background image

Fig. 9—Service Label

A00286

LED CODE

If status code recall is needed, briefly remove then reconnect  one main limit wire to display stored status code.

SERVICE

To  initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead.

Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the

inducer motor at high speed until the end of the test, then shift to low speed for 10 seconds. The hot surface ignitor,

blower motor low-heat speed, blower motor high-heat speed, and blower motor cool speed will be turned ON for

10-15 seconds each.  Gas Valve and Humidifier will not be turned on.

326379-101   REV.   A (lit-top)

CONTINUOUS OFF

  -  Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.

CONTINUOUS ON

  -  Control has 24VAC power.

RAPID FLASHING

  -  Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE

NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

STATUS

COMPONENT TEST

11 NO PREVIOUS CODE 

 - Stored status codes are erased automatically after 72 hours.

12 BLOWER ON AFTER POWER UP  

(115 VAC or 24 VAC)      -Blower runs for 90 seconds, if unit is powered

up during a call for heat (R-W closed).

13 LIMIT, DRAFT SAFEGUARD, FLAME ROLL-OUT SWITCH OR BLOCKED VENT SWITCH 

(when used)

LOCKOUT

 - Control will auto reset after three hours. Reset switch.  Refer to #33.

14 IGNITION LOCKOUT -

Control will auto-reset after three hours. Refer to #34.

21 GAS HEATING  LOCKOUT

 - Control will NOT auto reset.

Check for: - Mis-wired gas valve                 - Defective control (valve relay)

22 ABNORMAL FLAME-PROVING SIGNAL

- Flame is proved while gas valve is de-energized. Inducer will run

until fault is cleared.  Check for:             - Leaky gas valve

-Stuck-open gas valve

23 PRESSURE SWITCH DID NOT OPEN

  Check for:

- Obstructed pressure tubing.

    - Pressure switch stuck closed.

24 SECONDARY VOLTAGE FUSE IS OPEN

Check for:    - Short circuit in secondary voltage (24VAC) wiring.

31 HIGH-HEAT PRESSURE SWITCH OR RELAY  DID NOT CLOSE OR REOPENED

Check for:  Control relay may be defective    - Refer to #32

32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED   

If open longer than five minutes,

inducer shuts off for 15 minutes before retry.    Check for:  - Proper vent sizing

- Defective inducer motor

- Disconnected or obstructed pressure tubing

- Excessive wind

- Defective pressure switch

      - Restricted vent                                  

                                - Inadequate combustion air supply

- Low inducer voltage (115VAC) if code flashes while unit runs in low-heat with high speed inducer.

If it opens after trial for ignition period, blower will come on for 90 second recycle delay.

33 LIMIT, DRAFT SAFEGUARD, FLAME ROLL-OUT SWITCH OR BLOCKED VENT SWITCH 

(when used)

LOCKOUT IS OPEN 

 - If open longer than three minutes, code changes to #13. Flame roll-out switch requires

manual reset.  Check for:  

  - Defective blower motor or  capacitor.

- Dirty filter or restricted duct system.       - Restricted vent

- Loose blower wheel.

   - Defective switch or connections.

- Proper vent sizing

   - Excessive wind

- Inadequate combustion air supply (Flame Roll-out Switch open).

- Open Flame Roll-out switch.   Manual reset or replace.

34 IGNITION PROVING FAILURE

- Control will try three more times before lockout #14 occurs. If flame signal

lost after trial for ignition period, blower will come on for 90 second recycle delay.   Check for:

- Oxide buildup on flame sensor (clean with fine steel wool).

- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

- Gas valve defective or gas valve turned off.

- Defective Hot Surface Ignitor

                  - Manual valve shut-off.

- Low inlet gas pressure.

              - Control ground continuity

- Inadequate flame carryover  or rough ignition.    - Flame sensor must be ungrounded.

- Green/Yellow wire

MUST

 be connected to furnace sheet metal.

43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS CLOSED

Check for:

-  Pressure switch stuck open         -  Disconnected or obstructed pressure tubing

45  CONTROL CIRCUITRY  LOCKOUT 

 Auto-reset after one hour  lockout due to;

- Flame sense circuit failure                  - Software check error                 - Gas valve relay stuck open

 Reset power to clear lockout.  Replace control if status code  repeats.

A00286

—9—

Summary of Contents for 312AAV L Series

Page 1: ...nd the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WA...

Page 2: ...uum cleaners or other cleaning tools 2 Soap powders bleaches waxes or other cleaning compounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning fluids or other vola...

Page 3: ...furnace casing and away from blower compartment 8 Remove 2 screws holding blower assembly to blower deck and slide blower assembly out of furnace 9 Clean blower wheel and motor using a vacuum with so...

Page 4: ...y combustion air incorrect size or damaged manifold orifice s improper gas or a restricted heat exchanger Action must be taken to correct the problem If it becomes necessary to clean the heat exchange...

Page 5: ...proper operation 16 Verify blower airflow and speed changes between heating and cooling 17 Check for gas leaks WARNING Never use a match or other open flame to check for gas leaks Use a soap and wate...

Page 6: ...LED status 4 If furnace is operating properly and continuously lit LED indicates proper operation replace outer access door 5 Component Test can also be initiated by performing the following a Remove...

Page 7: ...nds 15 Blower off delay gas heating selections are 90 120 150 180 seconds cooling or heat pump 90 seconds or 5 seconds when DHUM is on LEGEND ACR AIR CONDITIONING RELAY SPST N O ACRDJ AIR CONDITIONING...

Page 8: ...omponent After replacing any component verify correct operation sequence Fig 8 Furnace Control A00380 LHT OFF DLY ON OFF W2 BLW 24 V THERMOSTAT TERMINALS SETUP SWITCHES LOW HEAT ONLY AND BLOWER OFF DE...

Page 9: ...for Short circuit in secondary voltage 24VAC wiring 31 HIGH HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED Check for Control relay may be defective Refer to 32 32 LOW HEAT PRESSURE SWITCH DID...

Page 10: ...speed and run for the entire component test then shift to low speed for 10 seconds The HSI blower motor low heat speed blower motor high heat speed and blower motor cool speed will run for 10 15 sec e...

Page 11: ...PEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 SECONDARY VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwo...

Page 12: ...2000 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 12 Printed in U S A SP0468 Catalog No 5331 201...

Reviews: