5
Express® Lavatory System SS-Series
Installation - Obsolete
SS-2/AST/STD, SS-2/AST/JUV
Bradley Corporation • 215-1244 Rev. D; EN 08-805
4/24/08
Installation Instructions
Step 1: Rough in
Note: See Figure 1a below (for Standard Height) and Figure 1b on page 6 (for Juvenile Height)
when roughing in the Express®.
IMPORTANT: Flush the supply lines before making connections. Debris in supply
lines can cause the valves to malfunction.
IMPORTANT: Dimensions shown in Figure 1a are for Standard Height and in
Figure 1a for Juvenile Height.
1. Rough in 1/2" NPT hot and cold supply lines through wall at dimensions shown.
2. Rough in 1-1/2" NPT drain waste connection through wall at dimensions shown.
3. Install (6) 3/8" wall anchors with a minimum pull-out rating of 1,000 lbs. (supplied by
installer) at the locations shown in Figures 1a and 1b.
(MM)
32"
(813)
28-5/8"
(727)
25"
(635)
11-3/8"
(289)
(6) 3/8" WALL
ANCHORS WITH
MINIMUM PULLOUT
RATING OF 1,000
LBS.
23-1/2"
(597)
9-3/8"
(238)
2-3/4"
(70)
1"
(25)
23-1/2"
(597)
9-3/8"
(238)
1/2" NPT HOT AND
COLD SUPPLIES,
OR TEMPERED
SUPPLY - STUB
OUT 2" (50) FROM
WALL
FINISHED
FLOOR
CENTERLINE
15-1/4"
(387)
1-1/2" NPT DRAIN -
STUB OUT 2" (50)
FROM WALL
Figure 1a
Installation Instructions continue . . .
3"
(76)
SS-2/AST/STD Express® Lavatory System Dimensions
Standard Height Mounting