EFX 125/S19-2300
Installation
4
4/17/2014
Bradley
•215-1594Rev.D;ECN14-09-007
2
Connect Supply Lines and Install Thermometer
3
Adjust Temperature with Water Running
When the check valves are in the
open (opera ting) position, the cover
screw for the stop/check stem will
be flush with the valve cap.
Check for leaks by pressurizing
unit SLOWLY.
Install Thermometer using pipe
sealant or teflon tape.
Check the temperature when approximately 20 GPM
water flow is reached (equivalent to one drench shower).
Slotted Cover
Screw
Stop/Check
Cover Screw
Check
Stop Nut
Water Recirculation
Plug
Thermometer
Tempered
Water (to
Fixture)
HOT
COLD
Slotted Cover
Screw
Temperature Set
Screw
C
H
4
Test Unit
Shutthehotwatersupplyoffbyclosinghotwaterinletvalveorsupplycheckvalve.Whilethehotwatersupplyisturnedoff,
checktomakesurethecoldwatercontinuestoflow.Ifthecoldwaterisflowingproperly,reopenthehotwatersupply.
Shutthecoldwatersupplyoffbyclosingthecoldwaterinletvalveorsupplycheckvalve.Whilethecoldwatersupplyisoff,
checktomakesurethatthehotwaterflowhasshutdown.Ifhotwaterisshutdown,reopencoldwatersupply.Testunit
weeklyforproperfunctionanddesiredsettemperature.
DO NOT SKIP THIS STEP!!!
This device must be checked for final temperature and adjusted as
necessary. The standard preset factory temperature setting is 85°F
(29°C).
[the range of the valve is 65°F–95°F (18°C–35°C)].
Consult
proper medical and/or safety authorities for the optimum temperature
recommended for your particular application.
5/32" Allen Wrench