5.3.3 Fault Test
Step 1.
On the termination board disconnect any wire of the three wires
(Positive, Negative, Interconnect) to the smoke alarms of zone1.
Ensure:
* Zone1 fault LED illuminates
* The panel buzzer will sound continuously.
* Activate the sounder silence switch. The buzzer will pulse once
every 40 seconds (chirp).
* Defect Mode relay contact will changeover.
Step 2.
Restore the wire, amber fault LED extinguishes. The Panel buzzer will
be silenced and defect mode contacts return to normal.
Step 3.
Repeat steps 1 and 2 for each zone.
Note:
Many options on the Residential Panel are user selectable. Additional testing
may be required if the system has been customised. Refer to system as installed
details.
5.3.4 Power Supply
Power supply voltages are pre-set at the factory to 13.7V DC.
Operate the AC supply switch off and on at least five times to check that the system
will not false alarm from AC power interruptions.
5.3.5 Field Testing
With the Control Panel in its NORMAL MODE:
Step 1.
Proceed to the smoke alarm on zone 1 which contains the end of line
(EOL) device. Remove the EOL and ensure that the control panel has
registered a fault condition. For this zone reconnect the EOL and the
fault condition clears.
Step 2.
Press and hold the test button for at least 5 seconds, Smoke alarm will
activate, ensure that an alarm has registered at the panel. All ancillary
outputs should activate.
Step 3.
Turn keyswitch to ‘OFF’ then back to ‘ON’. The alarm led will extinguish
and all ancillary outputs will reset.
Step 4.
Repeat steps 1 - 3 for each zone.
Step 5.
Press ‘Locate’ and turn key switch to ‘Fire’ (FIRE/LOCATE MODE).
Press Ancillary Isolate. Proceed to each smoke alarm on each zone
in turn and activate the Test button. The individual smoke/heat alarm
will sound standalone. Check any associated Remote Indicator lights.