Appendix
Pump
In this menu, the preset profiles for the pump can be selected or under “manual” all settings can be done personally. The settings
can still be changed after a profile has been selected.
Profile
Delete this text and replace it with your own.
Output Signal
In this menu, the type of pump is set: heating pumps have the greatest output with a small input signal, solar pumps in contrast
have very little output with a small input signal. Solar = normal, heating = inverted. For 0-10 V pump always choose the "Normal"
setting
PWM / 0-10V off
This voltage / this signal is emitted if the pump is turned off (pumps
with cable break detection need a minimal voltage / minimal signal).
PWM / 0-10V on
This voltage / this signal requires the pump in order to turn on and to run at a minimum speed.
PWM / 0-10V max.
With this value, the maximum voltage level / maximum frequency can be specified for the highest speed of the energy saving
pump, which is used, for example, during the flushing or manual operation.
Speed when „On“
In this menu, the calculation basis of the displayed speed is changed. If, for example, 30% is specified here, the fre-
quency/voltage set under “PWM On” / “0-10V On” will be displayed during creation so that a 30% speed is present. When cre-
ating the voltage/frequency of PWM Max / 0-10V Max, 100% speed is displayed. Temporary values are calculated
correspondingly.
This function does not influence the rule, but rather only the display on the status screen.
Example for pump settings