Bradford White BRUTE DELUXE BMT2H Installation And Operation Instructions Manual Download Page 28

Page 28

 

Bradford White Corp

5.  The Brute Deluxe will enter the start sequence, 

as long as the unit is being called for heat. The 

blower and pump come on for pre-purge, then 

the ignitor warm-up sequence starts and after the 

ignitor warm-up is complete and all safety devices 

are verified, the gas valves open. If ignition doesn’t 

occur, check that there is proper gas supply. Wait 5 

minutes and start the unit again. During initial start 

up, air in the gas line may cause the Brute Deluxe 

to "lock out" during the first few trials for ignition. 

Depending on the ignition modules installed, the 

manual reset button on the ignition modules may 

need to be depressed to restart the Brute Deluxe.

6.  When the unit is running, the supply gas pressure 

must be checked. Inlet gas pressure must not 

exceed 13" W.C. (3.2kPa). The minimum inlet gas 

pressure is 5" W.C. (1.2kPa).

7.  Once the inlet gas pressure is verified, the 

outlet gas pressure from each valve (manifold 

gas pressure) must be checked, and adjusted, if 

necessary. The manifold gas pressure must be 2.5" 

W.C. (0.62kPa).

8.  Complete the setup by checking the CO

2

 at the 

outlet of the unit. The CO

2

 should be 8% for natural 

gas, or 9.2% for propane.

9.  After placing the appliance in operation, the 

Burner Safety Shutoff Device must be tested

.

 

(a)  Close gas shutoff valve with burner operating.

 

(b)  The flame will go out and blower will 

continue to run for the post purge cycle. 

One additional attempt to light will follow. 

Ignition will not occur as the gas is off. The 

ignition control will lockout, and will have to 

be reset before the unit will operate.

 

(c)  Open gas shutoff valve. Restart the appliance. 

The ignition sequence will start again and the 

burner will start. The appliance will return to 

its previous mode of operation.

NOTE:

 Unit sizes 1000–2000 have two ignition controls 

and two ignitors, which work independently of one 

another. If the ignition control for stage 1 fails to properly 

light the main burners for that stage, the second ignition 

control will still be active, and will be able to energize 

stage 2. This, of course, will only occur upon call for 

stage 2 and if all other safety devices confirm that the 

unit will run in a safe condition.

6.6.2  High Altitude Adjustment and Set Up

Brute Deluxe appliances may be operated at high 

altitude (7700 ft., 2347 m) with a reduction in output 

of approximately 10%. At altitudes of less than or 

more than 7700 ft. (2347 m) the appliance will perform 

equally as well, but with differing reductions in output. 

At elevations higher than 7700 ft. (2347 m) the reduction 

in output will exceed 10% and at elevations below 7700 

ft. (2347 m) it will be less than 10%. High altitude 

adjustment must not be made on appliances operating at 

elevations below 2500 ft. (762 m).

and to replace any part of the control system and any 

gas control that may have been  

under water.

6.3  Operating Temperature Control

All Brute Deluxe's are equipped with a two-stage 

aquastat. To utilize this mounted controller be sure to 

have the "Local/Remote" selector switch to "Local". 

Set the controller to the desired operating set point. 

The controller has an interstage differential that can be 

adjusted from 3°F to 10°F. This allows the user to have 

some control over how stage 2 and stage 1 call for heat 

(

see Figure 22

).

Because the Brute Deluxe controller senses inlet 

water and the manual reset high limit senses outlet water, 

the high limit should be set 40-50°F higher than the 

controller, to avoid nuisance lockout of the manual reset 

high limit.

6.4  External Boiler Operations

If controlling the stages of the BMT2 from an 

external source (multiple boiler control, BAS, etc) the 

"Local/Remote" selector switch above the terminal 

strip must be placed in the "Remote" position. In this 

mode, the controller that is mounted on the BMT2 will 

no longer have control of the unit. The 24V from the 

unit waits at the input terminal, and the external control 

switches this 24V from the input terminal to the stage 

terminal.

6.5  Limit Controls

The manual reset high limit control is provided 

as standard equipment on all heaters. An additional 

automatic reset switch is optional.A high limit 

temperature-sensing bulb is always located in the heater 

outlet. Burners will automatically shut down whenever 

overheating occurs.

6.6  Operating the Burner and Set Up

 

6.6.1 Set Up for 0 to 2500 Feet Altitude

The Brute Deluxe appliance utilizes a modular 

design to achieve its stage-firing. The setup must be 

checked before the unit is put in operation. Problems 

such as failure to start, rough ignition, strong exhaust 

odors, etc. can be due to improper setup. Damage to 

the Brute Deluxe resulting from improper setup is not 

covered by the limited warranty.

1.  Using this manual, make sure the installation 

is complete and fully in compliance with the 

instructions.

2.  Determine that the appliance and system are filled 

with water and all air has been bled from both. 

Open all valves.

3.  Observe all warnings on the Operating Instructions 

label and turn on gas and electrical power to 

appliance.

4.  Switch on the appliance power switch located on 

the right side of the unit.

Summary of Contents for BRUTE DELUXE BMT2H

Page 1: ...r d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne to...

Page 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Page 3: ...White factory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Brute Delux...

Page 4: ...ry items are shipped in separate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or d...

Page 5: ...ump is sized for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensi...

Page 6: ...gure 2 Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL A...

Page 7: ...ings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors th...

Page 8: ...he vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I F...

Page 9: ...appliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that v...

Page 10: ...t 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent shal...

Page 11: ...ight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half in...

Page 12: ...fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Foll...

Page 13: ...ring any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during an...

Page 14: ...he system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size boiler Pump mounted boilers c...

Page 15: ...including copper if the water is moved too quickly The water flow requirements for the Brute Deluxe water heater are based upon the hardness of the water The water flow is kept high enough to prevent...

Page 16: ...Page 16 Bradford White Corp Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Page 17: ...Page 17 Brute Deluxe 500 2000 Install Operating Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Page 18: ...Page 18 Bradford White Corp Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Page 19: ...Page 19 Brute Deluxe 500 2000 Install Operating Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Page 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Page 21: ...rk on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded boiler Single pole switches including those of safety controls and protective devices must not be wi...

Page 22: ...BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67 J...

Page 23: ...Page 23 Brute Deluxe 500 2000 Install Operating Figure 19 Brute Deluxe 500 750 Connection Diagram...

Page 24: ...Page 24 Bradford White Corp Figure 20 Brute Deluxe 1000 Connection Diagram...

Page 25: ...K W L2 LOAD 1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator...

Page 26: ...tiple boiler control BAS etc wire Stage 1 to the terminals marked Input Stage 1 and Stage 1 and wire Stage 2 to the terminals marked Input Stage 2 and Stage 2 The Local Remote selector switch above th...

Page 27: ...ll bleeding devices and open make up water valve Allow system to fill slowly 2 If make up water pump is employed adjust pressure switch on pumping system to provide a minimum of 12 psi 81 8 kPa at the...

Page 28: ...but with differing reductions in output At elevations higher than 7700 ft 2347 m the reduction in output will exceed 10 and at elevations below 7700 ft 2347 m it will be less than 10 High altitude adj...

Page 29: ...ist in these adjustments are a CO2 or O2 Analyzer and a U Tube Manometer or other device capable of reading a pressure of 2 5 3 0 inches W C 0 62 0 75 kPa Start the adjustment process by checking the...

Page 30: ...ore and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff valve and 120 volt power and check a...

Page 31: ...al gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 D...

Page 32: ...esentative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water heater is oper...

Page 33: ...F3015 5F3015 5F3015 13 Cover Housing Pump 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 5F3016 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2 2 2 2 2 2 2 Internal Compo...

Page 34: ...2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Page 35: ...59 Low Water Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter...

Page 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F70...

Page 37: ...Page 37 Brute Deluxe 500 2000 Install Operating Figure 23 Sheet Metal Components...

Page 38: ...Page 38 Bradford White Corp Figure 24 Internal Components...

Page 39: ...001800 1250 A2001800 1500 A2001900 1750 A2001900 2000 A2109700 Brute Deluxe Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900...

Page 40: ...Bradford White Corporation reserves the right to change specifications components features or to discontinue products without notice 200 Lafayette St Middleville MI 49333 Warranty 800 531 2111 www Br...

Reviews: