Controls:
Alarm Locate
- silences all Smoke / Heat Alarms except the Alarm(s) that have
actuated. Used to locate the source of the fire or a faulty or contaminated Smoke /
Heat Alarm. Automatically resets after approximately five (5) minutes.
Alarm Isolate
- silences all Smoke / Heat Alarms. Used to silence the units while
smokes, cooking fumes or steam are cleared from the Smoke / Heat Alarm.
Automatically resets after approximately five (5) minutes.
Sounder Silence
- mutes the integral RFIP fault sounder. Automatically resets to
normal after fault condition is cleared.
Key Switch:
AUTO
- system 'ON', set for automatic alarm response.
OFF
- system 'OFF', charger 'on', system off output activated.
Note: A red indicator on the front panel adjacent the key switch will flash to
provide a local warning to the occupants that the system has been turned
'OFF'. A signal output is provided for remote monitoring of this condition.
FIRE
- all Smoke/Heat Alarms sound, alarm outputs selected activate.
Indicators:
Mains ON, green LED, steady
System OFF, red LED, flashing
Alarm Activated, red LED, flashing
Alarm Output Fault, amber LED, steady
MCP Input Fault, amber LED, steady
Alarm Locate selected, amber LED, steady
Alarm Isolate selected, amber LED, steady
Sounder Silence selected, amber LED, steady
Power Supply Fault
– optional, amber LED, steady
Summary of Contents for ALARM 2000
Page 1: ...SITE MANUAL Issue 5 ALARM 2000 Residential Fire System MA260 November 2017...
Page 40: ...Site Manual Alarm 2000 Iss 5 40 Charger low 26 5V Battery low 23 8V Battery fail 21 0V...
Page 42: ...Site Manual Alarm 2000 Iss 5 42 7 Location and type of smoke heat alarms Location Type Model...
Page 43: ...Site Manual Alarm 2000 Iss 5 43 8 Location and type of ancillary equipment Location Type Model...
Page 63: ...Site Manual Alarm 2000 Iss 5 63...
Page 64: ...Site Manual Alarm 2000 Iss 5 64...
Page 65: ...Site Manual Alarm 2000 Iss 5 65...