Braeburn 140404 Installation Manual Download Page 12

No.   Installer Setting 

Display  

Factory   

Setting 

Comments

     (

Notes follow table)

  

Indicator 

Default 

Options

 

(More information follows this table)

11    Short Cycle Protection      

SCP

 

    

5

 

  

 

to

 0

  

Selects a compressor short cycle protection delay of 5,

             

           

      

  

   

 

4, 3, 2 or zero minutes after a compressor call

12     Outdoor Sensor Compressor    

COM BAL

      

NO 

  

  NO   

Disables Compressor Balance Point Control

        Balance Point 

            

      

   

   

to

 50

 

Selects a Compressor Balance Point of 0 to 50° F

          

   

            

      

   

    

 

[Note 1, 2]

13     Outdoor  Sensor Auxiliary     

AUX BAL       NO 

  

  NO

,  

Disables Auxiliary Heat Balance Point Control 

       Heat Balance Point 

            

      

  

  

40 

to

70

  Selects an Auxiliary Heat Balance Point of 40 to 70° F

          

   

            

      

   

    

 

[Note 1, 2]

 

14     Equipment  Staging 

    

STAGING       ZON 

  

  ZON 

 

Select to stage on number of zones calling (Setting 15)

          

   

            

      

   

 

 TIM

   

Select to stage on Zone Panel Timer

          

   

            

      

   

 

 TST

   

Select to stage on Thermostat Staging Calls 

[Note 8]

15    Equipment Staging Lock     

STAGLOK      2

 

        

- # of 

Selects the number of zones that must call before the 

             

           

      

        zones  

equipment will upstage Zone Count (setting 14 = ZON)

16     Second Stage Fan Control      

G2 FAN       ZON 

  

  ZON  

Select to Turn on Second Stage Fan on number of calling 

          

   

            

      

   

    

 

zones  (Setting  17)

          

   

            

      

   

 

 STG

  

Select to Turn on Second Stage Fan when second stage 

          

   

            

      

   

    

 

is  activated

17    Second Stage Fan  

    

G2 ZONES    2 

         2 

- # of  

Select the number of zones that must call before the 

             

           

      

        zones  

second stage fan will turn on

18     Priority  Zone 

    

PRIORTY       1 

  

OFF   

Select to have opposite calls answered in any zone

          

   

            

          

   

to 

4  

Select zone 1 to 4 to limit calls so equipment will only 

             

           

      

  

   

 

service call matching last call of zone 1-4  

19     Opposite  Mode Timer 

    

OP MODE

      

15

  

  

15 

to

 60

 

Select the number of minutes to delay system changeover 

             

           

      

  

   

 

when zones are calling for heat and others zones are 

          

   

            

      

   

    

 

calling  for  cooling. 

20     Zone  to Activate 

   

 EM HEAT       1  

  

NO   

Select to allow Emergency Heat from Thermostats

        Emergency  Heat 

            

      

   

to

 4

  

Select to match the Zone on the main panel allowed to

          

   

            

      

   

    

 

call  emergency  heat. 

[Note 3]

 

21     Fire Alarm 

    FIRE ALM      NI 

  

NI   

Select for a normally inactive (Open) fire relay

 

  

       Normal Active /  

           

      

  

NA

  

Select for a normally active (Closed) fire relay

        Normal  Inactive 

            

      

   

    

 

[Note 4]

12

NOTES - Configuration

[1]

 Only available if MSH system type is selected.

[2]

 Only available if outdoor sensor is connected.

[3]

 Thermostat type must be heat pump.

[4]

 All equipment and fans will shut down and all dampers will power close

[5] 

Disable will not show plenum temperature and will prevent staging by temperature.

[6]

 Only available if supply air sensor is enabled.

[7]

 O/B selection on equipment must match thermostat O/B selection.

[8] 

Multi-stage thermostats must be used.

[9]

 Set thermostats to conventional.

Summary of Contents for 140404

Page 1: ...he entire panel before applying transformer power This panel is designed for professional installation and is to be installed and configured as described in this manual Any other use is not recommende...

Page 2: ...lectronic self resetting current limiting for panel power and damper zones Configuration Conventional and Heat Pump equipment up to 4 Heating Stages and 2 Cooling Stages Maximum Zones 4 Zones Main Pan...

Page 3: ...aster installations Figure 2 3 EM HEAT R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 1 PO COMM PC DAMPER ZONE 1 R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 2 DAMPER ZONE 2 PO COMM...

Page 4: ...op of wiring terminal and gently pull out wire s EM HEAT R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 1 PO COMM PC DAMPER ZONE 1 R Y1 Y2 W1 E AX1 W2 AX2 O B W3 G L C T HERMOSTAT Z ONE 2 DAMP...

Page 5: ...PUT 2nd Stage Compressor G 1 OUTPUT 1st Stage Fan Control G2 1 OUTPUT 2nd Stage Fan Control W1 E AX1 1 OUTPUT W1 1st Stage Conventional Heat E Emergency Heat AX1 1st Stage Auxiliary Heat W2 AX2 1 OUTP...

Page 6: ...ne Panel 2 Wire Damper PO C PC PO COM PC Zone Panel 3 Wire Damper Thermostat Wiring 3 2 Install the system thermostats using the instructions provided by the manufacturer Connect the thermostats to th...

Page 7: ...eat Call G Fan Call C 24 VAC Transformer Common Note 1 3 HEAT 2 COOL With Auxiliary Heat R 24 VAC Power O B Changeover Valve Note 2 L Optional System Fault Monitor AX1 Auxiliary Heat Relay 3rd Stage H...

Page 8: ...panel as shown For a single stage heating and cooling system the 2nd and 3rd stage connections are not used For a system using a dual transformer remove jumper Rc to Rh see Figure 3 page 4 Make sure...

Page 9: ...Power Heating Transformer Rc Connected to Rh with Jumper O B Changeover Valve Note 4 L Optional System Fault Monitor W2 Auxiliary Heat Relay 2nd Stage Heating Note 5 Y1 Compressor Call Stage 1 1st St...

Page 10: ...ms you will need to make configuration changes described in this section To start configuration 1 Press SETUP and hold for 3 seconds 10 2 The panel backlight will turn on and the display will change 3...

Page 11: ...trol REV VAL O O Select for cool active reversing valve B Select for heat active reversing valve Note 7 6 Auxiliary Stage COMP LOC OFF OFF Select for Compressor runs with Auxiliary Heat Call Compresso...

Page 12: ...ted 17 Second Stage Fan G2 ZONES 2 2 of Select the number of zones that must call before the zones second stage fan will turn on 18 Priority Zone PRIORTY 1 OFF Select to have opposite calls answered i...

Page 13: ...municating properly the display will show the zone number and OK If the zone is not communicating properly the display will show Address Invalid or Duplicate Address See Error Conditions section 7 for...

Page 14: ...PC This test powers all dampers open or closed Press SELECT to test or NEXT to advance to return to first test LED COLOR INDICATION Panel Status LED Panel Power Green Flashing Green When Normal Equip...

Page 15: ...D s the expandable zone panel has a full function built in backlit display panel that provides information on the current operations of the zone panel When the expandable zone panel is running in norm...

Page 16: ...o cooling calls will be answered if emergency heat is switched on To select Emergency Heat from the main panel 1 Press and release the EM HEAT button located below the main display 2 The display will...

Page 17: ...un Delay HI Limit Displayed when the Plenum Temperature is exceeded during equipment heating operation All heating stages will be turned off and the fan will be turned on until the plenum temperature...

Page 18: ...an expansion panel This message will appear when an expander is powered up and wired to the communication terminals To locate the expander panel with the invalid address view the expander panel status...

Page 19: ...anel display 4 If new zones do not appear check wiring and ensure expansion zones have power 5 Press HOLD FOR EXIT for 3 seconds to complete adding zones The expansion zones may be wired to either the...

Page 20: ...es 5 6 Expander Panel Zones 7 8 Expander Panel As Needed Daisy Chain All Zones Located at Main Panel Star Wiring All Zones Located at Main Panel Main Panel Expander Panel Zones 7 8 Expander Panel Zone...

Page 21: ...Panel Zones 7 8 500 Ft Maximum 21 Main Panel Expander Panel Zones 5 6 Expander Panel As Needed 500 Ft Maximum Expander Panel As Needed Expander Panel As Needed Daisy Chain Zones Located Remote to Mai...

Page 22: ...opy of this warranty Visit us online www braeburnonline com warranty Phone us 866 268 5599 Write us Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 5YEAR WARRANTY LIMITED Braeburn Systems...

Reviews: