background image

12

Briggs & Stratton Power Products Home Generator System

Owners Manual

4A. For electric starting, press start switch on generator

cradle.To prolong the life of the starter components,
press the starter button for no more than 15 seconds,
and pause for 30 seconds.

4B. For manual starting, grasp starter grip and pull slowly

until you feel some resistance.Then pull cord out with
rapid full arm stroke. Let rope return slowly. Do Not
let rope “snap back” against starter.

5.

If the choke lever has been moved to the “Choke
position to start the engine, gradually move it to the
Run” position as the engine warms up.

NOTE: If engine still fails to start after 3 pulls, check for
proper oil level in crankcase.This unit is equipped with a
Low Oil Shutdown System. See engine manual.

Refer to the engine owner’s manual for complete
starting instructions.

Connecting Electrical Loads

• Let engine stabilize and warm up for a few minutes after

starting.

• Turn ON the generator main breaker to energize the

30 Amp connector.

• Connect the unit to the power inlet box, following the

connection instructions given in the section “Switch to
Generator Power” on page 15. Or plug in and turn on
the desired 120 and/or 240 Volt AC, single phase,
60 Hertz electrical loads.

• Do Not connect 240 Volt loads to the 120 Volt

receptacles.

• Do Not connect 3–phase loads to the generator.

• Do Not connect 50 Hz loads to the generator.

• DO NOT OVERLOAD THE GENERATOR. When

not used with the semi-automatic transfer switch, add up
the rated watts (or amps) of all loads to be connected at
one time.This total should not be greater than the rated
wattage/amperage capacity of the generator. See “Don’t
Overload the Generator” on page 14.

Stopping the Engine

• Unplug all electrical loads from generator panel

receptacles. Never start or stop engine with electrical
devices plugged in and turned on.

• Let engine run at no–load for 30 seconds to stabilize the

internal temperatures of engine and generator.

• Move the fuel valve to the “Off” position.
• Wait for the engine to idle down.
• Move the rocker switch to the “Stop” position.

RECEPTACLES

120 Volt AC, 20 Amp, Duplex

Receptacle

Each receptacle (Figure 11) is protected against overload by
a 20 Amp push–to–reset circuit breaker.

Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2400 Watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).

120/240 Volt AC, 30 Amp, Locking

Receptacle

Use this plug to connect the unit to the connection box
with the supplied cord.

A NEMA L14–30 plug is used with this receptacle. Connect
a 4–wire cord set rated for 250 Volt AC loads at 30 Amps
(or greater) (Figure 12).You can use the same 4–wire cord
if you plan to run a 120 Volt load.

Figure 11 — 120 Volt AC, 20 Amp, Duplex Receptacle

Summary of Contents for 1678

Page 1: ...da es justa un momento lejos Vous avez des questions Vous n avez pas besoin d aller loin pour trouver de l aide Call Home Standby Helpline Llamada L nea Directa de Reserva de Hogar Appelez Ligne Direc...

Page 2: ...symbol indicates a situation that could result in equipment damage Follow safety messages to avoid or reduce the risk of injury or death The engine exhaust from this product contains chemicals known t...

Page 3: ...id and is extremely caustic Contact with battery fluid will cause severe chemical burns DANGER Do not touch hot surfaces Allow equipment to cool before touching Running engines produce heat Temperatur...

Page 4: ...formed choices and communicate effectively with your installation contractor s Read and understand the Owner Orientation Section of this manual BEFORE contracting or starting your HGS installation To...

Page 5: ...92 cm from combustible material NFPA 37 Leave at least 3 ft 92 cm all around for access to the generator The unit s exhaust port must be at least 5 ft 152 cm from any building opening window door vent...

Page 6: ...hts can be taken from light bulbs The rated wattage of tools appliances and motors can usually be found on a data plate or decal affixed to the device If the appliance tool or motor does not give watt...

Page 7: ...t the power transfer system components and conduit 3 Conduit fittings wire nuts and insulated copper wire for connecting the semi automatic transfer switch to the outside connection box Delivery Inspe...

Page 8: ...n valve facing outward 3B Place one end of the needle nose pliers on the bottom of the axle and the other end of the pliers on top of the e ring Seat the e ring by pressing the pliers closed 4 Slide t...

Page 9: ...fill fuel tank when engine is running or hot Allow unit to cool for two minutes before refueling Do Not light a cigarette or smoke when filling the fuel tank WARNING Do Not overfill the fuel tank Alwa...

Page 10: ...of dirt and dust that gets in the engine Choke Lever Used when starting a cold engine Circuit Breakers AC Each receptacle is provided with a circuit breaker to protect the generator against electrical...

Page 11: ...rovided Figure 7 to make the grounding attachment Connecting a No 12 AWG American Wire Gauge stranded copper wire to the grounding wing nut and to an earth driven copper or brass grounding rod electro...

Page 12: ...o Not connect 3 phase loads to the generator Do Not connect 50 Hz loads to the generator DO NOT OVERLOAD THE GENERATOR When not used with the semi automatic transfer switch add up the rated watts or a...

Page 13: ...rator is running How to Use the Battery Charger Use the battery float charger jack to keep the starting battery charged and ready for use Battery charging should be done in a dry location such as insi...

Page 14: ...the engine as described in this manual 2 Plug in and turn on the first load preferably the largest load you have 3 Permit the generator output to stabilize engine runs smoothly and attached device ope...

Page 15: ...enerator control panel Start the generator using instructions given in the section Operating the Generator on page 11 5 Close the generators main circuit breaker 6 After a ten second delay the transfe...

Page 16: ...the house connector box see Figure 15 4 At the generator connect the other end of the power cord to the generator see Figure 16 Make sure the circuit breaker on the generator is open OFF 5 Start the g...

Page 17: ...ON T POLLUTE CONSERVE RESOURCES RETURN USED OIL TO COLLECTION CENTERS Generator Maintenance Generator maintenance consists of keeping the unit clean and dry Operate and store the unit in a clean dry e...

Page 18: ...ge See engine owner s manual for instructions Other Storage Tips To prevent gum from forming in fuel system or on essential carburetor parts add fuel stabilizer into fuel tank and fill with fresh gaso...

Page 19: ...gasoline 9 Overchoking 10 Low oil level 11 Excessively rich fuel mixture 12 Intake valve stuck open or closed 13 Engine has lost compression 14 Failed battery 1 Set switch to On 2 Turn fuel valve to...

Page 20: ...20 Briggs Stratton Power Products Home Generator System Owners Manual NOTES...

Reviews: