5.2
Assembly of flue cascade systems BK 250/1 and BK 250/2 (flue outlet at the back)
Assemble the components listed in the table as shown in
fig
.
Important
Apply lubricant to gaskets.
Important
Route the flue with a fall towards the combustion equipment so
the condensate can drain from the flue to the central condensate
collector or to the siphon connection. The minimum fall for a
horizontal flue pipe is min. 3 ° (5.5 cm / m).
Fig.6
Assembly (flue outlet at the back)
RA-0001888
1
2
3
4
5
6
2
2
3
2
2
2
6
1 End cover without siphon connection
2 Clamp
3 Tee for flue entry
4 Tee for flue exit
5 End cover with siphon connection
6 Eccentric connector 160/250 or 200/250