Problem
Cause
Correction
Eng ine is running, but no AC output
is available.
1. Circuit breaker open or defective.
2. Service code in generating set control
board.
3. Poor wiring connections or defective
transfer switch.
1. Reset or replace circuit breaker.
2. Contact local service provider.
3. Check and repair or contact local
service facility.
Eng ine runs well at no-load but “bogs down”
when loads are connected.
1. Generating set is overloaded.
2. Short circuit in a connected load.
3. Shorted generating set circuit.
4. Fuel pressure or mixture is incorrect.
5. Kinked fuel line between regulator and
engine.
1. Remove one or more loads.
2. Disconnect shorted electrical load.
3. Contact local service facility.
4. See Gaseous Fuel System in the
installation manual.
5. Remove kink. Replace if necessay.
Eng ine will not start; or starts and runs rough.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
4. Clogged air filter.
1. Install (new) 15 Amp fuse. See System
Control Board
2. Open fuel valve(s); check propane tank
3. Replace battery.
4. Clean or replace air filter.
Engine shuts down during operation.
1. Fuel supply turned off or depleted.
2. Control board digital display shows a
service code code.
1. Check fuel valves, fill propane tank.
2. Refer to Service code Detection
System.
Loss of power on circuits.
1. Generating set circuit breaker is open.
2. Transfer switch problems.
1. Reset circuit breaker.
2. See transfer switch manual.
Unit will not exercise.
1. Control board not set to AUTO.
2. Exercise timer not set or set to OFF.
3. Unit date and time not set.
4. Failed battery.
5. 15 Amp fuse missing or blown.
1. Press AUTO button on control board.
2. Set exercise timer.
3. Set unit date and time.
4. Replace battery.
5. Install (new) 15 Amp fuse. See System
Control Board.
Excessive Vibration
1. Loose mechanical fastener.
1. Check and repair or contact local
service facility.
Odor of fuel
1. Fuel leak.
1. Turn off manual shutoff fuel valve.
Contact local service facility.
Utility power returns, unit does not stop
1. Blown fuses in transfer switch.
2. 5 minute minimum runtime not lapsed.
3. Poor wire connection or defective
controllers.
1. Install (new) fuses.
2. Wait 5 minutes.
3. Check, repair or contact local service
facility.
Troubleshooting
Summary of Contents for 6kVA Generating Set
Page 1: ...Operator s Manual Generating Set EAC...
Page 32: ...32 PAGE LEFT INTENTIONALLY BLANK...
Page 33: ...EAC...
Page 35: ...35 4 7 7 7 7 8 9 10 11 13 15 19 19 19 15 19 19 21 21 23 24 28 31 31...
Page 36: ...36...
Page 37: ...37 NEGATIVE NEG OFF 15...
Page 38: ...38 15 Negative NEG 1 5 1 5 30 5 1 5 15A 15...
Page 39: ...39 90...
Page 40: ...40 HD5 2500 3 5 2 5 90 10 20 3 5 300 1 5 6 C 25 C...
Page 41: ...41 1 2 A 1 5 1 5 30 5 1 5...
Page 42: ...42 5W30 ATO 15 A 1 2 25 3 3 0 5 5...
Page 43: ...43 6 A B C D E F G H 12 J B C D F H J E G...
Page 44: ...44 8 A B C D E F G H 12 J B C D F H J E G...
Page 45: ...45 A...
Page 46: ...46 1 A 2 1 B 2 C 1 2 C B...
Page 47: ...47 A B USB C AUTO OFF OFF 5 MANUAL AUTO OFF D 15 A 15A E USB F B C F E D...
Page 51: ...51 API SJ CF 5W 30 12 AUTO 15 15 15 70 3 80 5 1 5 5 AUTO OFF 15...
Page 53: ...53 1 OFF 2 3 OFF 4 15 5 6 15 ON AUTO OFF 5 30 AUTO 15 15 8 FULL...
Page 54: ...54 10 10 2 55 3...
Page 55: ...55 15 5 8 100 1 OFF 2 15 3 1 7 25 4 15 5 AUTO...
Page 58: ...58 1 OFF 2 15 3 4 5 6 7 8 9 1 2 3 4 10 11 12 13 1 2 3 4 5...
Page 59: ...59 1 2 3 4 5 20 180 1 2 www briggsandstratton com 15...
Page 64: ...80005870 Rev...