20
Setting Exercise Timer
The generating set is equipped with an exercise
timer. During the exercise period, the unit runs for
approximately 20 minutes and then shuts down.
Electrical load transfer DOES NOT occur during the
exercise cycle (unless an utility power outage occurs).
The generating set will only enter the exercise cycle if
the unit is in the AUTO mode and this exact procedure
is followed.
To set the exercise timer:
NOTICE
The generating set is set with a deservice
code exercise cycle setting of Tuesday at 2:00 P.M,
Central Time. To change the cycle setting, proceed to
the following steps:
1. Choose the day and time you want your
generating set to exercise.
2. Press and hold the left arrow and right arrow
simultaneously for 3 seconds to enter the General
Set-Up program mode. See General Set-Up flow
chart in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE
Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow
to toggle through between 1 and 12. Choose
the hour of day you want the generating set to
exercise then hit the “OK” button.
SELECT MINUTE: Use the left of right arrow to
toggle between :00 and :59. Choose the minute
of the day you want the generating set to exercise
then hit the “OK” button.
SELECT AM/PM: Use the left of right arrow to
toggle between AM and PM. Once chosen, hit the
“OK” button.
NOTICE
During the weekly exercise cycle, the
generating set will run for 20 minutes, but it will
not supply power to the home. During the exercise
cycle, the in-home monitor will continue blinking the
Generating set READY green LED.
If you want to change the day and time the unit
exercises, simply perform the procedure again.
To turn off the generating set exercise cycle, go to
the OFF selection within the day of the week menu
and press OK. The display will then scroll: EXERCISE
CYCLE OFF.
CAUTION
With the system switch set to
AUTO
,
the engine could crank and start at any
time without warning, resulting in minor or
moderate injury.
• To prevent possible injury that may be caused by
such sudden starts, always set the system switch to
OFF
if performing maintenance on the system.
• Remove the 15 Amp fuse before working on or
around the generating set or transfer switch.
Summary of Contents for 6kVA Generating Set
Page 1: ...Operator s Manual Generating Set EAC...
Page 32: ...32 PAGE LEFT INTENTIONALLY BLANK...
Page 33: ...EAC...
Page 35: ...35 4 7 7 7 7 8 9 10 11 13 15 19 19 19 15 19 19 21 21 23 24 28 31 31...
Page 36: ...36...
Page 37: ...37 NEGATIVE NEG OFF 15...
Page 38: ...38 15 Negative NEG 1 5 1 5 30 5 1 5 15A 15...
Page 39: ...39 90...
Page 40: ...40 HD5 2500 3 5 2 5 90 10 20 3 5 300 1 5 6 C 25 C...
Page 41: ...41 1 2 A 1 5 1 5 30 5 1 5...
Page 42: ...42 5W30 ATO 15 A 1 2 25 3 3 0 5 5...
Page 43: ...43 6 A B C D E F G H 12 J B C D F H J E G...
Page 44: ...44 8 A B C D E F G H 12 J B C D F H J E G...
Page 45: ...45 A...
Page 46: ...46 1 A 2 1 B 2 C 1 2 C B...
Page 47: ...47 A B USB C AUTO OFF OFF 5 MANUAL AUTO OFF D 15 A 15A E USB F B C F E D...
Page 51: ...51 API SJ CF 5W 30 12 AUTO 15 15 15 70 3 80 5 1 5 5 AUTO OFF 15...
Page 53: ...53 1 OFF 2 3 OFF 4 15 5 6 15 ON AUTO OFF 5 30 AUTO 15 15 8 FULL...
Page 54: ...54 10 10 2 55 3...
Page 55: ...55 15 5 8 100 1 OFF 2 15 3 1 7 25 4 15 5 AUTO...
Page 58: ...58 1 OFF 2 15 3 4 5 6 7 8 9 1 2 3 4 10 11 12 13 1 2 3 4 5...
Page 59: ...59 1 2 3 4 5 20 180 1 2 www briggsandstratton com 15...
Page 64: ...80005870 Rev...