Bray Series 70 Installation, Operation And Maintenance Manual Download Page 6

4

Series 70

Servo NXT - EtherNet/IP

Installation, Operation and Maintenance Manual

3.1 Operational Modes
3.1.1 Remote Mode

By default, the operating mode of the Servo 
NXT EIP is Remote Mode, where the valve 
is positioned based on commands from the 
EtherNet/IP network. Exiting another mode of 
operation generally results in the Servo NXT EIP 
returning to remote mode. 

3.1.2 Local Mode

Local Mode is entered if a connection is made 
to the Control Box terminals and one or both 
terminal voltages are pulled low. This allows the 
Servo NXT EIP to be controlled by a local control 
box, mounted to or near the actuator.

This mode of operation prevents remote 
operation of the Servo NXT EIP. Once exiting 
Local Mode, the unit will return to Remote 
Mode. 

3.1.3 Manual Mode

This operating mode allows for the actuator to 
be controlled directly from the buttons on the 
Servo NXT EIP. By utilizing the keypad, the user 
can change the position of the valve with a 
single button press. 

Manual mode is exited in the same way it is 
entered: by pressing and holding the manual 
mode button for 1 second. While in manual 
mode, the indicator next to the manual mode 
button remains lit. Manual mode can only be 
entered when the unit is in Remote Mode. 

This mode allows the unit to be positioned using 
the buttons on the Servo NXT EIP. 

•  Up arrow button – energizes actuator in the 

open direction

•  Down arrow button – energizes actuator in 

the close direction

•  Enter button – brakes the actuator if it is 

operating

This mode of operation prevents remote 
operation of the Servo NXT EIP. Once exiting 
Manual Mode, the unit will return to Remote 
Mode. 

3.1.4 Autocalibration Mode

The Servo NXT EIP uses an automated calibration 
sequence to determine the operating points 
for the application in which it is installed. These 
operating points allow the Servo NXT EIP to 
calculate the correct feedback position of the 
product, making autocalibration an important 
step during commissioning. 

Servo NXT EIP units that have not been 
calibrated will flash the indicator next to 
autocalibration button to show that they are 
using default values for calculating position. 
Autocalibration Mode is entered by pressing 
and holding the Autocalibration button for at 
least 3 seconds. While in Autocalibration Mode, 
the autocalibration indicator remains lit. Upon 
completion of the autocalibration sequence, the 
autocalibration indicator will no longer flash and 
remain off, indicating that the new parameters 
have been stored in memory. 

If a fault occurs during autocalibration, then 
the autocalibration sequence is aborted and 
all the fault LEDs will start flashing to indicate 
a failed autocalibration attempt. The unit will 
not operate while this fault is active. To clear 
the fault, the handwheel can be pulled out to 
indicate operator interaction. Additionally, there 
is also an output bit that can be toggled to clear 
the fault.

No other operating modes can be entered during 
autocalibration and entering Autocalibration 
Mode will override any previous mode of 
operation. This mode of operation prevents 
remote operation of the Servo NXT EIP. Once 
exiting Autocalibration Mode, the unit will return 
to Remote Mode. 

Summary of Contents for Series 70

Page 1: ...ETHERNET IP Installation Operation and Maintenance Manual THE HIGH PERFORMANCE COMPANY BRAY COM Network Status Mac ID 125K 250K Baud Rate Reprogram Open Close Controller Status Autocal Begin Autocali...

Page 2: ...FOR MORE INFORMATION ON THIS PRODUCT AND OTHER BRAY PRODUCTS PLEASE VISIT OUR WEBSITE www bray com...

Page 3: ...4 2 Power Connections 6 4 2 1 Input Power 6 4 2 2 Heater optional 6 4 2 3 Motor 6 4 3 Factory Connections 6 4 3 1 Limit Switches 6 4 3 2 Torque Switches optional 6 4 3 3 Handwheel Switch 6 4 3 4 Contr...

Page 4: ...tch 10 4 5 5 Enter Switch 10 5 0 EtherNet IP Interface 10 5 1 EtherNet IP Conformance 10 5 2 Scanner Configuration 10 5 3 Address Assignment 10 5 4 Establish Connection 11 5 4 1 Input Assembly Data 12...

Page 5: ...0 Servo NXT EtherNet IP to establish and maintain the desired process setpoint 2 1 Definition of Terms Servo NXT EIP Bray EtherNet IP based controller primarily intended for use in the Series 70 elect...

Page 6: ...This mode of operation prevents remote operation of the Servo NXT EIP Once exiting Manual Mode the unit will return to Remote Mode 3 1 4 Autocalibration Mode The Servo NXT EIP uses an automated calibr...

Page 7: ...Bray logo Red Fault LEDs Limit Switch fault Handwheel fault Torque fault Feedback fault White Autocalibration LED White Manual Mode LED User switches Autocalibration switch Manual Mode switch Up arro...

Page 8: ...These switches prevent the Servo NXT EIP from operating the actuator to a point where the gearing could bind up and become damaged These switches are engaged by a cam shaft coupled to the output gear...

Page 9: ...4 3 4 Control Box optional Connections for the local control station if present The local control station allows for local operation of the actuator putting the Servo NXT EIP into Local Mode and over...

Page 10: ...wner connection shall transition to steady green when any subsequent Exclusive Owner connection is established Devices that support multiple Exclusive Owner connections shall retain the O T connection...

Page 11: ...and the other switch has a wire disconnected then this fault will also occur 4 4 7 2 Handwheel Fault This red LED is on if a handwheel fault is active This occurs if the handwheel is detected to be in...

Page 12: ...gnificantly more detail on the concerns and requirements for successfully establishing and managing a functional EtherNet IP network This list is not exhaustive and there are many more references avai...

Page 13: ...ges should be configured based on the Connection Manager attributes defined in the EDS file The EDS file provides limits for implicit messaging to ensure the device maintains reliable generation of da...

Page 14: ...edback position positive values only 0 20 Stroke Time REAL 32 Time in seconds the last full stroke took to complete positive values only 0 24 Motor Operating Time REAL 32 Time in hours that the motor...

Page 15: ...ating in the open direction 6 Autocalibration Running BOOL 1 Set high when actuator is running through the calibration routine 7 PST Running BOOL 1 Set high when actuator is running through the partia...

Page 16: ...e actuator attempts to operate a load outside the operational torque limits 3 Motor Stall Fault BOOL 1 Dynamic Fault Set high in the event of motor stall no motor movement detected 5 Autocalibration F...

Page 17: ...BOOL 1 Toggle Bit Change bit state to operate the actuator to PST offset position to test device operability 2 4 Partial Stroke Test Stop BOOL 1 Toggle Bit Change bit state to cancel an ongoing partia...

Page 18: ...t Open Speed REAL 32 Percent of max speed the motor should run at in the open direction Range 10 100 Default 100 0 16 Open Speed Start Position REAL 32 Position where open speed limiting should begin...

Page 19: ...L 1 When high inverts input feedback position range Default Low 1 Enable Actuator Speed Limiting BOOL 1 Set high to enable speed limiting for the range specified Default Low 2 Enable Torque Limiting B...

Page 20: ...and set it to use the address set in memory 4 Establish that explicit messages can be exchanged with the Servo NXT EIP through the network scanner a Data received should align with the information co...

Page 21: ...PC ABS Blend Mounting Screw Material Nylon Terminals Wire Gauge 26 16 AWG 0 13 1 31 mm2 Torque Limit 3 5 in lbs 15 6 N Voltage Limit 200 V Current Limit 5 A Switch Force 0 79 lbf 3 5 N Temperature Rat...

Page 22: ...skestra e 25 47877 Willich Germany Tel 49 2154 8875 0 ENERGY Mining Oil Gas Power FGD Nuclear Power INDUSTRIAL Chemical Pulp Paper Textile Marine WATER Water Wastewater Ultra Pure Water Desalination I...

Reviews: