56
ENGLISH
APPENDIX A
ITALIANO
Table 6:
C23 parameter - Function of output 8.
VALUE
DESCRIPTION
0
No function.
1
Fan logic; relay closed when the proportional fan is on.
2
Reversed fan logic; relay closed when the proportional fan
is off.
3
Valve logic; relay closed when the valve is opened.
4
Reversed valve logic; relay closed when the valve is closed.
5
ON/OFF logic; relay closed when the thermostat is turned on.
6
Reversed ON/OFF logic; relay closed when the thermostat is
turned off.
7
Economy logic; relay closed when the thermostat is in
economy mode or is turned off.
8
Reversed economy logic; relay closed when the thermostat is
turned on and it is not in economy mode.
9
Heating/cooling logic; relay closed when the thermostat is in
heating mode.
10
Reversed heating/cooling logic; relay closed when the
thermostat is in cooling mode.
VALUE
DESCRIPTION
11
Input 3 repeat; relay closed when the input 3 is closed.
12
Input 3 reversed repeat; relay closed when the input 3 is
opened.
13
Input 4 repeat; relay closed when the input 4 is closed.
14
Input 4 reversed repeat; relay closed when the input 4 is
opened.
15
Input 16 repeat; relay closed when the input 16 is closed.
16
Input 16 reversed repeat; relay closed when the input 16 is
opened.