15

Gas Connections 

 

The gas supply lines must meet all requirements of the National Fuel Gas Code 
(ANSI Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas 
Installation Code (Latest Edition) or CAN/CGA B149.2 Propane Installation Code 
(Latest Edition). 
 
The minimum permissible gas supply pressure for the purpose of input adjustment 
is one (1.0) inch 

(0.25 kPa) 

water column above the operating manifold pressure.  

See the rating plate and gas valve for the manifold pressure and gas type.  The 
maximum permissible gas supply pressure is fourteen (14.0) inches 

(3.5 kPa)

 water 

column for natural gas and liquefied petroleum gases/propane gas. 

 

1.  Connect this water heater only to the type of gas (Natural or Propane gas) as 

shown on the rating plate.  Use clean black iron pipe or equivalent material 
approved by local codes and ordinances. (Dirt and scale from the pipe can 
enter the gas valve and cause it to malfunction).  The inlet gas line must have a 
minimum length of three (3) inches 

(7.6 cm)

 drip leg 

(sediment trap) 

installed as 

close to the water heater’s gas valve as possible.  A ground joint union must be 
installed as close to the water heater as possible in the gas supply line feeding 
the water heater to permit servicing of the water heater. Compounds used on 
the threaded joints of the gas piping must be resistant to the action of liquefied 
petroleum gases/propane gas.  DO NOT apply pipe dope to the gas valve inlet 
and make certain that no pipe dope has become lodged in the inlet screen of 
the gas valve.  Extreme care must be taken to ensure no pipe dope enters the 
gas valve.  Avoid excessive torque when tightening the gas supply line to the 
gas valve.  Excessive torque may result in cracking of the gas valve housing 
and could create a gas leak.  When tightening gas supply line to L.P. control, it 
is recommended to hold the inlet body of the control securely with an adequate 
wrench.  The suggested maximum torque is 31.5 ft. lbs. (4.4 kg-m).   

 

2.  This water heater and its gas connection must be leak tested before placing the 

water heater in operation.  Check for gas leaks with a soap and water solution 
and a brush or a commercial leak detector fluid. 

NEVER USE A MATCH OR 

OPEN FLAME FOR TESTING!

 

 

3.  While checking for leaks care must be taken to prevent solution from  

contacting the electrical connections at the control. If electrical connections at 
the control become wet, they must be thoroughly dried before attempting to 
operate the water heater. 

 

WARNING 

The manufacturer of this water heater will not be liable for any damage or 
injury caused as a result of a cracked gas inlet as a result of excessive 
torque.

 

 

CAUTION 

The water heater and individual shutoff valve must be disconnected from the 
gas supply piping system during any pressure testing of the system at test 
pressures in excess of 1/2 psi (3.5 kPa).  The water heater must be isolated 
from the gas supply piping system by closing its manual shutoff valve during any 
pressure testing of the gas supply system at test pressures equal to or less than 
1/2 psi (3.5 kPa).  The supply line must be capped when not connected to the 
water heater. 

Summary of Contents for RG2DVMH30T6X-264

Page 1: ...nstalled and serviced by a plumbing professional MANUFACTURED HOME MOBILE HOME CLOSED COMBUSTION DIRECT VENTING INSTALLATION AND OPERATING INSTRUCTION MANUAL FOR YOUR SAFETY Do not store or use gasoli...

Page 2: ...installation of this water heater We require that you carefully read this manual as well as the enclosed warranty and refer to it when questions arise If you have any specific questions concerning you...

Page 3: ...arances 8 Drain Pan Installation 9 Combustion Air Supply 10 Venting 11 Water Connections 12 Gas Connections 15 Gas Conversion Instructions 16 GENERAL OPERATION 20 Lighting and Shutdown Instructions 21...

Page 4: ...ntake tube and heater tie down materials These components for field installation may have been shipped with this heater and must be installed according to these instructions see figure 1 No other comp...

Page 5: ...tionally the water heater should be flushed with appropriate dissolvers to eliminate any bacteria INSTALLATION Locating the Water Heater This water heater MUST NOT be installed in any location where g...

Page 6: ...ature and pressure relief valve WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored against the water heater or vent air intake system and p...

Page 7: ...eater is to be a Sealed to the floor with sealant in a smooth and easily cleanable way or b Installed with an optional leg kit that includes legs and or extensions that provide a minimum clearance of...

Page 8: ...r wood panel or equivalent extending beyond the full width and depth of the appliance by at least 3 inches 7 6 cm in any direction or if the appliance is to be installed in an alcove or closet the ent...

Page 9: ...final installation 4 Align drain pan hole with hole cut in floor and underside sheathing for air intake 5 Apply 4 diameter circle of silicone around bottom of air intake plate and screws used to secu...

Page 10: ...yellow luminous burner flame causing carboning or sooting of the combustion chamber burners and flue tubes with possible damage to the heater AIR INTAKE INSTALLATION 3 7 6cm diameter telescoping air...

Page 11: ...e fastened to the top of the water heater and to the adjacent walls with the screws provided See Figure 5 Venting Make certain the flue baffle is in place and centered in the flue tube Cut a 7 1 4 inc...

Page 12: ...let and hot water outlet are dielectric waterway fittings with 3 4 NPT male thread Make the proper plumbing connections between the water heater and the plumbing system to the house Install a shut off...

Page 13: ...Vacuum Relief Valves The combination temperature and pressure relief valve must be marked with a maximum set pressure not to exceed the maximum working pressure of the water heater The combination te...

Page 14: ...e tank for a long period of time generally two weeks or more Hydrogen gas is extremely flammable To prevent the possibility of injury under these conditions we recommend the hot water faucet to be ope...

Page 15: ...dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive torque when tightening the gas supply line to the gas...

Page 16: ...or by removing cap from gas regulator Depress and rotate knob clockwise to NAT setting using a screwdriver Replace cap Figure 6 3 Change the pilot regulator by removing pilot regulator cap Depress and...

Page 17: ...provided with the water heater 2 Change the main gas regulator to LP as noted in step 2 of the instructions 3 Change the pilot regulator to LP as noted in step 3 of the instructions 4 Replace equipped...

Page 18: ...igure 7 only 1 Follow the instructions above except remove cap from gas regulator and depress and rotate plunger counterclockwise 2 Remove main burner orifice and pilot assembly and replace with RED c...

Page 19: ...cedure 9 To light pilot follow the lighting instructions provided on the water heater and in this installation and operation instruction manual 10 Remove equipped for card from cloth bag and attach to...

Page 20: ...e gas control knob clockwise to the OFF position OR for the Robertshaw control rotate the gas control knob clockwise to the OFF position 3 Shut off the gas supply to the water heater 4 Close the cold...

Page 21: ...21 Lighting and Shutdown Instructions...

Page 22: ...al until the minimum acceptable temperature is achieved See Figure 9 above for approximate temperature settings Figure 10 The thermostat dial is set to its lowest temperature setting when shipped from...

Page 23: ...thermostat dial It is suggested that the starting point setting not be greater than the mark on the thermostat dial approximately 120 F 48 9 C as pictured above Rotate the thermostat dial clockwise to...

Page 24: ...the water system This valve will reduce point of discharge temperature by mixing cold and hot water in branch water lines A licensed plumbing professional or local plumbing authority should be consult...

Page 25: ...tion temperature and pressure relief valve to insure that the valve has not become encrusted with lime Lift the lever at the lever at the top of the valve several times until the valve seats properly...

Page 26: ...E WATER HEATER ARE WARRANTED Manufactured under one or more of the following U S Patents 5 277 171 5 341 770 5 372 185 5 485 879 5 574 822 5 596 952 5 660 165 5 682 666 5 761 379 5 943 984 5 954 492 5...

Page 27: ...27 TYPICAL INSTALLATION...

Page 28: ...oor 2 Jacket Top 13 Convertible gas control valve 3 Fiberglass Insulation 14 Pilot Assembly 4 Glass Lined Tank 15 Gas Feed Line Burner 5 Tank Skirt Assembly 16 Main Burner Orifice 6 Jacket Base Assemb...

Reviews: