8. Check that all cable terminations within the control panel are suitably grouped, tidy
and secured as appropriate, and that all protective shrouds are in place.
Yes No Not Applicable
9. Check that both the primary and secondary power sources are of a suitable type
and capacity to meet the systems maximum load requirements, and are capable
of meeting the nominated standby and alarm times.
Yes No Not Applicable
10. Check the float voltage to ensure the charger setting is correct.
Battery type: ……………………………………………….
Battery capacity: …………………………………………..
Float Voltage (27.5 +/-
0.5%): ……………………………….
11.
With primary power supplied check that the control panel ‘Mains on’ indicator and
the green power on indicators for all Smoke / Heat Alarms are illuminated.
Yes No Not Applicable
12. Where the Smoke / Heat Alarms are interconnected, locate the last unit on the
circuit and check that the operation of the test button causes all Smoke / Heat
Alarms to sound.
Yes No Not Applicable
13. Where the Smoke / Heat Alarms are interconnected and with all Smoke / heat
Alarms sounding, check that the locate function silences all Smoke / Heat Alarms
except the unit initiating the alarm, and that the locate control indicator illuminates.
Yes No Not Applicable
14. Where the Smoke / Heat Alarms are interconnected and with all Smoke / Heat
Alarms sounding, check that the isolate function silences all Smoke / Heat Alarms,
and that the isolate control indicator illuminates.
Yes No Not Applicable
15. Open circuit and short circuit the end of line device on the manual call point circuit,
or conduct other appropriate tests to ensure that fault and alarm conditions are
operating correctly, and that the sounder silence facility functions correctly.
Yes No Not Applicable
16. Open circuit and short circuit the end of line device on the alarm output circuit to
ensure that fault and alarm conditions are operating correctly.
Yes No Not Applicable
17. Conduct appropriate tests to ensure that each output functions as required.
Yes No Not Applicable
Summary of Contents for ALARM 2000
Page 1: ...SITE MANUAL Issue 5 ALARM 2000 Residential Fire System MA260 November 2017...
Page 40: ...Site Manual Alarm 2000 Iss 5 40 Charger low 26 5V Battery low 23 8V Battery fail 21 0V...
Page 42: ...Site Manual Alarm 2000 Iss 5 42 7 Location and type of smoke heat alarms Location Type Model...
Page 43: ...Site Manual Alarm 2000 Iss 5 43 8 Location and type of ancillary equipment Location Type Model...
Page 63: ...Site Manual Alarm 2000 Iss 5 63...
Page 64: ...Site Manual Alarm 2000 Iss 5 64...
Page 65: ...Site Manual Alarm 2000 Iss 5 65...