Air Delivery --- CFM (With Filter)*
UNIT SIZE
RETURN---AIR
SUPPLY
SPEED
EXTERNAL STATIC PRESSURE (in. wc)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
024045
Bottom or
Side(s)
5
1185
1145
1115
1075
1035
980
905
820
720
580
4
920
880
835
800
755
720
680
645
605
540
3
735
685
625
585
530
490
435
395
345
295
2
820
765
725
670
630
580
545
490
455
405
1
650
595
535
490
430
390
330
280
235
--- ---
048070
Bottom or
Side(s)
5
1625
1585
1535
1495
1460
1415
1365
1295
1220
1125
4
1405
1360
1320
1280
1240
1195
1155
1115
1070
1030
3
1240
1200
1155
1110
1065
1020
975
935
895
850
2
1190
1140
1095
1050
1000
955
915
870
830
790
1
1035
985
930
885
835
785
745
695
650
600
048090
Bottom or
Side(s)
5
1845
1800
1755
1710
1665
1595
1500
1400
1275
1105
4
1590
1545
1500
1455
1410
1365
1315
1270
1180
1000
3
1365
1320
1270
1215
1170
1125
1070
1025
955
900
2
1225
1160
1110
1060
1010
950
895
830
770
710
1
1100
1030
960
875
805
730
645
570
505
425
060110
Bottom or
Side(s)
5
2255
2205
2150
2100
2040
1985
1920
1835
1735
1615
4
1600
1525
1465
1400
1335
1275
1210
1150
1080
1015
3
1945
1890
1830
1770
1715
1655
1600
1545
1480
1430
2
1420
1340
1280
1200
1140
1065
1005
925
865
790
1
1280
1205
1140
1055
990
910
840
760
695
630
060135
Bottom or
Side(s)
5
2295
2240
2185
2125
2070
2005
1925
1805
1670
1545
4
1725
1660
1605
1545
1460
1395
1340
1285
1230
1170
3
1910
1865
1800
1745
1685
1610
1545
1485
1435
1380
2
1630
1575
1510
1435
1365
1300
1245
1185
1130
1065
1
1430
1355
1285
1200
1125
1075
1015
945
855
800
*A filter is required for each return---air inlet. Airflow performance included 1---in. (25 mm) washable filter media such as contained in factory---authorized acces-
sory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
ELECTRICAL DATA
313AAV/
JAV UNIT
SIZE
VOLTS---
HERTZ---
PHASE
OPERATING VOLTAGE
RANGE
*
MAXIMUM
UNIT AMPS
MAXIMUM WIRE
LENGTH FT (M)
}
MAXIMUM FUSE
OR CKT BKR
AMPS
{
MINIMUM
WIRE GAGE
Maximum
Minimum
024045
115---60---1
127
104
8.1
34 (10)
15
14
048070
115---60---1
127
104
9.5
29 (9)
15
14
048090
115---60---1
127
104
10.3
27 (8)
15
14
060110
115---60---1
127
104
13.1
34 (10)
20
12
060135
115---60---1
127
104
13.1
34 (10)
20
12
* Permissible limits of the voltage range at which the unit operates satisfactorily.
{
Time---delay type is recommended.
}
Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
313AA
V/
JA