background image

 
 

Flair 8 EV-CN8-SD/LS Issue 1 

 

 

 

Chimney Requirements

 

 

 

These appliances must not be fitted into a chimney serving another heating appliance. It is most 
important that there is no obstruction in the flue or chimney. Please ensure that any existing 
chimney is clear of obstruction and swept clean immediately before installation of the new stove. 
Where the chimney is believed to have served an open fire previously it is possible that the higher 
flue gas temperature from a closed appliance may loosen deposits that were previously firmly 
adhered, with the consequent risk of flue blockage. It is therefore recommended that the chimney 
be swept a second time within a month of regular use after installation.  
 
A flue draught minimum of 12 Pascals to a maximum 18 Pascals is required for satisfactory 
appliance performance. A properly built masonry or factory constructed chimney (with a minimum 
vertical height of 5 metres) should ensure a consistent draught (draw). 45° bends can be used in 
the flue run (maximum of four bends) you will need to add an extra 1 metre of vertical flue height 
for each bend.  
 
The flue draught should be checked under fire at high output and if it exceeds the recommended 
maximum, a draught stabiliser must be fitted so that the rate of burning can be controlled, and to 
prevent over firing (See section “Warning Notes”). If you have any doubts about the suitability of 
your chimney, consult your local dealer/stockist or engineer. If your flue draft is below the minimum 
recommendation then it may be necessary to increase the vertical chimney height, add additional 
flue insulation or possibly add a special cowl to the top of the chimney (e.g. anti down draft cowl to 
eliminate wind induced down draft).  
 
The outlet from the chimney should be above the roof of the building in accordance with the 
provisions of Building Regulations Approved Document J. 
 
If installation is into an existing chimney then it must be sound and have no cracks or other faults 
which might allow fumes into the house. Older properties, especially, may have chimney faults or 
the cross section may be too large i.e. more than 230 mm x 230 mm. Remedial action should be 
taken, if required, seeking expert advice, if necessary. If it is found necessary to line the chimney 
then a flue liner suitable for solid fuel must be used in accordance with Building Regulations 
Approved Document J. 
 
If there is no existing chimney then either a prefabricated block chimney in accordance with 
Building Regulations Approved Document J or a twin walled insulated stainless steel flue to BS 
1856-1  can be used. These chimneys must be fitted in accordance with the manufacturer’s 
instructions and Building Regulations. 
 
If a flexible liner is required the liner diameter must not be less than 6” / 150mm. 
 
Any bend in the chimney or connecting fluepipe should not exceed 45°.  90° bends are not 
permitted. . For top flue installations it is possible to sweep through the appliance by removing the 
internal baffle however it is recommended that you provide adequate access (e.g. easily accessible 
soot door). For rear flue connection we recommend the use of a tee section, this should be capped 
at the bottom to catch soot and debris. All joints in the connection between the stove and the 
chimney must be made gastight using fire cement and where necessary fire-proof rope infill.  
 

Please refer to British Standards BS EN 15287-1:2007 design, installation and 
commissioning of chimneys for additional requirements.

 

 

Summary of Contents for Flair 8 EV-CN8-LS

Page 1: ...D LS Issue 1 1 Installation Operating Instructions Covering Models Flair 8 EV CN8 SD EV CN8 LS Wood Burning Stoves Tested to EN 13240 These appliances must be installed and commissioned by a HETAS reg...

Page 2: ...ation Controls Layout 12 Controls Explained 13 Air wash System 13 Ash Pan 13 Recommended Fuels 14 Lighting the Stove Kindling Stage 15 Burning Wood 16 Warning Notes 17 Maintenance Ash Removal 18 Chimn...

Page 3: ...llation must comply with current Building Regulations Local Authority By laws and other specifications or regulations as they affect the installation of the stove It should be noted that the Building...

Page 4: ...re should be taken to avoid the possibility of personal injury CO Alarms Building regulations require that whenever a new or replacement fixed solid fuel or wood biomass appliance is installed in a dw...

Page 5: ...ed and tested for intermittent use European standards need to be complied with when installing this appliance Flair 8 EV CN8 SD EV CN8 LS Nominal Heat Output Wood to Room kW 8 Efficiency 80 Weight Kg...

Page 6: ...Flair 8 EV CN8 SD LS Issue 1 6 Dimensions ALL DIMENSIONS ARE IN MILIMETRES...

Page 7: ...of the stove to carpets or wooden floors must be at least 300mm As it is possible that on opening the door of the stove for fuel to fall out a fender must be fitted if the hearth is flush with the ca...

Page 8: ...the top of the chimney e g anti down draft cowl to eliminate wind induced down draft The outlet from the chimney should be above the roof of the building in accordance with the provisions of Building...

Page 9: ...ve a fixed permanent air vent see Building Regulations Approved Document J for further information Calculating the vent For new build you will need to provide 8 x 550mm2 4400mm2 free air Older propert...

Page 10: ...EV CN8 SD LS Issue 1 10 Assembly The diagram below shows the stove with all internals taken out To install these parts follow the numbered sequence above to un install simply follow the sequence in r...

Page 11: ...on and commissioning ensure that the operating instructions for the stove are left with the consumer Ensure to advise the customer on the correct use of the appliance and warn them to use only the rec...

Page 12: ...elow shows the position of the two air controls these controls need to be operated correctly to control the combustion rate of the stove T The main door handle on these appliances will get hot Use the...

Page 13: ...out to control the total amount of air required for suitable combustion The secondary air intake brings in air above the grate this air is drawn down the inside of the glass creating the AIRWASH syst...

Page 14: ...ut the stove and flue The coating of soot and tar in the chimney is volatile creating a high risk of chimney fires A growing tree contains a high percentage of water the wood needs to be dried out sea...

Page 15: ...enerous amount of dry kindling onto the newspaper ensure their is sufficient air gaps between the kindling a criss cross or pyramid style pattern is ideal to accomplish this Kindling Newspaper Stage 2...

Page 16: ...down the Secondary Air Intake as required You can now control the burn rate of the stove using the secondary air intake You are looking for a controlled flame not smouldering in the embers or licking...

Page 17: ...H OVER FIRING WILL NOT BE COVERED BY THE WARRANTY Fumes Properly installed operated and maintained this stove will not emit fumes into the dwelling Occasional fumes from de ashing and re fuelling may...

Page 18: ...open fire previously it is possible that the higher flue gas temperature from a closed appliance may loosen deposits that were previously firmly adhered with the consequent risk of flue blockage It is...

Page 19: ...e chimney to prevent heat being drawn up the chimney to waste Green or wet wood is being burnt The chimney has excessive draw this is unusual Seek installer advice with regard to installing a Flue Dra...

Page 20: ..._______________________ Address _________________________________________________________________ Telephone Inc area code ____________________________________________________ HETAS Registration Number...

Page 21: ...ght Firebrick 9 Back Right Firebrick 10 Front Right Firebrick 11 Ashpan 12 Door 13 Glass 14 Handle 15 Left Hinge Assy 16 Latch Assy 17 Base 18 Secondary Air Control 19 Primary Air Control 20 Secondary...

Page 22: ...GmbH NOTIFIED BODY RRF 1625 Firmensitz Im Lipperfeld 34 b D 46047 Oberhausen The following harmonised standards and Technical specifications have been met and comply with good engineering practice an...

Page 23: ...o COMPANY NAME COMPANY ADDRESS POSTCODE 3RD YEAR SERVICE completion date SERVICE ENGINEER REG No COMPANY NAME COMPANY ADDRESS POSTCODE 4TH YEAR SERVICE completion date SERVICE ENGINEER REG No COMPANY...

Page 24: ...ned units Replaced parts or components will become the property of Broseley Fires Should you wish to claim under the warranty please contact the supplier dealer from whom you purchased the appliance D...

Reviews: