Page 87
MagnaTech
BOILERS AND VOLUME WATER HEATERS
199
Invalid LCI (Limit Control Input)
enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Code Description
Procedure
200
Invalid lightoff rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
201
Invalid lightoff rate proving setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
202
Invalid MFEP (Main Flame
Establishing Period) time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
203
Invalid MFEP (Main Flame
Establishing Period) flame failure
response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
204
Invalid NTC sensor type setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
205
Invalid Outlet high limit response
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
207
Invalid PII (Pre-Ignition Interlock)
enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
210
Invalid Postpurge time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset
module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.