background image

(1.) Attach variable-speed, reversible drill to end of

spring cable (end opposite brush).

(2.) Remove cell outlet plates. IMPORTANT: Replace

screws in center panel before cleaning.

(3.) Insert brush end of cable into upper opening of cell

and slowly rotate with drill. DO NOT force cable.
Gradually insert at least 36 in. of cable into 2 upper
passes of cell. (See Fig. 7.)

(4.) Work cable in and out of cell 3 or 4 times to obtain

sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.

(5.) Remove burner assembly and cell inlet plates.

NOTE:

Be very careful when removing the burner assembly to

avoid breaking the ignitor. See Fig. 8 for the correct ignitor
location.

(6.) IMPORTANT: Replace screws in center panel and

cells before cleaning.

(7.) Insert brush end of cable in lower opening of cell,

and proceed to clean 2 lower passes of cell in same
manner as 2 upper passes.

(8.) Repeat foregoing procedures until each cell in

furnace has been cleaned.

(9.) Using vacuum cleaner, remove residue from each

cell.

(10.) Using vacuum cleaner with soft brush attachment,

clean burner assembly.

(11.) Reinstall cell outlet plates and screws FIRST;

then, reinstall cell inlet plates and burner assem-
bly. Care must be exercised to center burners in
cell openings.

9. After cleaning flue openings, check sealant on flue collector

to ensure that it has not been damaged. If new sealant is
needed, contact your dealer or distributor.

10. Clean and replace flue collector assembly, making sure all

8 screws are secure.

11. Reinstall relief box.

12. Reconnect wires to the following components:

a. Draft safeguard switch.

b. Inducer motor.

c. Pressure switches.

d. Limit overtemperature switch(es).

e. Gas valve.

f. Hot surface ignitor.

g. Flame-sensing electrode.

h. Wiring connectors leading to control.

13. Reconnect vent pipe to relief box. When applicable replace

vent pipe enclosure.

14. Replace blower door only.

15. Turn power and gas to ON.

16. Set thermostat and check furnace for proper operation.

17. Verify blower airflow and speed changes between heating

and cooling.

18. Check for gas leaks.

19. Replace control door.

WARNING:

Never use a match or other open flame to

check for gas leaks. Use a soap-and-water solution. A
failure to follow this warning could result in fire, personal
injury, or death.

D.

Electrical Controls and Wiring

NOTE:

There may be more than 1 electrical supply to unit.

The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 9 and 10 for field wiring
information and to Fig. 11 for unit wiring information. If the
polarity is NOT correct, the furnace control will display rapid
flashing on the status LED and prevent heat operation. The control
system also requires an earth ground for proper operation of the
microprocessor.
With power disconnected to unit, check all electrical connections
for tightness. Tighten all screws on electrical connections. If any
smoky or burned connections are noticed, disassemble the connec-
tion, clean all parts and stripped wire, and reassemble properly and
securely. Electrical controls are difficult to check without proper
instrumentation; therefore, reconnect electrical power to unit and
observe unit through 1 complete operating cycle.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control. Any 24-v electrical shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse. The control will
display code 24 when fuse needs replacement.

Fig. 7—Cleaning Heat Exchanger Cell

A91252

Fig. 8—Position of Ignitor to Burner

A93347

BURNER

IGNITOR

11 32

"

7 8

"

C

L

C

L

IGNITOR
ASSEMBLY

CELL
PANEL

BURNER

13 32

"

HOT
SURFACE
IGNITOR
ASSEMBLY

—5—

Summary of Contents for 330JAV

Page 1: ...ted States follow all safety codes including the National Fuel Gas Code NFPA No 54 1996 ANSI Z223 1 1996 In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2...

Page 2: ...commercial sources may also be used to prevent ESD damage CARE AND MAINTENANCE For continuing high performance and to minimize possible equip ment failure it is essential that periodic maintenance be...

Page 3: ...ter through filter from opposite direction of airflow e Rinse and let dry Oiling or coating of filter is not recommended or required f Place filter in furnace g Replace blower and control access doors...

Page 4: ...alified service technician NOTE Deposits of soot and carbon indicate the existence of a problem which needs to be corrected Take action to correct the problem If it becomes necessary to clean heat exc...

Page 5: ...ctors leading to control 13 Reconnect vent pipe to relief box When applicable replace vent pipe enclosure 14 Replace blower door only 15 Turn power and gas to ON 16 Set thermostat and check furnace fo...

Page 6: ...connect and reconnect of red wire Fig 9 Heating and Cooling Application Wiring Diagram for Single Stage Thermostats and Single Speed Condensing Units A97443 115 V FUSED DISCONNECT SWITCH WHEN REQUIRED...

Page 7: ...condition E Troubleshooting Refer to service label See Fig 12 Page 10 contains a trouble shooting guide This guide can be a useful tool in isolating furnace operation problems Beginning with the word...

Page 8: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Page 9: ...DOWNFLOW ONLY SWITCH DID NOT CLOSE OR REOPENED Check for Proper vent sizing and condensate pitch with side wall vent Low inducer voltage 115v Blower motor and capacitor Defective inducer motor Defect...

Page 10: ...eck for proper orifice size Control will attempt to light burners 4 times approximately 1 minute between attempts Code 34 Voltage is present at the gas valve for 7 sec during each ignition trial Syste...

Page 11: ...11...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: