SERIES 6A ELECTROPNEUMATIC POSITIONER
QUICK START GUIDE
11 of 12
© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM The Information
contained herein shall not be copied, transferred, conveyed, or displayed in any manner that would
violate its proprietary nature without the express written permission of Bray International, Inc.
4.0
POSITIONER OPTIMIZATION (Continued)
Step 5
Use the Menu Button
to scroll to
parameter 41 (YCUP, full open).
Step 6
Change the parameter to the desired
upper limit for full open.
Example
: If the positioner is at 85% or
higher, the actuator provides full force
open.
Step 7
Exit Configuration mode by pressing the
Menu Button
for >5 seconds. The
device will be in Manual Mode (“MAN’).
Press the Menu Button
once to
leave the positioner in AUTO mode.