BRV ModvlvS Logico Installation And Operating Instructions Manual Download Page 16

Heat request is started when the flow temperature is continuously below reference temperature for 1 minute.

Reference/

This value determines the acceptable underflow of the heating circuit temperature beyond the calculated reference flow tem-
perature at the buffer sensor or flow sensor. If the temperature at the buffer sensor exceeds the reference flow temperature by the
value set here, the heating request is deactivated.

The setting value reference/ appears only in the menu if a sensor has been set under buffer sensor.

Heat request is started when the flow temperature is continuously below reference temperature for 1 minute.

Turn off HC

Summer:

HC turns off when the summer/winter changeover (outside temperature) is exceeded.

 Room:

HC is turned off when the summer/winter changeover (outside temperature) or the room setpoint temperatures

are exceeded.

Buffer sensor

Input of heating circuit buffer sensor

In this menu, the sensor is set, which is used as a reference sensor for the heating circuit request.

The request only works if an energy source (burner, compressor, solid chamber) is activated as an additional function
and if this source is set for the heating circuit request

(see also burner: see " Heating Circuit request " on page 18

Room Controller

This value is used to appoint the amount of influence the room temperature has on the reference flow temperature, as a per-
centage. For each degree deviation between room temperature and set point temperature, the percentage set here is added
from the calculated set flow temperature to the set flow temperature or subtracted from it until the min. or max flow values.

Example: Reference room temp.: e.g. 25 °C; room temp.: e.g. 20 °C ±5 °C. Calculated reference temp.: e.g. 40 °C: room con-
troller: 10 %= 4 °C 5 X 4 °C= 20 °C. Accordingly, 20 °C are added to the reference flow temperature, giving 60 °C. If the value is
higher than the one set in max. flow temp, the resulting temperature is the one set in max. flow temp.

Room Reference (Day)

The desired room temperature for day mode. As long as this temperature is not reached, the reference flow temperature is
raised and/or lowered according to the percent setting in ‚room controller‘. If ‚room controller‘ is set to 0 %, this function is deac-
tivated.

Room Reference (Night)

The desired room temperature for night mode. As long as this temperature is not reached, the reference flow temperature is
raised and/or lowered according to the percent setting in ‚room controller‘. If ‚room controller‘ is set to 0 %, this function is deac-
tivated.

In the modes ‚Set point‘ and ‚Set point program, the room controller has no influence.

Thermostat (X)

The room controller is selected here. If no room controller is connected and a room controller is connected via the CAN Bus,
another room controller can be selected here.
The CAN bus ID of controller is shown in Menu 'Special Functions' under 'Network'. In °CALEON see the CAN Bus ID in the
expert menu under Network. Choose the Room Controller with the CAN Bus ID of the corresponding controller.

Sensor Typ

If a sensor input is connected to a room controller, it must be set here whether it is a room temperature sensor (RC20) or a switch-
ing contact.

Mixer

This menu contains all settings relating to the mixer of the heating circuit.

Direction

Direction of the mixing valve can be set here.

Mixer turn time

The mixer is switched on i.e. is opening or closing for the time span set here, then the temperature is measured to control the flow
temperature

16

Summary of Contents for ModvlvS Logico

Page 1: ...Heating Controller ModvlvS Logico Weather compensated heating circuit controller Installation and operating instructions Read carefully before installation commissioning and operation 1...

Page 2: ...ference Actual 15 Reference Actual 16 Turn off HC 16 Buffer sensor 16 Mixer 16 Mixer run time 17 Signal type 17 PV contact 17 Mod Offset 17 Energy Saving Mode 17 Heating Circuit 2 17 Settings Domestic...

Page 3: ...cal Data The valid accident prevention regulations VDE regulations the regulations of the local power utility the applicable DIN EN stand ards and the installation and operating instruction of the add...

Page 4: ...nit l Use of the device for other than its intended purpose l Operation above or below the limit values listed in the Specifications section l Force majeure Disposal and Pollutants The unit conforms t...

Page 5: ...PWM output V1 V2 for 10 k working resistance 1 kHz level 10 V Terminal 24V voltage output Max load by external devices 24V 6W Max cable length VFS RPS sensors 3m CAN 3m at 3m a shielded twisted pair c...

Page 6: ...order l External relay for V1 V2 0 10V relay 1W 6A 77502 Hydraulic Variants The following illustrations should be regarded only as schematic representations of the respective hydraulic systems and do...

Page 7: ...rolling high efficiency pumps V2 0 10V PWM signal output e g for controlling high efficiency pumps S6 Temperature Sensor 6 outdoor 24V Power supply The connection of the ground wire is made at the low...

Page 8: ...istorted when screwed on 5 Using a drill and size 6 bit drill three holes at the points marked on the wall and push in the plugs 6 Insert the upper screw and screw it in slightly 7 Fit the upper part...

Page 9: ...the cable jacket must reach into the housing just to the other side of the strain relief Installing the Temperature Sensors The controller operates with Pt1000 temperature sensors which are accurate t...

Page 10: ...exit a menu If applicable a request for con firmation appears to save the made changes The function of the other 3 keys 4 is shown in the display right above the keys The right hand key generally has...

Page 11: ...on sumers connected and check the sensor values for plausibility Then set to automatic mode see Manual on page 14 The setup wizard can be accessed in menu 7 2 at any time Consider the explanations for...

Page 12: ...he right button changes the unit of time days and the two left buttons scroll through the diagram Operating hours Display of the operating hours of the consumers connected to the controller for exampl...

Page 13: ...cuit Day This menu is used to select the daytime mode times for the heating circuit three time periods can be specified for each weekday and copied to the following days Unspecified times are automati...

Page 14: ...14 days reference value program For the next 14 days you can enter the menu 4 temperatures for the next 14 days After 14 days the reference temperature of the 14th day is used continuously until the...

Page 15: ...ther room too hot In this case the slope of the curve should be reduced stepwise by 0 2 points and increases the day correction by 2 4 C each Night Correction Parallel characteristic translation The n...

Page 16: ...low values Example Reference room temp e g 25 C room temp e g 20 C 5 C Calculated reference temp e g 40 C room con troller 10 4 C 5 X 4 C 20 C Accordingly 20 C are added to the reference flow temperat...

Page 17: ...e technical description of your PV sys tem Mod Offset At modulated heat request the requested temperature can be increased by the value adjusted here Energy Saving Mode The Energy saving mode switches...

Page 18: ...the technical description of your PV sys tem 14 day Reference If operating mode 14 day reference value is selected see Operating mode on page 14 the reference flow temperature for each of the 14 days...

Page 19: ...offer any secure protection against legionella because the controller requires an adequate added amount of energy and the temperatures cannot be monitored in the entire storage area and the con nected...

Page 20: ...2 00 noon for 5 seconds to prevent seizing of the pump valve after long periods of inactivity ABS R X Activation daily weekly of the anti lock protection to a relay X at 12 00 for 5 seconds Frost Prot...

Page 21: ...or adjust it if desired Pressing esc more than once takes you back to the selection mode thus cancelling the commissioning help see Commissioning help on page 11 May only be started by a specialist du...

Page 22: ...ress of the data logger Auto Configuration DHCP If auto configuration is activated the data logger requests IP addresses and network parameters from a DHCP server that assigns an IP address subnet mas...

Page 23: ...tivated and can be used to make adjustments if necessary 1 Measurement values 2 Statistics 3 Times 8 Menu lock 9 Service values 9 Service values Serve for remote diagnosis by a specialist or the manuf...

Page 24: ...13 l Assess check plausibility of statistics see Serve for function control and long term monitoring of the system on page 12 l Check the error memory see Error messages on page 12 l Verify check plau...

Page 25: ...lude not only current measurement values and operating states but also all of the settings for the controller Write the service values down just once after commissioning has been successfully complete...

Page 26: ...eed a minimal voltage minimal signal PWM 0 10V on This voltage this signal requires the pump in order to turn on and to run at a minimum speed PWM 0 10V max With this value the maximum voltage level m...

Page 27: ...Technical data PWM and 0 10V Show signal Represents the set pump signal in a graphic and text overview 27...

Page 28: ...ation cannot be excluded Subject as a basic principle to errors and technical changes Date and time of installation Name of installation company Space for notes Your specialist dealer Manufacturer SO...

Reviews: