7. QUICK VIEW OF USER SETTINGS

 

It is not possible to edit settings when these screens are displayed. 

This feature can also be activated with the front window closed! 

 

Press and hold the 

 button to display the initial power up screen. 

 

Press the same button again to display the “Last Tripped Information” screen 
(

refer to the next section for further information on this feature).

 

 

Press again to display the “Overcurrent Summary” screen. 

 

Press again to display the contact details for Broyce Control. 

 

Press again to revert back to Normal operation. 

 
8. LAST TRIPPED INFORMATION

 

Refer to next page for detailed information of this feature 

                                    
 

Notes during programming 

    

If during programming it is necessary to abort, press the  

 

button briefly.

    

Pressing and holding either

 

 

or

 

for >1sec. will increment or decrement 

the new value at a quicker rate. 

Stepping through each User Setting screen is performed by pressing and holding 

the 

button until the desired screen is displayed.  

Short presses of the 

button will allow further editable settings to be changed 

within a specific screen. 

If the user remains in a setting or summary screen where no adjustments or button 

presses are made within a certain period, the screen will revert back to Normal 
operation. Additionally, any settings that have been made but not stored will not be 
saved. 

“O/C” refers to Overcurrent. 

 

 

TRIPPING MODE 

 

 

A fault which develops on a phase will be indicated by an increase in current 
reading on the LCD. When the level of current exceeds the Low-set setting, 
the phase at fault will be highlighted by the digits flashing.

 

 

The LCD backlight will flash.

 

 

Relay 2 will energise if assigned to Overcurrent and set to energise at the start 
of the time out period (See Section 3. RELAY 2 SETTING).

 

 

The characters 

“I>”

 will display to indicate the Low-set has been triggered. 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 

If the current continues to increase above the High-set setting, the

 

characters 

“I>”

 will change and display 

“I>>”

 to indicate the High-set has been 

triggered. 

 

 
 
 
 
 
 

 

When the unit finally trips, the digits of the phase at fault will stop flashing and 
remain highlighted. This allows the user to see which phase was at fault and 
caused the unit to trip.

 

 

The red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED will also flash.

 

 

The relays which energised are also displayed on the screen after tripping.

 

 

Press 

to reset and return the unit back to normal operation (assuming 

the fault has been cleared). The LCD reverts back to displaying the normal 
system currents and the red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED stops flashing.

 

 

If either relay is set for Auto resetting, then they would have de-energised after the 

fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the display 
would also disappear. Pressing the “R

“R

“R

“RESET” 

ESET” 

ESET” 

ESET” button will only clear the LCD. If either 

relay is set for Manual resetting, then pressing the “RESET”

“RESET”

“RESET”

“RESET” button will de-energise the 

relay(s) and clear the LCD.

 

 

 

 

PROGRAMMING (continued) 

 

 

3. RELAY 2 SETTING 

Default setting for Relay 2 is to energise at the end of the time out period. 

Resetting mode is Auto. 

 

 

Setting of “Relay 2”

“Relay 2”

“Relay 2”

“Relay 2” is carried out in a similar manner as “Relay 1”

“Relay 1”

“Relay 1”

“Relay 1”; however it 

is necessary to assign the relay to either energise at the start (S) or end (E) of 
the time out period.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed. 

 

 

Press and hold the 

 button to set the options for ““““OVERCURRENT” 

OVERCURRENT” 

OVERCURRENT” 

OVERCURRENT” as 

described in the next section. 

 

4. OVERCURRENT SETTING 

The description for the Curves is abbreviated when displayed on the screen. Refer 

to “IDMT Characteristic Curves” for further explanation. 

Default settings for Overcurrent are shown in the last LCD screen example in this 

section. 

 

 

Settings for Overcurrent are displayed in turn following subsequent presses of 

the 

 button.  The Low-set trip current (I>) is displayed first.

 

 
 
 
 

 

 

 

Press either 

 or 

to change the current.

 

 

Press the 

 button to select the remaining settings and use the 

 and 

buttons to change them.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed.  

Screen example above also shows the default settings for OVERCURRENT. 

 

Press and hold the 

 button to set the options for ““““EARTH FAULT” 

EARTH FAULT” 

EARTH FAULT” 

EARTH FAULT” as 

described in the next section. 

 

If the Curve in selection “2:” is set to Definite Time, then selection “3:” will display 

“3: t>” and the required delay can then be set. 

If High-set is set to Disable in selection “4:”, then I>> or t>> cannot be 

adjusted.

 

 

5. OVERCURRENT SUMMARY  

It is not possible to edit settings when this screen is displayed. 

 

 

Following the setting of “Overcurrent”, the LCD displays the “Overcurrent” 
screen showing a summary of the settings made during programming. All 
settings are displayed. The selected CT ratio, Network Frequency and Relay 
operation (following a Reset) information is also displayed.

 

 
 
 
 
 

 
 

 
 
 

 

6. SAVING OF SETTINGS

 

 

If after viewing the Summary screen the settings are correct, press and hold 

the 

 button until the word ““““Saved.

Saved.

Saved.

Saved.”””” appears. Any new settings are now 

stored.

 

 

The screen will revert back to Normal operation.

 

 

 

O/C  SUMMARY   
  I>  5.00A 
  NI   3/10 
  k>  0.1 
  I>>50.00A 
  t>>0.05s 
  R1 = MAN   R2 = AUTO (E) 
  CT=5:5, FREQ=50Hz 

    

RELAY CONFIGURATION 
 
  RELAY 1:      RELAY 

2

:           

  AUTO        AUTO (E)       
 

MAN        

MAN (E) 

             

AUTO (S)

 

              MAN (S) 

 

O/C SETTING 
Low set 
    1: I>  5.00A 

    

 

The letter in brackets refers to 
whether Relay 2 has been set 
to trigger at the start or end of 
the time out period. 
(E) = E

EE

End of time out 

(S) = S

SS

Start of time out 

Either abbreviation can appear 
after the word MAN or 
AUTO 

See Section 3. RELAY 2 
SETTING 

 

I

L1

 

 

20.70

A

    

I> 

I

L2

 

 

40.00

A    

 

I

L3

 

 

27.50

A  

 

 

 

I

L1

 

 

20.70

A

    

I>> 

I

L2

 

 

89.00

A    

R1    R2

 

I

L3

 

 

27.50

A  

 

 

Low-set 
triggered

 

High-set 
triggered 
 
Relay(s) which 
energised on 
tripping

 

  

O/C SETTING 
Low Set: 
    1: I>  5.00A 
    2: Curve NI 3/10 
    3: k> 0.1 
High Set: 
    4: I>> 50.00A 
    5: t>> 0.05s 

    