Commissioning
25
7311160-04 09.20
4.3 CO
2
-Content
Guide Values for CO
2
-content
4.4 Nominal heat load
Setting nominal heat load
If none of the gas types specified in the injector pressure table are available at the
site, the nominal load is lower or higher. If, by way of derogation from the factory
setting, a customized nominal power setting is made, the required setting value
(gas flow in L/min) is to be taken from the following table.
Model
Natural Gas E, LL
LPG (propane)
WGB 90/110 C
%
8,3 - 8,8
9,5 - 10,0
WGB 90/110 E
%
8,3 - 8,8
10,3 - 10,8
for WGB 90/110 H
%
8,5 - 9,0
10,3 - 10,8
for BGB 90/110 H
%
8,5 - 9,0
10,3 - 10,8
SGB 120 C/D
%
8,7 - 9,3
10,5 - 11,0
SGB 160 C/D
%
8,7 - 9,3
10,5 - 11,0
SG 320 C/D
%
8,7 - 9,3
10,5 - 11,0
Model
BGB/WGB
90
BGB/WGB
110
SGB 120
C/D
SGB 160
C/D
SGB 320
C/D
Nominalheat load (full load)
kW
90,0
110,0
120,0
160,0
320,0
Gas flow rate in l/min
7,0
214
262
285
381
762
7,5
200
244
266
356
711
8,0
188
229
249
333
667
8,5
176
216
234
314
627
Operating heating value
H
uB
in kWh/m
3
9,0
167
204
221
296
593
9,5
158
193
211
281
561
10,0
150
183
200
367
533
10,5
143
175
191
254
508
11,0
136
167
182
242
485
11,5
130
159
174
232
464