BrookVent Aircycle 1.1 Installation And Maintenance Manual Download Page 12

aircycle 1.1/1.2 – In-built Control & SB  

Last Updated 02-01-13  

 Page 12 of 14 

 

6.0 Fan Speed Control 

 

The fan speeds of the unit are controlled by two potentiometers (Speed Pots) on top of the unit; 
these are clearly marked “Trickle” and “Boost”.  
 
These two separate speed options allow one speed to be set for normal day to day operation (I.e. 
Trickle) and an increased speed to be set (I.e. Boost) that operates only when the Grey switch wire is 
triggered by a 240v boost signal such as a Wall Switch or Humidity Stat. 
 
If the Boost is required to be set, it should always be set higher than the Trickle. 
 
Turing these Speed Pots clockwise increases the fan speed. 
 
 
 
 

 
 
 

 

 

 

6.1 Tempering Summer Bypass 

 

The Tempering Summer Bypass, unique to Brookvent, operates on a linear scale between 20 

Degrees Celsius (No Summer Bypass) and 27 Degrees Celsius (Full Summer Bypass); gradually 

increasing the amount of air directed around the Heat Recovery Core as the temperature of the 

extract air from the home rises thus comfortably regulating the indoor air temperature during 

warmer months. 

This feature is factory set, automatic, and requires no maintenance. 

 

 

 

 

 

Trickle 

Boost 

Summary of Contents for Aircycle 1.1

Page 1: ...e 1 of 14 Heat Recovery Ventilation Applicable to aircycle 1 1 1 2 Ws For Wall Mounting with In built Control Summer Bypass Installation and Maintenance Instructions for the Installer Please refer to...

Page 2: ...by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the app...

Page 3: ...and supplied into the habitable rooms such as bedrooms dining rooms and living rooms 1 1 Model Variations This installation manual refers to the Brookvent aircycle 1 1 and pertains to the following m...

Page 4: ...quirements and local additional rules Explanation of the ventilation system to the user Warning for the user to check or replace the air filters on time All the above as set out in the latest edition...

Page 5: ...aircycle 1 1 1 2 In built Control SB Last Updated 02 01 13 Page 5 of 14 3 0 Specifications Front...

Page 6: ...r Media G2 3 Electrical 240V EC Quiet Fan Technology Controls Extremely Efficient In built Control Board Single 240v boost input Light switch humidistat PIR etc Single 240v boost supply line optional...

Page 7: ...aircycle 1 1 1 2 In built Control SB Last Updated 02 01 13 Page 7 of 14 3 2 Airflow Pressure Performance Curve Airflow Performance Curve...

Page 8: ...to ductwork wiring and the connection of the condensate drain It is important that filters to the system can also be accessed for replacement 4 1 Mounting The aircycle 1 1 1 2 Ws is designed for Wall...

Page 9: ...es to a minimum Where it is not possible to continue throughout the dwelling in rigid 125mm diameter round pipe due to the void spaces available a conversion to rigid 204mm x 60mm flat rectangular duc...

Page 10: ...ction on the bottom of the unit The condensate drain should incorporate a P Trap or equivalent as shown before being discharged into the waste drainage system of the dwelling The P Trap should be fill...

Page 11: ...s to comply with current IEE wiring regulations A switch or circuit breaker must be used in the power supply circuit It should be in close proximity to the HRV unit and should be clearly marked as the...

Page 12: ...uch as a Wall Switch or Humidity Stat If the Boost is required to be set it should always be set higher than the Trickle Turing these Speed Pots clockwise increases the fan speed 6 1 Tempering Summer...

Page 13: ...o the levels required 7 1 Filter Replacement The filters of this HRV unit will usually need to be changed every 6 12 months depending on occupancy use and the type of environment the dwelling is locat...

Page 14: ...carried out to ensure that the required air flows are achieved throughout the property The volume airflow at each point should be measured using a suitably calibrated Airflow Meter anemometer this is...

Reviews: