SERIES 6A ELECTROPNEUMATIC POSITIONER
QUICK START GUIDE
8 of 12
© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM The Information
contained herein shall not be copied, transferred, conveyed, or displayed in any manner that would
violate its proprietary nature without the express written permission of Bray International, Inc.
2.0
CALIBRATION (continued)
Step 9
Step 9: Press the Menu Button
for
5 seconds. The device will now be in
‘MANUAL’ mode.
Step 10
Step 10: Use the
or
buttons to
manually close or open the valve to
ensure that the desired travel limits are
being attained.
Step 11
Step 11: Toggle between Manual (“MAN”)
and ‘AUTO’ mode by pressing the
Menu Button
.
Step 12
Step 12: While in ‘AUTO’ mode, test the
responsiveness of the device by varying
the command signal from 4 mA to
20 mA.