44
Service menu
Sense II – 6 720 818 367 (2015/10)
Thermal disinfection
Perform thermal disinfection to kill off pathogens (e.g.
legionella) on a regular basis. For larger DHW systems, there
may be legal requirements (
regulation on drinking water) for
thermal disinfection. Observe the instructions in the technical
documentation of the heat source.
•
Yes
:
– The entire DHW volume is heated to the set
temperature once a week or once a day according to
the settings.
– The thermal disinfection starts automatically at the set
time according to the time set in the controller.
– It is possible to cancel and to manually start the thermal
disinfection.
•
No
: The thermal disinfection is not started automatically. It
is possible to manually start the thermal disinfection.
7.3
Solar system settings
Fig. 29
Solar settings menu
If a solar system is integrated into the heating system via an MS
module, corresponding menus and menu items are available.
An extension of the menus by the solar system is described in
the operating instructions of the relevant solar module.
In the
Solar settings
menu
with all solar systems
the sub-
menus listed in Tab. 25 are available.
Daily heat-up
Yes
The daily heat-up is only available for DHW heating with an MM 100/MM 200 module
or EMS 2 heat source. The entire DHW volume is automatically heated up daily at the
same time to the temperature that has been set via Daily heat-up temp. The heat-up is
not performed, if within 12 h before the set time, the DHW volume was already heated
up at least once to the set temperature (e.g. due to solar yield).
No
No daily heat-up.
Daily heat-up temp.
60
... 80 °C
Temperature to which the DHW volume is heated up during the daily heat-up.
Daily heat-up time
00:00 ...
02:00
... 23:45
Time for the start of the daily heat-up.
Menu item
Adjustment
range
description
Table 24 Settings in the DHW system I – II menu
WARNING:
Risk of scalding!
During thermal disinfection, the domestic hot
water is heated to above 60 °C.
▶ Only carry out thermal disinfection
outside normal hours of use.
▶ Inform all parties concerned and make
sure that at mixer is installed.
6 720 815 238-04.1O
WARNING:
Risk of scalding!
▶ If DHW temperatures above 60 °C are set
or thermal disinfection is switched on, a
mixer must be installed.
NOTICE:
System damage
▶ Fill and vent the solar system prior to
commissioning.
If the area of the installed solar collectors is
incorrectly set, the solar yield displayed in the
info menu is wrong as well.
Menu item
Purpose of the menu
Solar thermal sys
installed
If Yes is set here, the other settings are
displayed.
Change solar
configuration
Graphical configuration of the solar
system
Current solar
configuration
Graphical representation of the
configured solar system
Solar parameters
Settings for the installed solar system
Start solar thermal
system
Once all the required parameters have
been set, the solar system can be
started.
Table 25 General settings for the solar system