• Connect one meter test lead to a good ground.
Connect the other test lead to the stator power
winding (Figure 3.45).
A reading of infinity should be measured. A reading of other
than infinity indicates a stator winding
shorted to ground.
Testing Dual Voltage Type Power Windings
• Set a VOM to the “OHM” scale.
• Connect the test leads to the stator wires #11 and
#22.
Measure the resistance and compare it to the nominal
resistance from the appropriate table
(Briggs & Stratton Power Products
®
“Portable Generator
Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later).
• Connect the test leads to the stator wires #22, and
#44.
Measure the resistance and compare it to the nominal
resistance from the appropriate table. Analyze the results the
same as in “Testing Single Voltage Type Power Winding”.
• Connect one meter test lead to a good ground.
Connect the other test lead to the stator power
winding. (Refer back to Figure 3.45).
A reading of infinity should be measured. A reading of other
than infinity indicates a stator winding
shorted to ground.
83
Section 3 • Generator Diagnostics and Adjustments
Portable Generator Familiarization & Troubleshooting Guide
Replace Stator
Replace Stator
Figure 3.45 — Testing For Short To Ground
Summary of Contents for 86262GS
Page 20: ...Section 1 Generator Fundamentals Portable Generator Familiarization Troubleshooting Guide 18...
Page 110: ...108 Section 4 Generator Assemblies Portable Generator Familiarization Troubleshooting Guide...
Page 117: ...115 Section 4 Generator Assemblies Portable Generator Familiarization Troubleshooting Guide...
Page 118: ...116 Section 4 Generator Assemblies Portable Generator Familiarization Troubleshooting Guide...
Page 119: ...GENERAC TORQUE TABLE Appendix A Portable Generator Familiarization Troubleshooting Guide 117...
Page 125: ...123 Appendix A Portable Generator Familiarization Troubleshooting Guide...
Page 126: ...Appendix A Portable Generator Familiarization Troubleshooting Guide 124...
Page 127: ......