24
Variable Speed Drive LED Location and Description (Sizes 13 and 24B)
COMM
STATUS
LED 207
LED 200
MOC LED Description (Sizes 13 and 24B)
Reference
Color
Status
Condition
Description
LED200
Red
Steady
On
Normal
Indicates MOC powered where DC bus at 40volts or higher
Off
Abnormal
No power, capacitor voltage drained
LED207
Amber
Steady
On
Normal
Compressor is running
Blinking
Abnormal
If compressor stops, it indicates some fault happening;
If compressor is running, it indicates speed is limited or reduced.
Off
Normal
Compressor stops and no fault
AOC LED Descriptions (Sizes 13 and 24B)
Reference
Color
Status
Condition
Description
STATUS
Amber
Steady
On
Normal
AOC status---standby mode
Blinking
Abnormal
AOC function/fault status
COMM
Green
Steady
On
Normal
Communication from AOC to indoor wall control
LED Not Functioning Properly--- Requires AOC or Inverter Replacement
Reference
Color
Suspect AOC board
Failure Description
STATUS
Amber
If Amber STATUS light is not on (neither steady nor blink-
ing), with power to outdoor unit
AOC STATUS is not functioning properly and AOC board
should be replaced.
COMM
Green
In Communicating mode, if Green COMM LED is not on
when AB indoor wires are connected to AOC AB connector
and indoor has communications
AOC is not capable of communicating with indoor; AOC
board should be replaced.
UI Fault Codes requiring AOC or Inverter Replacement
Fault Code Description
Fault Code
Failure Description
Communications Loss
179
Loss of communication with outdoor unit AOC board;
AOC or Inverter may need to be replaced
NOTE
: If any of the AOC control board header pins are damaged or are not making good contact, AOC board should be replaced.
Summary of Contents for 189BNV EVOLUTION
Page 17: ...17 Fig 38 Fault Code Label ...