Bronkhorst®
Instruction Manual ES-FLOW™ 1xxC
9.17.153A
29
6.1.4
Network configuration
Changes made to the network settings will
not
be restored by a factory reset.
Default configuration
Network configuration is done ex factory as indicated on the serial number label or in the technical specifications. The table
below shows the supported configurations for the available interface protocols (default settings are printed in bold):
Protocol
(RS-232)
FLOW-BUS
(RS-485)
Modbus
(RTU/ASCII)
PROFIBUS DP
CANopen
DeviceNet™
Address
3
3
…125
1
…247
0…
126
1…
127
0…
63
Baud Rate
9600
19200
38400
57600
115200
230400
460800
187500
400000
9600
19200
38400
56000
57600
115200
128000
256000
(autodetect)
9600
19200
45450
93750
187500
500000
1500000
3000000
6000000
12000000
10000
20000
50000
125000
250000
500000
800000
1000000
125000
250000
500000
Parity
0
0
0, 1,
2
2
0
0
Network configuration for Ethernet based fieldbus types is done automatically via the Ethernet protocol.
Communication via fieldbus connector (RS-485)
Use the following parameters to configure the instrument for communication through the fieldbus connector (5-pin M12):
Fieldbus 1 Address
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…255
199
125/10
0x0FAA/4011
Fieldbus 1 Baud Rate
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned long
RW
B
0…1.0E10
201
125/9
0xFD48…0xFD49/64841…64842
Fieldbus 1 Parity
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…2
335
125/12
0x0FAC/4013
The following values are supported:
Value
Description
0
No parity
1
Odd parity
2
Even parity
Communication via standard connector (RS-232/RS-485)
Use the following parameters to configure the instrument for communication through the 8-pin M12 connector:
Fieldbus 2 Address
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
B
0…255
309
124/10
0x0F8A/3979