. The cooling operation described in item 3.

above also applies to operation with a Thermidistat. The exceptions
are listed below:

1.

Low cooling

--When the R to Y1 circuit is closed, R to G

circuit is open, and there is a demand for dehumidification,

the furnace blower motor BLWM will drop the blower air-
flow to 65% of low--cooling airflow for a maximum of 10
minutes each cooling cycle or until the R to G circuit closes

or the demand for dehumidification is satisfied. Low--cool-
ing airflow is the true on--board CF selection as

shown in Fig. 39.

2.

High cooling

--When the R to Y/Y2 circuit is closed, R to G

circuit is open, and there is a demand for dehumidification,

the furnace blower motor BLWM will drop the blower to
65% of high--cooling airflow for a maximum of 10 minutes

each cooling cycle or until the R to G circuit closes or the
demand for dehumidification is satisfied. High--cooling air-
flow is based on the A/C selection shown in Fig. 39.

3.

Cooling off--delay

--When the “call for cooling” is satisfied

and there is a demand for dehumidification, the cooling

blower--off delay is decreased from 90 seconds to 5
seconds.

Continuous Blower Mode

When the R to G circuit is closed by the thermostat, the blower
motor BLWM will operate at continuous--blower airflow.

Continuous blower airflow selection is initially based on the CF
selection shown in Fig. 39. Factory default is shown in Fig. 39.

Terminal EAC--1 is energized as long as the blower motor BLWM

is energized.
During a call for heat, the blower BLWM will transition the blower

motor BLWM to continuous blower airflow, low--heat airflow, or
the midrange airflow, whichever is lowest. The blower motor

BLWM will remain ON until the main burners ignite then shut

OFF and remain OFF for the blower--ON delay (30 seconds in
low--heat and 35 seconds in high--heat) allowing the furnace heat

exchangers to heat more quickly, then restarts at the end of the
blower--ON delay period at low--heat or high--heat airflow

respectively.

The blower motor BLWM will revert to continuous--blower
airflow after the heating cycle is completed. In high--heat, the

furnace control CPU will drop the blower motor BLWM to
low--heat airflow during the selected blower--OFF delay period

before transitioning to continuous--blower airflow.
When the thermostat “calls for high--cooling,” the blower motor

BLWM will operate at high--cooling airflow. When the thermostat

is satisfied, the blower motor BLWM will operate an additional 90
seconds at high--cooling airflow before transitioning back to

continuous--blower airflow.
When the R to G circuit is opened, the blower motor BLWM will

continue operating for an additional 5 seconds, if no other function

requires blower motor BLWM operation.

355B

A

V

Summary of Contents for 355BAV

Page 1: ...rsonnel The authority having jurisdiction gas inspection authority municipal building department fire department etc should be consulted before installation to determine the need to obtain a permit Co...

Page 2: ...Arrangement 13 Bottom Closure Panel 14 Gas Piping 14 Electrical Connections 16 Removal of Existing Furnaces from Common Vent Systems 20 Combustion air and Vent Pipe Systems 20 Physical Data 33 Condens...

Page 3: ...ust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF A...

Page 4: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe prac...

Page 5: ...2 495 080 20 060080 21 533 19 3 8 492 19 1 2 495 100 20 060100 21 533 19 3 8 492 19 1 2 495 120 20 060120 24 1 2 622 22 7 8 581 23 584 Fig 2 Dimensional Drawing A gas fired furnace for installation i...

Page 6: ...urnace installation These materials are shipped in the main blower compartment Installer Packet Includes Installation Startup and Operating Instructions Service and Maintenance Instructions User s Inf...

Page 7: ...20001 S CANADA NSCNGPIC For a copy contact Standard Sales CSA International 178 Rexdale Boulevard Etobicoke Toronto Ontario M9W 1R3 Canada Combustion and Ventilation Air S US Section 9 3 of the Natio...

Page 8: ...in Fig 7 from the factory See appropriate application instructions for these procedures MINOR PROPERTY DAMAGE Failure to follow this caution may result in minor property damage Local codes may requir...

Page 9: ...onfiguration section for tubing attachment To relocate condensate trap to the left hand side perform the following 1 Remove 3 tubes connected to condensate trap 2 Remove trap from blower shelf by gent...

Page 10: ...ucer Housing Unused Drain Connections Upper Collector Box Drain Connection Attached to the UPPER collector box drain connection is a factory installed plug This plug prevents condensate leakage in thi...

Page 11: ...to the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combusti...

Page 12: ...position 1 3 4 1 3 4 1 3 4 1 3 4 5 16 5 16 5 16 5 16 44mm 8mm 44mm 8mm 8mm 8mm 44mm 44mm A89014 Fig 12 Leveling Legs Hazardous Locations FIRE EXPLOSION INJURY OR DEATH HAZARD Improper location or inad...

Page 13: ...bow and 10 ft 3 0 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the...

Page 14: ...lter s as shown in Fig 14 For bottom return air applications filter may need to be cut to fit some furnace widths Install filter as shown in Fig 15 WASHABLE FILTER FILTER SUPPORT FILTER RETAINER 171 2...

Page 15: ...connecting a tee to riser leading to furnace so straight through section of tee is vertical Then connect a capped nipple into lower end of tee Capped nipple should extend below level of gas controls...

Page 16: ...nt operation can occur Do not bypass or close switch with panel removed WARNING UNIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit operation Furnace control must be gr...

Page 17: ...115 60 1 127 104 8 9 14 31 9 4 15 080 14 115 60 1 127 104 8 9 14 31 9 4 15 080 20 115 60 1 127 104 13 8 12 32 9 7 20 100 20 115 60 1 127 104 13 8 12 32 9 7 20 120 20 115 60 1 127 104 13 8 12 32 9 7 2...

Page 18: ...n furnace door and blower access panel NOTE If a bypass humidifier is used setup switch SW1 3 Low Heat Rise Adjust should be in ON position This compensates for the increased temperature in return air...

Page 19: ...19 A09683 Fig 23 Wiring Diagram 355BAV...

Page 20: ...tdoor air such as an attic or crawl space and the space is well isolated from the living space or garage Materials Combustion air and vent pipe fittings primers and solvents must conform to American N...

Page 21: ...tion instructions Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances Do not take combustion air from inside the chimney wh...

Page 22: ...Locate combustion air inlet as far as possible from swimming pool and swimming pool pump house CAUTION EXAMPLE A 100 000 BTUH furnace located in Indianapolis elevation 650 ft 198 1 M above sea level c...

Page 23: ...UNIT DAMAGE HAZARD Failure to follow this caution may result in unit component damage Inducer housing outlet cap must be installed and fully seated against inducer housing Clamp must be tightened to...

Page 24: ...ST be provided for the ventilation devices in addition to that required by the furnace Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine i...

Page 25: ...structure either through sidewall or roof For vent termination clearance refer to Fig 34 for Direct Vent 2 Pipe system and Fig 35 for Ventilated Combustion Air option Roof termination is preferred si...

Page 26: ...n preferred 1 in 25mm maximum typ from wall to inlet 12 in 305mm minimum from overhang or roof Maintain 12 in min clearance above highest anticipated snow level or grade whichever is greater A At leas...

Page 27: ...12 in 305mm minimum clearance above highest anticipated snow level or grade whichever is greater 6 in 152mm minimum clearance between wall and end of vent pipe 10 in 254mm maximum pipe lengt h Sidewal...

Page 28: ...meter hole for 3 in 76 mm kit 2 Loosely assemble concentric vent combustion air termina tion components together using instructions in kit 3 Slide assembled kit with rain shield REMOVED through hole N...

Page 29: ...SWITCHES AND BLOWER OFF DELAY STATUS AND COMM LED LIGHTS 3 AMP FUSE TRANSFORMER 24 VAC CONNECTIONS PL3 ECM BLOWER HARNESS CONNECTOR PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR EAC 1 TERMINAL 115 VAC 1 0 AM...

Page 30: ...30 A05009 Fig 34 Direct Vent Termination Clearance 355BAV...

Page 31: ...31 A05013 Fig 35 Other than Direct Vent Termination Clearance 355BAV...

Page 32: ...4 to 1219 60 000 2 Pipe or 2 In 51 Concentric 1 1 2 38 42 13 37 11 32 10 27 8 22 7 17 5 2 51 70 21 70 21 70 21 70 21 70 21 70 21 80 000 2 Pipe or 2 In 51 Concentric 1 1 2 38 25 8 20 6 15 5 10 3 5 2 NA...

Page 33: ...s otherwise stated use perforated disk assembly factory supplied in loose parts bag Wide radius elbow Vent sizing for Canadian installations over 4500 ft 1372 M above sea level are subject to acceptan...

Page 34: ...ch may result in damage to plants WARNING Condensate Drain Protection Freezing condensate left in condensate trap and drain line may cause cracks and possible water damage may occur If freeze protecti...

Page 35: ...rates HUM terminal is only energized when blower is energized in heating Continuous Fan CF Setup Switches The CF setup switches are used to select desired airflow when thermostat is in continuous fan...

Page 36: ...urn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R thermostat lead is disconnected SW1 2 Adaptive Heat Mode OFF Allows 2 stage operation with a single stage thermosta...

Page 37: ...r to be conducted through the blower door interlock switch ILK to the furnace control CPU transformer TRAN inducer motor IDM blower motor BLWM hot surface igniter HSI and gas valve GV SINGLE STAGE THE...

Page 38: ...valve relay contacts GVR close to energize the gas valve GV the gas valve opens The gas valve GV permits gas flow to the burners where it is ignited by the Hot Surface Igniter HSI Five seconds after...

Page 39: ...igh heat airflow five seconds after the R to W2 circuit closes 2 Switching From High To Low Heat If the thermostat R to W2 circuit opens and the R to W1 circuit remains closed the furnace control CPU...

Page 40: ...r dehumidification the furnace blower motor BLWM will drop the blower airflow to 86 of high cooling airflow High cooling airflow is based on the A C selection shown in Fig 39 3 Cooling off delay When...

Page 41: ...h Single Speed Air Conditioner A00276 Fig 44 Two Stage Furnace with Two Speed Air Conditioner A00277 Fig 45 Two Stage Furnace with Single Speed Heat Pump Dual Fuel A00278 Fig 46 Two Stage Furnace with...

Page 42: ...Pump A00280 Fig 48 Dual Fuel Thermostat With Two Stage Furnace and Two Speed Heat Pump A00281 Fig 49 Two Stage Thermostat With Two Stage Furnace and Two Speed Air Conditioner See note 2 A02348 Fig 50...

Page 43: ...plications 10 NO connection should be made to the furnace HUM terminal when using a Thermidistat 11 Optional connection If wire is connected dip switch SW1 2 on furnace control should be set in ON pos...

Page 44: ...CPU turns the hot surface igniter ON for 15 seconds then OFF 3 The furnace control CPU then turns the blower motor BLWM ON at midrange airflow for 15 seconds then OFF 4 After shutting the blower moto...

Page 45: ...45 Table 11 Orifice Size and Manifold Pressures for Gas Input Rate Tabulated Data Based on 20 000 Btuh High Heat 13 000 Btuh Low Heat Per Burner Derated 2 1 000 Ft 305 M Above Sea Level A08376A 355BAV...

Page 46: ...ble 11 Orifice Size and Manifold Pressures for Gas Input Rate Tabulated Data Based on 20 000 Btuh High Heat 13 000 Btuh Low Heat Per Burner Derated 2 1 000 Ft 305 M Above Sea Level Continued A08376B 3...

Page 47: ...t See Fig 53 j Remove jumpers R to W W1 and R to W2 3 Verify natural gas input rate by clocking gas meter NOTE Be sure all pressure tubing combustion air and vent pipes and burner enclosure front are...

Page 48: ...r altitudes n Remove jumper across R W W1 and W2 thermostat connections to terminate call for heat Set temperature rise UNIT DAMAGE HAZARD Failure to follow this caution may result in overheating the...

Page 49: ...ires during current measurement Fig 54 illustrates an easy method of obtaining thermostat amp draw measurements The amp reading should be taken after blower motor has started and furnace is operating...

Page 50: ...d when in ducer motor is disconnected the furnace will shut itself down immediately Determine the reason pressure switches did not function properly and correct the condition 5 Turn off 115 v power to...

Page 51: ..._____ Sidewall ________________ Anticipator Setting Adjusted or ________________ Attic ________________ Cycle Rate 3 Cycles per Hr Selected ________________ Crawl Space Safety Controls Check Operation...

Page 52: ...ge at any time specifications or designs without notice and without incurring obligations E2010 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date...

Reviews: