Maintenance and upkeep:

Maintenance and service work should only be carried out by competent technicians with experience and

qualifications in the handling of A2L refrigerants.

The appliance should always be disconnected from the power supply before any work is carried out.

Before maintenance work is carried out all technicians should:

a) Carry out safety checks to ensure the risk of ignition is minimised.

b) Operate with controlled procedures to minimise the risk of flammable gas or vapour being present while

    work is carried out.

c) Ensure all staff in the local area are instructed in the nature of the work being carried out.

d) Not work in confined spaces.

e) Check work areas with an appropriate leak detector prior to and during work to minimise the risk of

    flammable atmospheres.

f) If any hot work is being carried out an appropriate fire extinguisher should be available to hand. Either

   Co2 or dry powder.

g) All possible ignition sources should be kept sufficiently far away from the work area.

h) Adequate ventilation shall be provided when breaking into the refrigeration system. The ventilation should

    safely disperse any released refrigerant to the external atmosphere.

i) When replacing electrical components only spare parts specified by the manufacturer shall be used.

j) Electrical work should be preceded with initial safety checks:

i) All capacitors need to be discharged in a manner that avoids sparks.

ii) No live electical components or wiring should be exposed while charging, recovering or purging the 

    system.

iii) There is continuity of earth bonding.

k) Under no circumstances should potential sources of ignition be used in the searching for or detection

    of refrigerant leaks.

l) On discovery of a leak all refrigerant should be removed before a repair is carried out. The manufacturer

   recommends purging the circuit with an inert gas before brazing.

m) Before charging ensure the refrigeration system is earthed.

SHEET 9 OF 13

Summary of Contents for MCe 9.0-21

Page 1: ...MCe 9 0 21 PORTABLE AIR CONDITIONER PRODUCT MANUAL MCe 9 0 21 SHEET 1 OF 13 ...

Page 2: ...rtant information P3 4 Technical specification P4 Set up and operation P5 6 Setting the digital thermostat P7 Control diagrams P8 Maintenance P9 10 Spare parts P11 12 Wiring diagrams P13 TABLE OF CONTENTS SHEET 2 OF 13 ...

Page 3: ...op of the appliance An air gap of at least 300mm should be allowed at the front and rear of the unit to ensure a clear airflow Do not disconnect the appliance from the supply under load For internal use only Do not use out of doors Warning Exhaust fan liable to start without notice Extension cables should be correctly rated for the load fully unwound and never run through water or over sharp edges...

Page 4: ...size for safe operation WARNING Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour SHEET 4 ...

Page 5: ...aust spigot supplied loose The rear exhaust spigot must be fitted before use Tools required No2 PZ screwdriver 1 Remove the 4 x M5 fixings with star washers at the rear of the machine 2 Use these fixings to secure the exhaust spigot in place Pinch tight Ensure the star washers are refitted Exhaust spigot fitted SHEET 5 OF 13 ...

Page 6: ...compressor will not start if the fan switch is not in the on position or the ambient temperature is below 15 C The compressor is fitted with a start delay timer and will not run for 3 minutes from activation of the cooling switch This device is designed to protect the compressor from repeated start stop cycles Set the digital thermostat to the desired temperature This is the set point During norma...

Page 7: ...oom temperature How to see the set point Defrost key Not used Set key Up down keys Power key Not used The appliance comes factory set at 15 C Push the SET key for more than 2 seconds to change the set point value The value of the set point will be displayed and the C LED starts blinking To change the set point value push the up or down arrows within 10 seconds The minimum set point is 15 C To memo...

Page 8: ...tank Locking castors Discharge hoses Exhaust spigot Digital controller Fans on rocker switch Tank full lamp Cooling on rocker switch Variable fan speed controller Control panel Operation and controls SHEET 8 OF 13 ...

Page 9: ... available to hand Either Co2 or dry powder g All possible ignition sources should be kept sufficiently far away from the work area h Adequate ventilation shall be provided when breaking into the refrigeration system The ventilation should safely disperse any released refrigerant to the external atmosphere i When replacing electrical components only spare parts specified by the manufacturer shall ...

Page 10: ...nk drain mechanism is operating correctly and the drain hose is present and in good condition 3 Regularly inspect the mains cable and plug for signs of damage or wear Do not operate the machine with a damaged mains cable 4 Check that the castors are running freely and that the breaking mechanisms are working correctly Troubleshooting guide SHOULD YOU CONTINUE TO EXPERIENCE PROBLEMS PLEASE CONTACT ...

Page 11: ...33 34 27 29 28 31 32 30 25 1 2 3 4 5 7 8 9 10 11 12 13 14 15 16 18 20 21 22 23 24 41 26 Exploded view 6 17 19 35 SHEET 11 OF 13 ...

Page 12: ...Spare Parts SHEET 12 OF 13 ...

Page 13: ...MCe 9 0 21 Wiring diagram SHEET 13 OF 13 ...

Reviews: