Installation 

S19-130F

Bradley Corporation • 

215-152CO Rev. P; ECN 08-512 

9/11/08

Installation

Supplies Required:

•  Teflon tape and pipe sealant
•  Piping to 1" NPT water supply inlet
•  Adequate supply pipe supports
•  Appropriate hardware to mount pulley to wall
•  Minimum 4" (102 mm) drain to accommodate 

30 gallons (115 liters) per minute discharge for 
shower waste

• Sign-mounting hardware

Step 1: Assemble components

1.  Assemble components as shown on page 4.

•  Apply pipe sealant or tape (by installer) to 

all male-threaded pipe joints.

•  Bottom edge of showerhead should be 7'-

0" (2134 mm) from the floor.

Step 2: Connect water supply

IMPORTANT:  Do not rely on Bradley’s 
Drench Shower to support supply 
piping.

1.  Connect water supply piping to 1" NPT inlet 

on unit (piping supplied by installer). Provide 
adequate supports (supplied by installer) 
for supply pipe using pipe hangers or other 
means.

2.  Mount the pulley and the eye screw to the 

wall (pulley hardware supplied by installer).

3.  Secure one end of the nylon cord to the “S” 

hook on the eyewash valve handle. Feed the 
cord through the pulley and then secure it to 
the eye screw.

4.  Mount the safety sign to the wall using sign-

mounting hardware supplied by installer.

5.  Open water supply lines. Test for leaks and 

adequate water flow.

4"

(102mm)

8.7"

(221mm)

 

Ø 3.

1"

(78.7mm)

24" 

(610mm)

7'-0"

(2134mm) 
Suggested 

Height to 

Floor

3'-0"

(914mm) 

to Floor

Summary of Contents for S19-130F

Page 1: ...00 272 3539 FAX 262 251 5817 bradleycorp com Installation 215 152CO Rev P ECN 08 512 2008 Bradley Corporation Page 1 of 4 9 11 08 S19 130F Drench Shower Cord Operated Table of Contents Pre Installation Information 2 Installation 3 S19 130F Components and Parts List 4 ...

Page 2: ...operation This equipment should be inspected annually to ensure compliance with ANSI Z358 1 Workers who may come in contact with potentially hazardous materials should be trained regarding the placement and proper operation of emergency equipment per ANSI Z358 1 For questions regarding the operation or installation of this product visit www bradleycorp com or call 1 800 BRADLEY Product warranties ...

Page 3: ... floor Step 2 Connect water supply IMPORTANT Do not rely on Bradley s Drench Shower to support supply piping 1 Connect water supply piping to 1 NPT inlet on unit piping supplied by installer Provide adequate supports supplied by installer for supply pipe using pipe hangers or other means 2 Mount the pulley and the eye screw to the wall pulley hardware supplied by installer 3 Secure one end of the ...

Page 4: ...7 1 Coupling 1 NPT Item Part No Qty Description Item Part No Qty Description 2 5 2 4 2 3 2 2 2 11 5 2 1 3 1 1 7 4 6 P O BOX 309 MENOMONEE FALLS WI 53052 0309 USA TEL 1 800 BRADLEY FAX 262 251 5817 http www bradleycorp com 114 050 8 P O Box 309 Menomonee Falls WI 53051 R TEST THIS UNIT EACH WEEK Test operate valve s each week and sign below Report any malfunctions immediately Ventil e wöchentlich i...

Reviews: